2.11.1
Stub-OC characteristic
The characteristic of the stub-OC element is shown as a circle that has a center at the origin,
as shown in Figure 2.11-2. The user can set the threshold value of the stub-OC element using
setting [
OCSTUB
]. The STUB-OC function can operate when the user set scheme switch
[
STUB
]
On
.
I
0
I
Figure 2.11-2 Characteristic of stub-OC
2.11.2
Scheme logic
Figure 2.11-3 shows the stub-OC logic; the stub-OC function can issue trip signals during the
DS being opened (i.e., logic signal ‘DS_OPEN’ = 1 (TRUE1)).
8200011C22
8000011C20
8100011C21
OCSTUB
A
B
C
≥1
ICD-B
ICD-C
&
&
&
ICD-A
DS_OPEN
≥1
800000EBB0 STUBOC_BLOCK
From PROT COMMON
STUBOC-EN
On
&
&
&
≥1
≥1
≥1
&
≥1
&
&
&
STUBOC-2PBlk
Block-PerP
Block-3P
From ICD
STUB-Test
On
&
OCSTUB-OR
STUBOC-TRIP
STUBOC-TRIP-A
STUBOC-TRIP-B
≥1
To TRC
To Recording
STUBOC-TRIP-C
8000001B60
&
8000001B20
8100001B21
8200001B22
&
8300001B23
STUBOC-TRIP
STUBOC-ARC-BLOCK
STUBOC-OPT-A
STUBOC-OPT-B
STUBOC-OPT-C
1
Figure 2.11-3 Scheme logic in STUB function
Scheme switch [
OCSTUB-2fBlk
] is provided in order that the OCSTBU element should
be blocked when second-harmonic frequency components (2f) are detected on the flowing
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......