6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1139 -
10.4.3
Setting
Setting of SIGMA_IY (Function ID: 713001)
Setting item
Range
Units
Contents
Default setting value
Note
s
SIGMA_IY-EN
Off / On
—
Enabling Sigma Iy function operation
Off
SIGMA_IY-AEN
Off / On
—
Enabling Sigma Iy alarming
Off
SIGMA_IY-Alarm
1.0 to 100000000.0
—
Alarm level in Sigma Iy function
10000.0
SIGMA_IY-Y
1.0 to 2.0
—
Y parameter for in Sigma Iy
1.0
Setting of CHK_SGMIY (Function ID: 223A01 to 223A03)
Setting item
Range
Contents
Default
setting
value
Notes
CHK_SGMIY-A:Sw
Off / On
Enable switch
On
CHK_SGMIY-A:Lvl
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
Warning
Error level
Minor error
CHK_SGMIY-B:Sw
Off / On
Enable switch
On
CHK_SGMIY-B:Lvl
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
Warning
Error level
Minor error
CHK_SGMIY-C:Sw
Off / On
Enable switch
On
CHK_SGMIY-C:Lvl
--- / Serious error / Serious error(Comm) / Minor error / Alarm/
Warning
Error level
Minor error
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......