Direct Access Parameter Information
https://www.toshiba.com/tic/
209
Integral Output Power Retention
Program
Utilities
Display Parameters
This parameter is used to set the disposition of the kWh meter
reading at power off.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number —
F748
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Integral Output Power Display Unit
Program
Utilities
Display Parameters
This parameter sets the unit of measure for the power/time
display.
Settings:
0 — 1=1 kWh
1 — 1=10 kWh
2 — 1=100 kWh
3 — 1=1000 kWh
4 — 1=10000 kWh
Direct Access Number —
F749
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
MAC Address 1
Program
Communications
Ethernet Settings
This parameter is used to configure the MAC Address 1
section of the MAC address of the device.
Direct Access Number —
F784
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 255
MAC
Address 1