6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1294 -
(iii)
Time synchronization
Time synchronization source can be selected in Time synchronization screen. The
synchronization function can be activated by configuration of the On/Off switch in this menu.
Figure 12.7-7 shows the configuration screen for the time synchronization function:
Figure 12.7-7 Time synchronization setting
The following shows how to operate in this screen.
TimeSyncSrc menu
Time SyncSrc (Time Synchronization Source) can be changed by the following procedure.
Figure 12.7-8 TimeSyncSrc
(1) Move cursor to the TimeSyncSrc menu and press
ENTER
.
(2) The TimeSyncSrc menu is composed of SNTP, BI, and IRIG-B.
Note: When “---” is selected, it means that time synchronization
is not operated.
By using time synchronization via Ethernet with a SNTP server, the user can connect up
to a maximum of four SNTP servers. If more than one SNTP is used, the priority of the servers
can be decided in ascending order of synchronized stratum value (in order of higher-accuracy)
and select the server with the smallest value.
Time Sync
10:48
1/3
_TimeSyncSrc
+
SNTP
SNTP
+>
On
BI SYNC
+>
Off
TimeSyncSrc
10:48
1/4
---
_SNTP
BI
IRIG-B
Time Sync
10:48
1/3
TimeSyncSrc
+
SNTP
SNTP
+>
On
BI SYNC
+>
Off
IRIG SYNC
+>
Off
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......