Direct Access Parameter Information
https://www.toshiba.com/tic/
235
My Function Time Data 2
Program
My Function
My Function Data
This parameter is used to set the response delay of the My Func
-
tion Time Data 2 terminal.
The applied discrete input signal must be present at the input ter
-
minal of the Q9 Plus ASD for the time setting here for a system
response.
Discrete terminal input activation that does not equal or exceed
this setting will be ignored.
Direct Access Number —
F929
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 3
Program
My Function
My Function Data
This parameter is used to set the response delay of the My Func
-
tion Time Data 3 terminal.
The applied discrete input signal must be present at the input ter
-
minal of the Q9 Plus ASD for the time setting here for a system
response.
Discrete terminal input activation that does not equal or exceed
this setting will be ignored.
Direct Access Number —
F930
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 4
Program
My Function
My Function Data
This parameter is used to set the response delay of the My Func
-
tion Time Data 4 terminal.
The applied discrete input signal must be present at the input ter
-
minal of the Q9 Plus ASD for the time setting here for a system
response.
Discrete terminal input activation that does not equal or exceed
this setting will be ignored.
Direct Access Number —
F931
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 5
Program
My Function
My Function Data
This parameter is used to set the response delay of the My Func
-
tion Time Data 5 terminal.
The applied discrete input signal must be present at the input ter
-
minal of the Q9 Plus ASD for the time setting here for a system
response.
Discrete terminal input activation that does not equal or exceed
this setting will be ignored.
Direct Access Number —
F932
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......