6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 658 -
map the input-point to the Object references having
attributes CO and CF†. Figure 4.4-16 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” and “CF”
stands for “Configuration” in the functional constraint (FC).
Table 4.4-6 Mapping signals required for SPCSO object of GGIO3302
Object_reference
Attribute Type
FC
Signal Number
Signal Name
Ctrl/GGIO3302$SPCSO1$Oper
ctlVal
BOOLEAN
CO
529001 700C016D08
OPTR01_CONTROL_REQ
Ctrl/GGIO3302$SPCSO1$Oper
ctlNum
INT8U
CO
Ctrl/GGIO3302$SPCSO1$Oper
T
Timestamp
CO
Ctrl/GGIO3302$SPCSO1$Oper
Test
BOOLEAN
CO
Ctrl/GGIO3302$SPCSO1$Oper
Check
Check
CO
Ctrl/GGIO3302$SPCSO1$Oper$origin
orCat
orCategory
CO
Ctrl/GGIO3302$SPCSO1$Oper$origin
orIdent
Octet64
CO
Ctrl/GGIO3302$SPCSO1
ctlModel
ctlModel
CF
Ctrl/GGIO3302$SPCSO1
sboClass
sboClass
CF
Check “Input”
Figure 4.4-16 Input-point mapped for GGIO3302
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......