6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 503 -
(iv)
Receiving “Select command Off” from the local-end
Figure 4.1-7 outlines the reception of the select command ‘Off’ from the local-end.
Signal reception
from the front panel
Select command Off from front panel
Signal output
Select
decision
Success
Failed
Selection logic
Selection logics
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command On from remote-end
Select command On from front panel
Select command On by the PLC
Select command Off by the PLC
Select command Off from remote-end
Figure 4.1-7 Outline of select command ‘Off’
Input signal generated at the local-end.
Figure 4.1-8 shows the select logic when a “Select command Off (Local-OFF-Control)” signal is
applied to the SPOS01 function. The signal is provided when the user presses a “OFF” key on
the IED front panel; the user is not required to map the signal from IEC61850 communication.
Input
Output
Select logic in SPOS01
Command
“Local-Off-Control”
1≥
[
SPOS01-CTRAHMI
]
SBO
SPOS01 function (Function ID:
510001)
SBO
DIR
&
&
1≥
&
0.1s
0
0.6s
0
SPOS01-Off
ILK
†
condition (“Off”) passed
ILK
†
bypassing
(
“Interlock Bypass”)
ICB_STATE
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
t
t
“SPOS01_FSL_BO_CSF”
(510001
_
8601011DC6)
Selection
“Failed”
To BO connection
Selection
“success”
To
“Wait for a command”
Select condition
‡
Select command
with ILK
†
condition
Operate command
with ILK
†
condition
For SBO operation
For DIR operation
Figure 4.1-8 Select ‘Off’ on the front panel in SPOS01
††
†
Note: The software interlocking (ILK) function can provide the operation criteria for
“Off”. The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...