6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 552 -
(ii)
Receiving “select command Open” from the remote-end
Figure 4.2-3 outlines the reception of the select command ‘Open’ from the remote-end.
Signal reception
IEC61850
Select command Open from the remote-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Closing from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-3 Outline of select command for Open
Input point required mapping
Figure 4.2-4 shows the select logic when a “Select command (Remote-Open-Control)” signal is
applied to the DPSY01 function. The input-point “DEV01_CONTROL_REQ” is used for the
reception of the “select command (Remote-Open-Control)” signal.
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
DPSY01 function (Function ID:
511001)
DEV01_CONTROL_REQ
Command
“Remote-Open-Control”
ILK
†
condition (“Open”) passed
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
In SBO operate
In DIR operate
Select
“Failed”
511001
_
7002016D08
DPSY01-Open
To BO connection
Input
Output
Selection logic in DPSY01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Select
“success”
“Automatic sequence control function (ASEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
1
≥
Select command
with ILK
†
condition
Operate command
with ILK
†
condition
Select command
without ILK
†
condition
Operate command
without ILK
†
condition
For SBO operation
For DIR operation
To
“Wait for a command”
For DIR operation
For SBO operation
Figure 4.2-4 Select ‘Open’ from the remote-end in DPSY01
††
†Note: The ILK function can provide the operation criteria for “Open”.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......