![Toshiba E3 Manual Download Page 27](http://html.mh-extra.com/html/toshiba/e3/e3_manual_424641027.webp)
26
10. NCU DDL File
Below is a Data Definition Language (DDL) file for the EIII Metasys direct N2 bus
interface which can be input to an N2 Network Controller Unit (NCU).
An electronic version of this file can be downloaded via the internet from
http://www.iccdesigns.com
.
********************************************************
** Toshiba EIII Adjustable Speed Drive **
********************************************************
CSMODEL "EIII","VND"
AITITLE "Analog Inputs"
BITITLE "Binary Inputs"
AOTITLE "Analog Outputs"
BOTITLE "Binary Outputs"
CSAI "AI1",N,N,"OUT FREQ","HZ"
CSAI "AI2",N,N,"CURRENT","%"
CSAI "AI3",N,N,"OUT VOLT","%"
CSAI "AI4",N,N,"INP VOLT","%"
CSAI "AI5",N,N,"IV INPUT","%"
CSAI "AI6",N,N,"RR INPUT","%"
CSAI "AI7",N,N,"RX INPUT","%"
CSAI "AI8",N,N,"INP POWR","kW"
CSAI "AI9",N,N,"OUT POWR","kW"
CSAI "AI10",N,N,"ENERGY k","kWh"
CSAI "AI11",N,N,"ENERGY M","MWh"
CSAI "AI12",N,N,"NOW FLT","CODE"
CSAI "AI13",N,N,"1ST FLT","CODE"
CSAI "AI14",N,N,"2ND FLT","CODE"
CSAI "AI15",N,N,"3RD FLT","CODE"
CSAI "AI16",N,N,"4TH FLT","CODE"
CSBI "BI1,N,N,”RUN STAT”,”STOP”,”RUN”
CSBI "BI2,N,N,”F/R STAT”,”REV”,”FWD”
CSBI "BI3,N,N,”ACC STAT”,”#1”,”#2”
CSBI "BI4,N,N,”INJ STAT”,”OFF”,”ON”
CSBI "BI5”,N,N,”CST STAT”,”NORMAL”,”COAST”
CSBI "BI6”,N,N,”E STAT”,”NORMAL”,”EOFF”
CSBI "BI7”,N,N,”FLT STAT”,”NORMAL”,”FAULT”
CSBI "BI8”,N,N,”FB STAT”,”DISABL”,”ENABL”
CSBI "BI9”,N,N,”F TERM”,”OPEN”,”CLOSED”
CSBI "BI10”,N,N,”R TERM”,”OPEN”,”CLOSED”
CSBI "BI11”,N,N,”S1 TERM”,”OPEN”,”CLOSED”
CSBI "BI12”,N,N,”S2 TERM”,”OPEN”,”CLOSED”
CSBI "BI13”,N,N,”S3 TERM”,”OPEN”,”CLOSED”
CSBI "BI14”,N,N,”S4 TERM”,”OPEN”,”CLOSED”
CSBI "BI15”,N,N,”RES TERM”,”OPEN”,”CLOSED”
Summary of Contents for E3
Page 5: ...4 This page intentionally left blank ...
Page 29: ...28 11 Notes ...