background image

Air Conditioning Control System (Touch Screen Controller)

Model name:

BMS-CT1280E
BMS-CT1280E-TR

Installation Manual

• Save These Instructions!

ENGLISH

Summary of Contents for BMS-CT1280E

Page 1: ...Air Conditioning Control System Touch Screen Controller Model name BMS CT1280E BMS CT1280E TR Installation Manual Save These Instructions ENGLISH ...

Page 2: ...of Main Unit Box and Panel 8 3 1 1 When Installing from the Front 8 3 1 2 When Installing from the Rear 9 3 2 Attaching the Power Adapter 10 3 3 Power Signal and Earth Line Connections 11 Thank you for purchasing the TOSHIBA air conditioning control system Please read this installation manual carefully before installation and perform the work only in the correct manner ...

Page 3: ...ies which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The...

Page 4: ...ty Failure to do so may result in excessive heat or fire Use specified cables and connect them securely and do not subject connecting terminals to external force Doing so may result in broken cables excessive heat or fire Always install a circuit breaker on the primary side of the power supply Clean the touch panel by wiping with an eyeglasses cleaner or other soft cloth To remove oil based ink wi...

Page 5: ...aximum 64 units TCC LINK 2 maximum 64 units Power meter interface Up to 4 units Digital I O interface Up to 4 units Communication ports RS 485 port 1 LAN port 1 USB port USB memory stick connection port 2 External contact input 8 inputs External contact output 4 outputs Operating temperature humidity range 0 C to 40 C 10 to 90 RH no condensation Dimensions H136 W205 D10 80 Embedded dimensions show...

Page 6: ...e LAN Can be connected to a PC via LAN communication and monitored and controlled Ø15 0 29 6 0 5 1500 0 20 0 30 5 110 0 0 5 62 0 0 5 Ø5 5 0 1 Ø2 5 0 1 0 0 5 0 15 0 0 Ø12 0 0 5 6 5 0 3 33 0 0 5 7 5 0 3 FERRITE AS REQUIRED WIRE NO 1185 GAUGE 16AWG BLACK SPEC LABEL LED 31 5 MAX COM DI 4 COM DI 3 COM DI 2 COM DI 1 TCC LINK1 INPUT TCC LINK2 RS 485 U1 U2 U1 U2 FG B A COM DI 8 COM DI 7 COM DI 6 COM DI 5 ...

Page 7: ...ver Software 6 Fixing screw 4 Fixing screw M4 12 for attaching the main unit from the front 7 Fixing screw 4 Fixing screw M3 8 for attaching the main unit from the rear 8 Closed end connector 2 RS 485 cable crimp connector 9 Binding band 2 For fixing the power adapter 10 Double sided tape 1 For fixing the power adapter No Wiring Wire type wire diameter wire length 1 For TCC LINK Microphone cord sh...

Page 8: ... adapter and LAN cable to the main unit 2 Fit the main unit on to the wall and switch board 3 Insert a flat head screwdriver etc into the groove on the left and right of the bottom of the panel There will be a snapping sound and the panel will come off REQUIREMENT Just insert the screwdriver and do not twist it To prevent the panel from falling support it during removal 4 Fix the 4 main unit screw...

Page 9: ...installation work 1 Drill four Ø4 holes in the switchboard wall etc 2 Fit the main unit on the switch board wall etc 3 Fix from the rear of the main unit Please use the supplied M3 8 screws 4 Connect the TCC LINK cable AC adapter and LAN cable to the main unit 5 When installation is completed peel off the transparent film Main unit box Panel 183 120 100 133 20 93 53 202 190 4 5 8 5 8 20 20 Air con...

Page 10: ...ng band and double sided tape REQUIREMENT Do not install in the following locations Locations with high humidity or water Dusty locations Locations in direct sunlight and locations subject to high temperatures Locations within 1 m from televisions or radios Outdoors under awnings or other locations exposed to rain and dew Installation allowed Installation not allowed Install so that the power cabl...

Page 11: ...Indoor unit Remote controller TCC LINKSignal line 2 RS 485 signal line TCC LINK 1 and TCC LINK 2 do not have polarity The RS 485 cable has polarity A B It will not work correctly if it is connected with incorrect polarity Connect the shielded wire of the RS 485 signal line to the FG terminal block Connection with power meter interface digital I O interface sold separately Power connector DC 12 V C...

Page 12: ...open the shielded wire of the TCC LINK communication cable and perform insulation processing When using the air conditioning control system with multiple units connect the shield of the TCC LINK communication line to the closed end and open the shield at the final end of the air conditioning control system to perform insulation processing Perform TCC LINK communication line shield grounding on the...

Page 13: ...e I O conditions State output Contact permissible voltage current 24 V DC 35 mA Wiring length Within 100 m Control input No voltage contact A Pulse or static No voltage contacts compatible with very small current should be selected 5 V DC 3 mA Pulse width 50 msec or more Wiring length Within 100 m DO1 Output common DO2 Output common DO3 Output common DO4 Output common DO1 Output common Digital inp...

Page 14: ...ection Connect the power meter interface and the digital I O interface to the RS 485 cable line For details of the connection method refer to the interface installation manual NOTE Set the termination resistance of TCC LINK 1 and 2 at the air conditioner When you remove the rear panel of this Unit there is SW100 which is the termination resistance of TCC LINK 1 and 2 In both cases please use in th...

Page 15: ...EN 15 EN Air Conditioning Control System Touch Screen Controller Installation Manual MEMO ...

Page 16: ...DEB5819101 ...

Reviews: