Toshiba E3 Specifications Download Page 3

 

M.

 

The drive shall have an adjustable retry function after a fault.  Both number of 
attempts (at least 10) and time between  (1-10 sec). 

N.

 

The drive shall have an adjustable output short circuit detection selection for 
standard motor and high-speed motors (very low inductance). 

O.

 

The drive shall have two programmable: volt per hertz patterns, maximum output 
frequencies, electronic thermal protection settings, stall protections, base 
frequencies, voltage boosts, and stall protection selections which can be chosen 
while running to run motor A or motor B. 

P.

 

The drive shall have an analog input filter adjustment to limit the effects of noise 
on the control signal. 

Q.

 

The drive shall permit switching between local/remote operation as well as 
manual/auto “on the fly.” 

R.

 

The drive shall have the ability to ignore run commands until a “dampers open” 
signal is received. In the event a “dampers open” signal is absent the drive shall 
be capable providing a “close damper” signal.  Upon receipt of “drive stop” signal 
The ASD shall be capable of providing a close damper signal.  

S.

 

The drive shall be provided with “anti-windmilling” or “motor shaft stationary 
control” 

T.

 

The drive shall have the following user selectable contingencies in the event of 
loss of analog control signal while the drive is running before loss: 

i.

 

Run at the user set lower frequency limit. 

ii.

 

Run at the user set upper frequency limit. 

iii.

 

Trip with a signal loss fault.  

iv.

 

Run at user-selected percentage of the last valid frequency signal. 

 

2.4

 

Operational Functions 

 

A.

 

The drive shall contain two separate acceleration/deceleration times with auto 
tuning for optimum setting (0.1 to 6000 seconds) with choice of linear, S, or C 
curves. 

B.

 

The drive shall be equipped with both local/remote and manual/auto keys on 
touch pad. 

C.

 

The drive shall be equipped with a quick setup key with 18 most frequently 
parameters in a HVAC type application. 

D.

 

The drive shall contain fifteen preset speeds, which can be activated from the 
keypad, terminal inputs, and host computer. 

E.

 

The drive shall have the capability of storable special custom user setting

.

 

F.

 

The drive shall restart into a rotating motor operating in either the forward or 
reverse direction and match that frequency. 

G.

 

The drive shall have adjustable soft stall (10% - 150%) which reduces frequency 
and voltage of the inverter to sustain a run in an overload situation. 

H.

 

The drive shall be capable of performing a time base pattern run using 4 groups of 
8 patterns each using the 15 preset speed values for a maximum of 32 different 
patterns. 

Summary of Contents for E3

Page 1: ...ionnaire E ISO 9001 1 2 Submittal Submittals shall include Toshiba standard operation manual Schematics can be obtained from factory upon request PART 2 E3 VARIABLE FREQUENCY DRIVE 2 0 General A This specification covers AC adjustable frequency drives for HVAC applications B The manufacturer shall not have less than fifteen years of experience in the manufacture of VFD s C The manufacturer shall m...

Page 2: ... Control with Automatic energy saving control B The drive shall have two 2 frequency priority selection feature C The drive shall be capable of setting both upper and lower limit frequencies D The ASD shall automatically adjust the PWM carrier frequency proportional to speed The range of automatic adjustment shall vary from 15khz to 5khz The minimum acceptable full speed carrier frequency 60 Hz wi...

Page 3: ...the following user selectable contingencies in the event of loss of analog control signal while the drive is running before loss i Run at the user set lower frequency limit ii Run at the user set upper frequency limit iii Trip with a signal loss fault iv Run at user selected percentage of the last valid frequency signal 2 4 Operational Functions A The drive shall contain two separate acceleration ...

Page 4: ...pulse train output proportional to frequency 48 96 360 times frequency 2 6 Protective Features A The drive shall contain three critical frequency jump points with individual bandwidth B The drive shall be UL rated for 200 000 AIC without the use of input fuses C All drives 460V 25HP and above shall be equipped with a 3 impedance DC link D The drive shall have external fault input E The drive shall...

Page 5: ...erter overheat trip 17 Emergency off trip message 18 EEPROM failure during write cycle 19 EEPROM abnormality during initial reading 20 RAM error 21 ROM error 22 CPU error 23 Communication interruption error 24 Gate array error 25 Output current detection circuit error 26 Option PCB error trip 27 Low operating current trip 28 Main circuit under voltage trip 29 Over torque trip 30 Software detected ...

Page 6: ... all parameters to factory default settings or user defaults whichever one is chosen H The drive shall have an elapsed time meter and will save the past four faults in memory 2 8 Optional features A 12 pulse diode rectification for maximum harmonics attenuation shall be available for 460V drives 25HP through 100HP B Pneumatic interface 3 15psi transducers are available upon request C Isolated inpu...

Page 7: ...um Part 3 Start up Training and Warranty A Start up and service is available as an additional option B The drive manufacturer shall guarantee the operation of the drive against failure due to defects for 30 months after shipment or 24 months of service whichever comes first C If factory authorized personnel perform the startup of the drive the standard warranty is increased to 24 months D The driv...