background image

 

 

 

 

 

 

 

 

TIC-LF470B 

 

Field Intelligent Device Series 

Electromagnetic Flowmeter 

LF470/LF612 

1/10",1/6”,1/4" (2.5,4,6mm )

 

Introduction

 

The electromagnetic flowmeter uses Faraday’s Law of 

electromagnetic induction to measure the process flow. 

The device consists of two units: a detector, through 

which

 

the

 

fluid

 

to

 

be

 

measured

 

flows

 

and

 

in

 

which

 

low-level signals proportional to flow rates are obtained; 

and a converter, which supplies excitation current to the

 

detector,

 

and

 

amplifies

 

the

 

signals

 

from

 

the

 

detector and

 

then

 

processes

 

and

 

converts

 

the

 

signals

 

into

 

the

 

4–20

 

mA

 

dc current

 

signal. The LF470 is a small meter size 

detector designed to measure a small amount of fluids 

containing substances such as chemicals. 

The wetted materials for the LF470 are corrosion 

resistant ceramic and platinum electrods and are 

applicable to almost any kind of fluids. The LF470 is a 

lightweight palm-sized detector.Combined with 

multi-functional converter LF612 (separate type) and 

LF232*

1

 (separate type) equipped with its patented 

Noise-Sentry

 original noise-suppression circuit and 

advanced algorithms. The LF470 is highly resistant to 

noise and provides a stable output even for fluids 

containing slurries. IR (Infrared) switches enable 

parameter setting of the converter without removing the 

cover. Flow direction can be set in either way, and its 

unique 128 x 128 dot matrix LCD    display allows the 

LCD to be rotated electronically to be rotated to 90, 180 

and 270 degrees without opening the cover 

The AF900 hand-held terminal (HART*

communicator) 

can be used to communicate with the flowmeter from a 

remote place. PROFIBUS-PA*

  interface is available 

as an option. 

*1: Please refer to the document ”TIC-LF232”. 

*2: HART protocol (Highway Addressable Remote 

Transducer) is a communication protocol for industrial 

sensors recommended by the HCF

 

(HART

 

Communication

 

Foundation). 

*3: PROFIBUS is the communication protocol for factory   

and process automation that the PROFIBUS Organization 

recommends. Instead of analog control with a 

conventional analog signal (4-20mA), it is the fieldbus 

which digitizes all signals. Flowmeters support 

PROFIBUS-PA. 

 

 
 
 
 
 
 

 
 
 
 

Figure 2.  Electromagnetic Flowmeter 

LF470/LF612 

 

 

 

 

Specifications

 

 

Overall Specifications 

Measurement range in terms of flow velocity:

 

0–1.0ft/s to 0–32.8ft/s (0–0.3 m/s to 0–10 m/s ) 

Accuracy: 

The overall accuracy combined with the 

LF612 or LF232 converter is shown in the 
following table. 

Accuracy 

Flow rate as a 

percent of range

1.0-3.3ft/s  

(0.3-1.0m/s ) 

3.3-32.8ft/s  

(1.0-10m/s ) 

50

100

 

±

0.8% of FS 

±

0.8% of rate

0

50

 

±

0.8% of FS 

±

0.4% of FS 

Note:

 The accuracy is measured under standard 

operating conditions at Toshiba's calibration facility. 

Fluid conductivity: 

50µS/cm minimum 

Fluid temperature:

 

Pipe connection material Fluid 

temperature

Stainless steel and other metals 

14 to 248 °F 

(

10

℃〜+

120

Polyvinyl chloride 
(shock-resistant) 

14 to 140 °F 

(

10

℃〜+

60

Ambient temperature: 

14

 

to

 

140

 

°F (–10 to +60

 

°C

 

Structure: 

IP67 

Power consumption: 

  ・

When combined with the LF612 converter: 

       approximately 12W (20VA) 
   

When combined with the LF232 converter: 

       approximately 14W (25VA) 

Fluid to be
measured 

Signal cable 

Excitation cable 

Power supply 

4-20mA dc output
and pulse output 

Figure 1. Configuration Diagram 

LF470

 

LF612

 

Certification number

 

Z01207

 

LF612 or LF232  
Converter

 

LF470 
Detector

 

Summary of Contents for Electromagnetic Flowmeter LF470/LF612

Page 1: ...icator can be used to communicate with the flowmeter from a remote place PROFIBUS PA 3 interface is available as an option 1 Please refer to the document TIC LF232 2 HARTprotocol Highway Addressable Remote Transducer is a communication protocol for industrial sensors recommended by the HCF HARTCommunication Foundation 3 PROFIBUS is the communication protocol for factory and process automation that...

Page 2: ...for current and pulse outputs Zero adjustment Executes zero adjustment on stream at zero flow rate Output signals Current output 4 20mAdc load resistance 0 to 750Ω Note The current output cannot be used with the PROFIBUS PA communication Digital outputs One point std and one more point is optionally available as follows Digital output DO1 std Output type Transistor open collector Number of outputs...

Page 3: ...nal Corp Conditions when power fails Parameter setting values are stored in non volatile memory and the values will be restored when the power returns to normal condition The outputs and display will remain as follows when power fails Current output 0mAdc Digital output OFF LCD display No display PROFIBUS No communication Power supply One of the following can be selected 100 to 240Vac 50 60Hz std ...

Page 4: ...39 86 2 φ0 24 φ6 hole 4 φ0 20 φ5 hole Detector mounting plate 4mm thick Mountingscrews 1 18 30 1 57 40 Figure4 LF470 Mounting Board 矢視A 信号ケーブル グランド 電源ケーブルグランド 封止栓 励磁ケーブルグランド 電流出力ケーブルグランド 接地端子 M4 取付金具 4 φ 11 取付金具 82 36 156 13 151 178 200 151 74 0 3 25 LCD 表示器 赤外線スイッチ Excitation cable ground 5 94 151 5 94 151 2 91 74 4 φ0 43 φ11 Attachment LCD display 7 01 178 7 87 200 IR Switch Cable ground 6 14 15...

Page 5: ...l input 20 30Vdc Power supply Instrument panel ordered separately Figure 6 Separate type LF470 LF612 flowmeters wiring Diagram Table 1 LF612 Converters Signal Table Symbol Description Cable L1 L2 Power supply Power cable CVV GND Ground for arrester FG Frame ground DI Digital Input 20 30Vdc DO1 Digital Output 1 DO2 Digital Output 2 COM Signal Common for DI DO1 DO2 Current Output 4 20mAdc or PROFIBU...

Page 6: ...60 4 482 Table 3 Meter size and Flow Velocity US unit Unit L min Meter size mm 0 3m s 1m s 3m s 10m s 2 5 0 08835 0 2945 0 884 2 945 4 0 2262 0 7540 2 262 7 540 6 0 5088 1 6967 5 090 16 967 About establishment environment Do not store or install the flowmeter Where there is direct sunlight Where excessive vibration or mechanical shock occurs Where high temperature or high humidity conditions exist...

Page 7: ...l chloride shock resistance Pt Ir for grounding plate H Hastelloy C Equivalent Packing used between main body and pipe connection adapter C Acid resistant ceramic D Alkali resistant ceramic G Ammonia resistance Mounting A Not provided B Provided 304 stainless steel Flow and calibration velocity range A 1 0 to 32 8 ft s standard range calibration B 1 0 to 32 8 ft s specified range calibration Cable...

Page 8: ...ting BNP material SUS304 Accessory for pipe installation BNP material SUS304 1 2 Digital input output Digital output points 1 DO1 Digital output points 2 DO1 DO2 Digital input point 1 DI 1 2 Current output and Communication function Current output HART communication PROFIBUS communication Current output is not usable 1 2 3 Power supply 100Vac 240Vac 50 60Hz 24Vdc 110Vdc E Instruction manual Englis...

Reviews: