Timer variable settings using PLC drivers
The user can set variable timers of user’s PLC logics using settings of PLC drivers (FB:
PLC_DRV 230302). The LCD screen menu provides settings [
UTM1
] ~ [
UTM24
], and the user
can set those timer values through the LCD screen.
Figure 7.4-1 shows that a delay timer “TON1” has been set 500ms in the PLC logic, but the
user can set new value using the setting [
UTM1
] (e.g., the user can change 500ms to 200ms on
the LCD). Since an internal IED memory is able to access the [
UTM1
], the IED can operate
with new value of the [
UTM1
] when new one is set.
IED memory
A timer value inputted
( 500 [ms] or 200 [ms] )
Timer FB
Constant value set
Fixed PLC =
5
00ms
PLC driver FB
Function ID: 230302
Element ID:
3200013001
Variable value set
Setting
[
UTM1
]
= 200 ms
=
5000ms
PLC editor
PLC function
User PLC logic
Input
Output
Figure 7.4-1 Time delay FB is adjusted by setting [UTM1] (example)
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......