Toshiba BMS-TP0641ACE Installation Manual Download Page 2

1

Precautions for Safety

• Read these "Precautions for Safety" carefully before installation.

• The precautions described below include important items regarding safety. Observe them without fail.

• After the installation work, perform a trial operation to check for any problem. Follow the Owner's

Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this
Installation Manual together with the Owner's Manual.

• Ask an authorized dealer or qualified installation professional to install or reinstall the Touch

Screen Controller.

Improper installation may result in electric shock or fire.

• Turn off the main power supply switch or breaker before attempting any electrical work.

Make sure all power switches are off. Failure to do so may cause electric shock.

• Perform installation work properly according to this Installation Manual.

Improper installation may result in electric shock or fire.

• Do not modify the unit.

Any modification may cause a malfunction, resulting in overheating or fire.

 WARNING

Upon customer’s approval, install the Touch Screen Controller at a place which satisfies the
following conditions.

• Place where the Touch Screen Controller can be installed securely.

• Place which can reserve a sufficient service space for safe maintenance or check.

• Place where CF (Compact Flash) card can be removed easily.

• Place which provides sufficient space for connecting/checking the terminals of interface, Input-

Output ports, etc.

Avoid the following places

.

• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus,

or communication equipment) is installed. (A bad influence may generated by malfunction of the
controller, control error, or noise may affect such equipment.)

• Perform wiring correctly in accordance with specified the current capacity.

Failure to do so may result in short-circuiting, overheating, or fire.

• Connect the specified cables for the terminals securely to prevent external forces from

affecting them.

Failure to do so may result in disconnection, overheating, or fire.

 CAUTION

Summary of Contents for BMS-TP0641ACE

Page 1: ...rol System Thank you very much for purchasing the TOSHIBA Touch Screen Controller Please read this manual carefully beforehand for proper installation of the controller CONTENTS Precautions for Safety 1 Introduction 2 Before Installation 3 1 Installation 3 2 Connection of Power cables Earth wires Signal wires 5 3 Trial Operation 8 ...

Page 2: ...odify the unit Any modification may cause a malfunction resulting in overheating or fire WARNING Upon customer s approval install the Touch Screen Controller at a place which satisfies the following conditions Place where the Touch Screen Controller can be installed securely Place which can reserve a sufficient service space for safe maintenance or check Place where CF Compact Flash card can be re...

Page 3: ... 240 VAC 50 60Hz 50VA 0 C to 50 C 20 to 85 RH no condensation 10 C to 60 C 256 H 316 W 54 D mm 3 5kg Air conditioning control Power distribution Indoor units connected BMS TP0641ACE BMS TP0641PWE BMS TP5121ACE BMS TP5121PWE Max 64 units Max 64 units Max 512 units Max 512 units ExternalView 249 95 75 91 75 256 19 30 16 54 5 49 242 99 3 75 82 5 302 55 5 48 70 75 316 Function switch F1 F2 F3 PCI expa...

Page 4: ...pact flash from coming out For card cover For connecting controller and TCS NET Relay Interface This manual Use the following materials to connect the signal lines and power lines procured on site Line For RS 485 For digital Input Output connection For Power Type Wire size Length Type Wire size Length Type Wire size Description 2 core shield wire 1 25mm2 500m max total length 2 core wire 0 3mm2 10...

Page 5: ... 1 0 243 1 0 R1 or less mm Panel thickness 1 6 7 mm REQUIREMENT Use a panel procured on site of thickness 1 6 7 mm 2 Desk Top Installation using the CONTEC stand procured on site For reference Display stand not supplied with the controller Use the CONTEC stand model IPC SND 03 For details of the stand visit the CONTEC web site Europe http www contec europe com China http www contec sh cn The angle...

Page 6: ...r details of the connection refer to I O port connection on next page Connect firmly the power cable to the power input terminal COM2 RS 485 TCS NET relay interface Power supply Connect the attached RS 485 cable to COM2 Ethernet To customer s PC Length of stripped power cable Length of stripped digital Input Output connector wire CAUTION Ensure to connect the breaker to the primary side of power C...

Page 7: ...er insulation 3 3k ohm Open collector 3 Max 100mA per 1 output Less than 30V DC Input type Number of input Input resistance Output type Number of output Output current Output voltage 1 The example of input circuit is shown below It is electrically insulated by the photo coupler 2 The example of output circuit is shown below It is electrically insulated by the photo coupler 10 k ohm 3 k ohm 1 2 W P...

Page 8: ...LAY INTERFACE RS 485 TERMINATOR Outdoor unit Indoor unit Indoor unit Remote controller Outdoor unit Indoor unit Remote controller Central remote controller A B A Power supply Power supply Power supply Switching HUB TOUCH SCREEN CONTROLLER Caution RS 485 cable has polarity If incorrectly connected it does not work Yellow Brown Power supply TCS NET RELAY INTERFACE TCC LINK TERMINATOR TCC LINK TERMIN...

Page 9: ...tion of Communication with Each Interface When the communication with the interface listed on the setting file is disconnected the communication error is displayed on the Touch Screen Controller Press the Alarm List button to confirm whether the communication error occurs or not Communication error judging time Approx 15 minutes The suspected causes of the communication error will be as follows Th...

Page 10: ...EH99852501 ...