4.4.4
Mapping for IEC61850 communication
The user can operate the OPTIM function over the IEC61850 communication after the
mapping using the GR-TIEMS. Note that the OPTIM function is designed for “Single Point
Controller (SPC) class” in the IEC61850 communication. The user should follow steps:
Step1:
Editing Logical Node
Step2:
Mapping output data
Step3:
Mapping input data
(i)
Editing Logical Node
The user should make a logical node (LN) for the OPTIM function. Figure 4.4-12 exemplifies
LN editing; the LN “General Input / Output (GGIO)” is chosen for the OPTIM function. After
the user defining an object “SPCSO”, the OPTIM logical node can be saved with the name
“GIGO” plus “LN Instance”. Make a definition of the object “SPCSO” in the OPTIM logical node.
“Either the SBO mode or the DIR mode can be chosen in the LN editing.
SBO defined in LN
Figure 4.4-12 Defining “SPCSO” object in GIGO3302 logic node
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......