TIC-LF470B 

 

 

5

 

 

 

Terminal board 

Connected detector

IV wire 

5.5 mm

2

 or more 

Power switch

(External double-pole power switch ) 

Thick walled steel conduit

Signal cable 

Power cable

(CVV) 

Digital input cable

(CVV-S) 

Current output (4~20mAdc) 
or PROFIBUS 

Grounded with 100

or less 

ground resistance 

(2-wire shielded hard-rubber

sheathed cable) 

(3-wire shielded hard-rubber cable)

Digital output 1 
Signal common for DI and DO

Digital output 2 
 
Digital input 

(20~30Vdc) 

Power supply 

[Instrument panel : ordered separately]

 

Figure 6.    Separate type LF470/LF612 flowmeters wiring Diagram 

 

Table 1. LF612 Converters Signal Table 

Symbol Description 

Cable 

L1 (

L2 (

Power supply 

Power cable (CVV) 

GND 

Ground (for arrester) 

 

FG Frame 

ground 

 

DI 

Digital Input (20

30Vdc) 

DO1 

Digital Output 1 

DO2 

Digital Output 2 

COM 

Signal Common for DI, DO1, DO2

 

 

 

Current Output (4

20mAdc) 

or PROFIBUS 

 

I/O cable (CVV-S) 

X  
Y Excitation 

Output 

E  

Excitation cable   

A  
B Signal 

Input 

G  

Signal cable   

 

 

Separate type LF470/LF612 flowmeter 

Excitation cable 

 

Grounded with 100

or less 

ground resistance 

 

Grounded with 100

or less 

ground resistance 

 

Summary of Contents for Electromagnetic Flowmeter LF470/LF612

Page 1: ...icator can be used to communicate with the flowmeter from a remote place PROFIBUS PA 3 interface is available as an option 1 Please refer to the document TIC LF232 2 HARTprotocol Highway Addressable Remote Transducer is a communication protocol for industrial sensors recommended by the HCF HARTCommunication Foundation 3 PROFIBUS is the communication protocol for factory and process automation that...

Page 2: ...for current and pulse outputs Zero adjustment Executes zero adjustment on stream at zero flow rate Output signals Current output 4 20mAdc load resistance 0 to 750Ω Note The current output cannot be used with the PROFIBUS PA communication Digital outputs One point std and one more point is optionally available as follows Digital output DO1 std Output type Transistor open collector Number of outputs...

Page 3: ...nal Corp Conditions when power fails Parameter setting values are stored in non volatile memory and the values will be restored when the power returns to normal condition The outputs and display will remain as follows when power fails Current output 0mAdc Digital output OFF LCD display No display PROFIBUS No communication Power supply One of the following can be selected 100 to 240Vac 50 60Hz std ...

Page 4: ...39 86 2 φ0 24 φ6 hole 4 φ0 20 φ5 hole Detector mounting plate 4mm thick Mountingscrews 1 18 30 1 57 40 Figure4 LF470 Mounting Board 矢視A 信号ケーブル グランド 電源ケーブルグランド 封止栓 励磁ケーブルグランド 電流出力ケーブルグランド 接地端子 M4 取付金具 4 φ 11 取付金具 82 36 156 13 151 178 200 151 74 0 3 25 LCD 表示器 赤外線スイッチ Excitation cable ground 5 94 151 5 94 151 2 91 74 4 φ0 43 φ11 Attachment LCD display 7 01 178 7 87 200 IR Switch Cable ground 6 14 15...

Page 5: ...l input 20 30Vdc Power supply Instrument panel ordered separately Figure 6 Separate type LF470 LF612 flowmeters wiring Diagram Table 1 LF612 Converters Signal Table Symbol Description Cable L1 L2 Power supply Power cable CVV GND Ground for arrester FG Frame ground DI Digital Input 20 30Vdc DO1 Digital Output 1 DO2 Digital Output 2 COM Signal Common for DI DO1 DO2 Current Output 4 20mAdc or PROFIBU...

Page 6: ...60 4 482 Table 3 Meter size and Flow Velocity US unit Unit L min Meter size mm 0 3m s 1m s 3m s 10m s 2 5 0 08835 0 2945 0 884 2 945 4 0 2262 0 7540 2 262 7 540 6 0 5088 1 6967 5 090 16 967 About establishment environment Do not store or install the flowmeter Where there is direct sunlight Where excessive vibration or mechanical shock occurs Where high temperature or high humidity conditions exist...

Page 7: ...l chloride shock resistance Pt Ir for grounding plate H Hastelloy C Equivalent Packing used between main body and pipe connection adapter C Acid resistant ceramic D Alkali resistant ceramic G Ammonia resistance Mounting A Not provided B Provided 304 stainless steel Flow and calibration velocity range A 1 0 to 32 8 ft s standard range calibration B 1 0 to 32 8 ft s specified range calibration Cable...

Page 8: ...ting BNP material SUS304 Accessory for pipe installation BNP material SUS304 1 2 Digital input output Digital output points 1 DO1 Digital output points 2 DO1 DO2 Digital input point 1 DI 1 2 Current output and Communication function Current output HART communication PROFIBUS communication Current output is not usable 1 2 3 Power supply 100Vac 240Vac 50 60Hz 24Vdc 110Vdc E Instruction manual Englis...

Reviews: