BN interface

Installation Manual

17

-EN

5-2. Setting up equipment data in the indoor unit

Obtain the equipment data of the indoor unit that is controlled by the BN interface from the indoor unit via the Uh Line 
communication cable.

Preparing to set up equipment data in the indoor unit

• Central Control address must be set in the indoor unit you want to control.

 

For information on how to set the address, refer to the installation manual of each indoor unit.

• Turn on all indoor and outdoor units. Set up as follows, waiting 10 minutes after turning on all the units.

Setup work

• Turn on the BN interface.
• When 10 minutes has elapsed since turning on the BN interface, hold down the shutdown button for 4 seconds or longer.

 

L1 LED goes on.

• When the BN interface has started up normally, start reading the equipment data of the interface unit. During this operation 

L1 LED will be on while L2 LED will be blinking on the BN interface.

• When reading of equipment data in the indoor unit ends normally, the BN interface will automatically start preparing for 

BACnet communication. L1 LED on the BN interface is blinking.

• When the preparations for BACnet communications end normally, L1 LED and L2 LED of the BN interface will start 

blinking.

• If an error occurs during reading of equipment data from the indoor unit or when preparing for BACnet communications, 

L1 LED and L2 LED of the BN interface will go on.
Determining the cause of such an error will require the use of engineering tools. For details, contact your dealer.

5-3. Cause of problem occurring during setup

6

Turning off the BN interface

Press the shutdown button, then wait 5 minutes before turning it off.

CAUTION

As the air-conditioning search mode will be engaged if the shutdown button is pressed for 4 seconds or longer, do not hold down 
the button.

Cause of problem

Cause

Action

The indoor unit cannot be found.

The indoor and outdoor units have not been 
turned on.

Make sure that indoor and outdoor units are 
turned on.

The indoor and outdoor units are being 
initialized and it is not possible to 
communicate with them.
LINK(Uh) LED does not blink at all

Make sure that indoor and outdoor units are 
turned on.
Make sure they have been on for at least 

 

10 minutes.

The Uh Line cables have been incorrectly 
connected.

Connect the cables correctly.

The central control address has not been set 
in the indoor units. 

Make sure that the central control address has 
been set in the indoor units.

The central control address set in 
the indoor units are not unique.

The same central control address has been 
set in a number of indoor units.

Make sure that the central control address has 
been correctly set in the indoor units.

Summary of Contents for BMS-IFBN1280U-E

Page 1: ...de licence et des informations sur la licence Hrvatski Preuzimanje Priručnika za instalaciju Ugovora o licenci i Informacija o licenci Magyar Telepítési kézikönyv Licencszerződés és Licencinformáció letöltése Italiano Download del Manuale di installazione del Contratto di licenza e delle Informazioni sulla licenza Latviešu Uzstādīšanas rokasgrāmatas licences līguma un licences informācijas lejupie...

Page 2: ...d signal line connections 7 3 Settings 14 3 1 Switch setting 14 3 2 LED 15 4 Factory default settings 15 5 Test run 16 5 1 BACnet communication settings 16 5 2 Setting up equipment data in the indoor unit 17 5 3 Cause of problem occurring during setup 17 6 Turning off the BN interface 17 AEEE Yönetmeligine Uygundur ...

Page 3: ...es damage extending to buildings household effects domestic livestock and pets indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol indicates compulsory mandatory items The actual contents of the obligation are indicated by a picture or text placed inside or next to the graphic symbol Warning Installation a...

Page 4: ...wer Cable Pin terminal 2 Uh Line caulked connectors Mounting bracket DIN rail 1 Use screws to secure the unit in locations without DIN rails walls etc Screws M4 x 12 2 For securing the DIN rails Rubber feet 4 For levelling the unit Screws M3 x 8 4 For securing the rubber feet to the unit Installation Manual 1 This manual License Agreement 1 License Information 1 Tie wrap 1 Power supply Rated volta...

Page 5: ... use Component Names Name Function 5V DCIN Connect the power adapter USB For service Ethernet LAN Connect to the Building Management System Shutdown button Shutdown or switch to air conditioning search mode L1 BACnet communication status indicator L2 BACnet communication status indicator setting error indicator 722 1 12 68 s s s s 䣒䣑䣙䣇䣔 䣎䣋䣐䣍䢪䣗䣪䢫 䣅䣒䣗 5525 86 9 1 WKHUQHW 1 6KXWGRZQ EXWWRQ ...

Page 6: ...to mount the unit or wall mount or surface mount it as shown below Use the supplied mounting bracket to wall mount or surface mount the interface 3 Surface mount Use screws to secure the supplied rubber legs to the interface before surface mounting it 1 DIN rail mount Install the interface on DIN rails mounted on a switchboard or elsewhere Front view Back view 2 Wall mount Use screws to attach the...

Page 7: ...ual 6 EN Installation Space and Maintenance Space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects PP PP ...

Page 8: ...r cable connection and Uh Line communication cable connection No Line Description 1 For Uh Line Type 2 core shielded wires Wire size Refer to Design of Control Wiring P 10 to P 13 Length 2 For Ethernet Type LAN cable higher than Category 5 UTP The appropriate use of straight cable cross cable should be done depending on your system used Length 100 m max 50 10 Connect the supplied pin terminal to t...

Page 9: ...iring Connections 8K LQH 9 1 WKHUQHW 1 䣒䣑䣙䣇䣔 䣎䣋䣐䣍䢪䣗䣪䢫 䣅䣒䣗 5525 8 8 8 8 8 8 8 8 8 8 8 8 8 BN interface Building Management System Power adapter Power Supply Uh Line main bus Outdoor unit Outdoor unit Indoor unit Indoor unit Remote controller Remote controller ...

Page 10: ...etting method Shield grounding process Central control wiring shielded wire When using the central remote controller with one unit open the shielded wire of the central control wiring and perform insulation processing When using the central remote controller with multiple units connect the shield of the central control wiring to the closed end and open the shield at the final end of the central re...

Page 11: ...ng table Communication method TU2C LINK U series TCC LINK other than U series Outdoor unit Other than on the left MMY MAP MCY MAP etc Indoor unit Other than on the left MM AP etc Wired remote controller Other than on the left Wireless remote controller receiver Other than on the left Central control device Other than on the left MMY M P U series model MM P U series model RBC AMS U series model RBC...

Page 12: ...ram The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series Item Communication line Central control wiring Uh line Wire diameter 1 0 to 1 5 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U3 U4 LINK Uh U6 U4 U1 U2 Uv A B U6 U4 U1 U2 Uv A B U6 U4 U1 U2 Uv ...

Page 13: ...ote controller are other than the U series Item Communication line Control wiring between indoor and outdoor units and central control wiring Wire diameter 1 25 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U2 U4 U3 U4 U3 U4 U6 U4 U1 Uv Uv Uv Uv U2 A B U6 U4 U1 U2 A B U6 U4 U1 U2 A B U6 U4 U1 U2 A B U1 U3 U2 U5 U6 U3 U4 U1 U2 U5 U6 U3 U4...

Page 14: ...communication error System diagram The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series Item Communication line Central control wiring Uh line Wire diameter 1 25 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U 2 U 4 U 3 U 4 U3 U4 U 6 U 4 U1 Uv U2 A B...

Page 15: ... mode function button Use this button to stop BACnet process and network process of the BN interface or to start up in the air conditioning search mode Note that button operation changes depending on how long it is depressed Time duration button is depressed Operation Less than 4 seconds Stop BACnet process and network process of the BN interface 4 seconds or more Starts air conditioning in the ai...

Page 16: ...or in the BN interface L1 Green BACnet communication status indicator L2 Red BACnet communication status indicator setting error indicator 38 1 8K 32 5 5525 䣒䣑䣙䣇䣔 䣎䣋䣐䣍䢪䣗䣪䢫 䣅䣒䣗 5525 䣒䣑䣙䣇䣔 䣎䣋䣐䣍䢪䣗䣪䢫 䣅䣒䣗 5525 No Item Factory default setting 1 IP address IP address 192 168 1 100 Subnet mask 255 255 255 0 2 UDP port 47808 0xBAC0 3 Device object instance number 100 4 Address setting switch 1 5 Test switc...

Page 17: ...P address IP address Use Setting File Creation Software 2 See Section 5 1 Network mask BACnet communication device identification number BACnet device object instance number When using together with a central control device not compatible with Uh Line Setting of old BN interface Setting for combined use with old controller When replacing with a BN interface that does not support Uh Line Setting of...

Page 18: ...an error occurs during reading of equipment data from the indoor unit or when preparing for BACnet communications L1 LED and L2 LED of the BN interface will go on Determining the cause of such an error will require the use of engineering tools For details contact your dealer 5 3 Cause of problem occurring during setup 6 Turning off the BN interface Press the shutdown button then wait 5 minutes bef...

Page 19: ...BN interface Installation Manual 18 EN ...

Page 20: ...1 Klimanıza ilişkin daha ayrıntılı bilgiler için ürün tanıtım broşürlerine gerektiğinde Alarko Carrier Yetkili Satıcı ve Servislerine ulaşabilmek için 444 0 128 numaralı Müşteri Danışma Hattımıza başvurabilirsiniz ...

Reviews: