Fresh-air inlet box

Installation Manual

3

Installing the duct

• Perform the indentation ventilation on the Fresh-air 

inlet box using the duct fan shown in the right figure.

CAUTION

• Confirm the processed outside air should be ranged 

from 54°F to 86°F (12 to 30°C).

• Confirm the sound insulation chamber is installed.

4

Duct fan wiring

• The interlock wiring should be applied between the duct fan and the indoor unit ventilator.

Insert the connector to CN60 on the main P.C. board of the indoor unit and connect the duct fan driving relay 
(DC12V).
The thick line (

) shows the connection circuit.

• After installing the duct, perform the test run to confirm whether the duct fan and the ventilation of the indoor 

unit work starting or stopping at the same timing. (For the test run, following to the instructions described on 
the indoor unit installation manual.)

Indoor unit

Fresh-air 
chamber

Sound 
insulation 
chamber

Duct fan

Outside air filter

Processed 
outside air

Fresh-air inlet box

CN60

Tighten the clamp with the (9) 
wire and the remote control wire.

Draw the (9) wire in the same way 
as remote controller wire. Pull out 
an end of the wire from the indoor 
unit frame.

Closed end connector

Closed end connector

Main control 
P.C. board 
MCC-1570

Duct fan drive relay

208/230V AC

Duct fan

(White)

RELAY

(9) Wire

5-EN

+00EH99678601_01EN_FreshAirInletBox-IM.book  Page 5  Tuesday, December 8, 2009  2:03 PM

Summary of Contents for Carrier TCB-GB1602UUL

Page 1: ...PLIT TYPE Fresh Air Inlet Box for 4 way Air Discharge Cassette Type Model name Fresh air inlet box TCB GB1602UUL Installation Manual Installation Manual Fresh air inlet box 1 English Manuel d installation Boîte d entrée d air frais 7 Français ...

Page 2: ... require hospitalization or long term treatment as an outpatient 2 Physical damage indicates the damage relating to the property material CAUTION ON INSTALLATION WARNING Use TOSHIBA Carrier products for the parts sold separately Use the products specified by TOSHIBA Carrier for the parts sold separately such as the fresh air chamber ceiling panel etc The use of the products other than specified ma...

Page 3: ...the 9 wire if a duct fan locally procured is installed 2 Attach the Fresh air chamber to the indoor unit For the details refer to the Fresh air chamber installation manual 3 Remove the shield plate for box from the Fresh air chamber Fig 1 4 Remove the shield plate assembly from the Fresh air chamber This part will be attached back later Fig 1 Indoor unit RAV SP 0UT UL Fresh air chamber TCB GFC1602...

Page 4: ...0Attach back the shield plate assembly removed in 3 4 as it was installed 11Fix the wind shield 7 to the position where the suction grille is removed as shown in the Fig 3 with 2 mounting screws 4 If the wind shield is not fixed it is impossible to control the room temperature This may cause improper operation CAUTION Be sure to provide the opening for inspection on the Fresh air inlet box side Th...

Page 5: ...ible duct to the external side of the flange circle and fix it by using a band at 1 to 1 2 25 to 30 mm position from the edge of the flexible duct 2 Sealing the connection port Wrap the tightening band with the heat insulating materials of 0 79 20 mm thickness or more Apply the adhesive tape around the heat insulating materials of the connection port to prevent the heat insulating materials from p...

Page 6: ...hick line shows the connection circuit After installing the duct perform the test run to confirm whether the duct fan and the ventilation of the indoor unit work starting or stopping at the same timing For the test run following to the instructions described on the indoor unit installation manual Indoor unit Fresh air chamber Sound insulation chamber Duct fan Outside air filter Processed outside a...

Page 7: ... 6 Fresh air inlet box Installation Manual EN MEMO ...

Page 8: ...EH99678601 1 ...

Reviews: