SPECIAL INSTRUCTIONS—CONTROLS
TEST RUN
Before turning on the power supply, carry out the following procedure.
1. Using 500V-Megger, check the resistance between the terminal block of the power supply
and the earth (grounding). The resistance must by 1MΩ or more.
2. If resistance of less than 1MΩ is detected, do not run the unit.
When a test run is performed together with air conditioners, follow the installation manuals of the
air conditioners.
Never press the electromagnetic contactor to forcibly perform the test run. (This would be very
dangerous because the protective device does not work).
Before starting a test run, be sure to set addresses per the installation manual supplied with the
outdoor unit.
Preparation
1. Push the
[
MENU ]
button to display the menu
screen.
2. Push and hold the
[
MENU ]
button and the
[
]
button at the same tine to display the “Field
setting menu”.
Push and hold the buttons for more than 4 seconds.
3. Select “1 Test mode” on the “Field setting menu” screen,
then push the “Set”
[
F2 ]
button.
Pushing the “Yes”
[
F1 ]
button sets the test
mode and the screen returns to the “Filed setting
menu” screen.
Push
[
CANCEL ]
twice, the screen (2)
appears.
Performing the test mode
1. Test Mode
2. Register service info.
3. Alarm history
4. Monitor function
5. Setting louver position
Summary of Contents for Carrier MMD-AP0180VHG2UL
Page 2: ...035 000051 001 Page 2 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 4: ...035 000051 001 Page 4 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 6: ...035 000051 001 Page 6 of 60 MMD IOM 1 2 11 10 2020 PRODUCT NOMENCLATURE ...
Page 27: ...035 000051 001 Page 27 of 60 MMD IOM 1 2 11 10 2020 AIRFLOW PERFORMANCE ...
Page 31: ...035 000051 001 Page 31 of 60 MMD IOM 1 2 11 10 2020 SPECIAL FACTORY OPTIONS ...
Page 42: ...035 000051 001 Page 42 of 60 MMD IOM 1 2 11 10 2020 SPECIAL INSTRUCTIONS CONTROLS ...
Page 43: ...035 000051 001 Page 43 of 60 MMD IOM 1 2 11 10 2020 SPECIAL INSTRUCTIONS CONTROLS ...
Page 46: ...035 000051 001 Page 46 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 47: ...035 000051 001 Page 47 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 48: ...035 000051 001 Page 48 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 49: ...035 000051 001 Page 49 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 50: ...035 000051 001 Page 50 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 51: ...035 000051 001 Page 51 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 52: ...035 000051 001 Page 52 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 53: ...035 000051 001 Page 53 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 54: ...035 000051 001 Page 54 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 55: ...035 000051 001 Page 55 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS 19 ...
Page 56: ...035 000051 001 Page 56 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...035 000051 001 Page 58 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 59: ...035 000051 001 Page 59 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...