4. APG001Z Point Summaries 

This database features 85 logical points: 24 Logical Analog Inputs (LAI), 19 Logical 
Analog Outputs (LAO), 24 Logical Digital Inputs (LDI) and 18 Logical Digital Outputs 
(LDO). These points configure, control or monitor the operation of the Drive. 
 
(Note)"PointName" in the parenthesis is a reservation definition. 

   

    The point of the reservation definition does not work. 

Table 1  Point Summary 

Point 

Number 

Point 
Type 

Point 

Name 

Factory

Default

Eng. 

Units 

Slope Intercept 

ON 

Text 

OFF 

Test 

01 LAO 

CTLR 

ADDRESS 

99 

02 LAO 

APPLICATION 

2739

 

- 1 0 -  - 

03 LAI 

FREQ 

OUTPUT 

HZ 

0.1 

04 LAI 

PCT 

OUTPUT 

PCT 

0.1 

05 LAI 

SPEED 

RPM 

06 LAI 

CURRENT 

0.1 

07 LAI 

TORQUE 

2000  PCT 

0.1 

-200 

08 LAI 

POWER 

KW 

0.1 

09 LAI 

DRIVE 

TEMP 

PCT 

0.1 

10 LAI 

DRIVE 

KWH 

kWH 

11 LAI 

DRIVE 

MWH 

MWH 

12 LAI 

RUN 

TIME 

13 

LAI 

DC BUS VOLT 

14 LAI 

OUTPUT 

VOLT 

15 

LAI 

PRC PID FBCK 

PCT 

0.1 

16 

LAI 

(PRC PID DEV) 

PCT 

0.1 

N/A 

N/A 

N/A 

17 LAI 

(MOTOR 

TEMP) 

PCT 

0.1 

N/A 

N/A 

N/A 

18 N/A 

N/A 

N/A 

N/A 

N/A N/A N/A  N/A 

19 N/A 

N/A 

N/A 

N/A 

N/A N/A N/A  N/A 

20 LAO 

OVRD 

TIME 

21 LDI 

FWD.REV 

FWD 

REV 

FWD 

22 LDO 

CMD 

FWD.REV 

FWD 

REV 

FWD 

23 LDI 

STOP.RUN 

STOP 

RUN 

STOP 

24 LDO 

CMD 

STP.STRT 

STOP 

RUN 

STOP 

25 LDI 

EXT1.2 

ACT 

EXT1 

EXT2 

EXT1 

26 LDO 

EXT1.2 

CMD 

EXT1 - 

0  EXT2 EXT1 

27 LDI 

DRIVE 

READY 

NOTRD

- 1 0 

READY 

NOTRDY 

28 LDI 

AT 

SETPOINT 

NO 

YES 

NO 

29 LDO 

DAY.NIGHT 

DAY 

NIGHT 

DAY 

30 LAO 

CURRENT 

LIM 

0.1 

31 

LAO  ACCEL TIME 1

(Note1)

 300 

0.1 

32 

LAO  DECEL TIME 1

(Note1)

 300 

0.1 

33 LDI 

HANDAUTO 

ACT 

AUTO 

HAND  AUTO 

34 N/A 

N/A 

N/A 

N/A 

N/A N/A N/A  N/A 

35 N/A 

N/A 

N/A 

N/A 

N/A N/A N/A  N/A 

36 

LDI 

FLN LOC ACT 

AUTO 

FLN 

AUTO 

37 LDI 

CTL 

SRC 

NO 

YES 

NO 

38 

LDI 

FLN REF1 SRC 

NO 

YES 

NO 

39 

LDI 

FLN REF2 SRC 

NO 

YES 

NO 

40 

LDO  DO 1 COMMAND 

OFF 

ON 

OFF 

41 

LDO  DO 2 COMMAND 

OFF 

ON 

OFF 

42 

LDO  DO 3 COMMAND 

OFF 

ON 

OFF 

43 

LDO  DO 4 COMMAND 

OFF 

ON 

OFF 

44 

LDO  DO 5 COMMAND 

OFF 

ON 

OFF 

45 

LDO  DO 6 COMMAND 

OFF 

ON 

OFF 

Summary of Contents for APOGEE FLN APG001Z

Page 1: ...tion manual is delivered to the end user of APOGEE FLN option unit 2 Read this manual before installing or operating the APOGEE FLN option unit Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site ...

Page 2: ...twork variables Otherwise the motor may suddenly start stop and that may result in injuries Mandatory Use an additional safety device with your system to prevent a serious accident due to the network malfunctions Usage without an additional safety device may cause an accident Caution Mandatory Set up Communication error trip function see below to stop the Inverter when the option unit is deactivat...

Page 3: ... LAI Summary 9 4 1 1 LAI Point Descriptions 10 4 2 Logical Analog Output LAO Summary 11 4 2 1 LAO Point Descriptions 12 4 3 Logical Digital Input LDI Summary 13 4 3 1 LDI Point Descriptions 14 4 4 Logical Digital Output LDO Summary 15 4 4 1 LDO Point Descriptions 16 4 5 FLN P1 Error Codes 18 5 MAILBOX FUNCTION POINTS 19 5 1 Parameter data 20 6 FRAME COUNTER MONITOR 21 7 VF PS1 ALARM CODE 22 8 VF P...

Page 4: ...ical specifications Internal circuits B Communication signal A Communication signal GND Signal common SCR APOGEE FLN communication signal EIA 485 Shield terminal B A GND SCR 47k 47k 4 7k 4 7k 120 SW102 TERM Don t use this connecter Connector to the inverter Don t use these switches Don t use this switch APOGEE Connector See 2 2 Terminal connector MSTB 2 5 4 STF 5 08 PHOENIX CONTACT APOGEE LED indi...

Page 5: ...d Confirm the network condition and connection of the cable C COM LED ON ERR LED OFF 0 5s ON 0 5s Invalid configuration was detected Note When inverter occurred in e 23 or e 24 the LED becomes this state D COM LED Flashing ERR LED Valid message was received for this node E COM LED ERR LED Flashing Invalid message was received any node F COM LED OFF ERR LED OFF No communication Confirm the network ...

Page 6: ...work error err8 trip 5 Preset speed operation by f852 setting 0 f852 0852 Preset speed operation selection 0 None 1 15 Preset speed operation by parameter setting 0 f853 0853 Communication option station address monitor Read Only Real station address monitor If a value of f834 is out of a range the value of f853 becomes 99 f899 0899 Network option reset setting 0 None 1 Reset option circuit board ...

Page 7: ...parameter f833 is connected to point number one hundred Pno 100 Reset is possible to factory setting in offline by using this parameter Point number one hundred is called the factory flag factory flag is used to determine if the initial values need to be initialized If the factory flag does not equal ACH the initial value for each subpoint will be set equal to the default value Then the factory fl...

Page 8: ... LAI PRC PID FBCK 0 PCT 0 1 0 16 LAI PRC PID DEV 0 PCT 0 1 N A N A N A 17 LAI MOTOR TEMP 0 PCT 0 1 N A N A N A 18 N A N A N A N A N A N A N A N A 19 N A N A N A N A N A N A N A N A 20 LAO OVRD TIME 1 H 1 0 21 LDI FWD REV FWD 1 0 REV FWD 22 LDO CMD FWD REV FWD 1 0 REV FWD 23 LDI STOP RUN STOP 1 0 RUN STOP 24 LDO CMD STP STRT STOP 1 0 RUN STOP 25 LDI EXT1 2 ACT EXT1 1 0 EXT2 EXT1 26 LDO EXT1 2 CMD E...

Page 9: ... 1000 PCT 0 1 0 68 LDO FLN LOC CTL AUTO 1 0 FLN AUTO 69 LDO FLN LOC REF AUTO 1 0 FLN AUTO 70 LDI DI 1 ACTUAL OFF 1 0 ON OFF 71 LDI DI 2 ACTUAL OFF 1 0 ON OFF 72 LDI DI 3 ACTUAL OFF 1 0 ON OFF 73 LDI DI 4 ACTUAL OFF 1 0 ON OFF 74 LDI DI 5 ACTUAL OFF 1 0 ON OFF 75 LDI DI 6 ACTUAL OFF 1 0 ON OFF 76 LDI DO 1 ACTUAL OFF 1 0 ON OFF 77 LDI DO 2 ACTUAL OFF 1 0 ON OFF 78 LDI DO 3 ACTUAL OFF 1 0 ON OFF 79 L...

Page 10: ...t commands but will not change their actual values or indicate override active Note PointName in the parenthesis is a reservation definition The point of the reservation definition does not work Table 2 Logical Analog Input LAI Summary Point Number Point Name Factory Default Eng Units Slope Intercept Min Max 03 FREQ OUTPUT 0 HZ 0 1 0 0 32767 04 PCT OUTPUT 0 PCT 0 1 0 0 32767 05 SPEED 0 RPM 1 0 0 3...

Page 11: ...s 13 DC BUS VOLT The DC bus voltage level of the drive 14 OUTPUT VOLT The AC output voltage applied to the motor 15 PRC PID FBCK The ratio of PID feedback signal to the corresponding vl base frequency 16 PRC PID DEV Reserved does not work 17 MOTOR TEMP Reserved does not work 82 AI 1 ACTUAL Indicates the input level of RR S4 terminal 83 AI 2 ACTUAL Indicates the input level of VI II terminal 84 AO ...

Page 12: ... designs the unit of Acceleration deceleration time in 0 1sec Please do not set 10 Acceleration deceleration time setting 0 01 sec 600 00sec in Factory default setting typ 10 A unit of Acceleration deceleration time setting is changed instantly when set typ 10 When this option is connected to the inverter the data unit of Point Number 31 and 32 is changed to 0 01 second It is possible that it lead...

Page 13: ...ata output This makes it possible to send out the data specified as AM analog output data AO 2 COMMAND through the AM analog output terminal Data can be adjusted in a range of 0 to 2047 resolution of 11 bits For details refer to Meter setting and adjustment of the instruction manual included with the inverter 50 PRC PID GAIN Sets the proportional gain of the PID 1 f362 51 PRC PID ITIM Sets the int...

Page 14: ...1 FWD REV FWD 1 0 REV FWD 23 STOP RUN STOP 1 0 RUN STOP 25 EXT1 2 ACT EXT1 1 0 EXT2 EXT1 27 DRIVE READY NOTRDY 1 0 READY NOTRDY 28 AT SETPOINT NO 1 0 YES NO 33 HANDAUTO ACT AUTO 1 0 HAND AUTO 36 FLN LOC ACT AUTO 1 0 FLN AUTO 37 CTL SRC NO 1 0 YES NO 38 FLN REF1 SRC NO 1 0 YES NO 39 FLN REF2 SRC NO 1 0 YES NO 70 DI 1 ACTUAL F OFF 1 0 ON OFF 71 DI 2 ACTUAL R OFF 1 0 ON OFF 72 DI 3 ACTUAL OFF 1 0 ON ...

Page 15: ... status of the F terminal on the drive 71 DI 2 ACTUAL Indicates the status of digital Input 2 Depending of the status of the R terminal on the drive 72 DI 3 ACTUAL Reserved does not work 73 DI 4 ACTUAL Indicates the status of Digital Input 4 1 ON 0 OFF Depending on the status of the RES f114 terminal on the drive 74 DI 5 ACTUAL Indicates the status of Digital Input 5 1 ON 0 OFF Depending on the st...

Page 16: ...OFF 0 Test 22 CMD FWD REV FWD 1 0 REV FWD 24 CMD STP STRT STOP 1 0 RUN STOP 26 EXT1 2 CMD EXT1 1 0 EXT2 EXT1 29 DAY NIGHT DAY 1 0 NIGHT DAY 40 DO 1 COMMAND OUT1 OFF 1 0 ON OFF 41 DO 2 COMMAND OUT2 OFF 1 0 ON OFF 42 DO 3 COMMAND FL OFF 1 0 ON OFF 43 DO 4 COMMAND OUT3 OFF 1 0 ON OFF 44 DO 5 COMMAND OUT4 OFF 1 0 ON OFF 45 DO 6 COMMAND R1 OFF 1 0 ON OFF 48 RST RUN TIME NO 1 0 RESET NO 49 RESET KWH NO ...

Page 17: ...97 43 DO 4 COMMAND The data of this point is outputted to the terminal which chose the designated data output 4 Output terminal selection number 98 99 For example when you control the output of an OUT3 terminal please set the parameter f133 OUT3 terminal 98 99 44 DO 5 COMMAND The data of this point is outputted to the terminal which chose the designated data output 5 Output terminal selection numb...

Page 18: ...priority over this point Thus this point is only effective in temporarily taking control from the analog inputs or some other internal control functionality 94 RESET FAULT Command from the FLN network to reset a faulted drive 1 RESET 0 NO The control input is rising edge sensitive so once the command is issued this point automatically returns to its inactive state This momentary operation avoids a...

Page 19: ...d by a FLN device Table 10 FLN P1 Error Code Error Code Description D7 H Operator priority too low A number of situations can return this error code F9 H Invalid point number FB H No COVs to report FC H Request Characterization FD H Invalid command FE H Invalid value Including the response for Dump Memory command 18 H and Modify Memory command 19 H APG001Z does not support these commands ...

Page 20: ...ritten RAM after that the data is written to Note 1 When the data is written in normally this point is changed from 1 to 0 otherwise this point remains 1 Note1 Please do the inverter cannot start for example ST terminal OFF at writing the parameter that commands to the inverter to drive and is inhibited during driving If not the data is only written RAM and this point remains 1 Example 1 Read the ...

Page 21: ...meter V R enables to set to 0 01 sec adjustment range 0 01 600 0 sec 1 Title means the display on the inverter panel 2 Communication number is affixed to each parameter that is necessary for designating the parameter for communication 3 Adjustment range means a data range adjustable for a parameter and the data cannot be written outside the range The data have been expressed in the decimal notatio...

Page 22: ...requency Parameter setting mode MODE auf The first basic parameter auf Wizard function is displayed Direction of rotation MODE fr f The direction of rotation is displayed fr f forward run fr r reverse run Frame counter UP m 50 Displays the frame counter numbers of communication through the network example In the case of 50 counts In the case of f711 72 a communication option reception counter sett...

Page 23: ...istor overload alarm Normal Alarming 10 Cumulative operation hours alarm Normal Alarming 11 Reserved 12 Reserved 13 Reserved 14 At the time of the instant blackout Forced deceleration stop Decelerating stopping lstp flickering 15 An automatic stop during the lower limit frequency continuance Decelerating stopping stop flickering Table 13 ALARM WORD 2 Pno 89 Table Bit Specifications 0 1 Remarks Cod...

Page 24: ...5 19 Gate array fault err6 26 1A Output current detector error err7 27 1B Option error err8 29 1D Low current operation status uc 30 1E Undervoltage main circuit up1 32 20 Over torque trip ot 33 21 Ground fault trip ef1 34 22 Ground fault trip ef2 36 24 Dynamic braking abnormal element ocr 37 25 Overcurrent during acceleration element overheat oc1p 38 26 Overcurrent during deceleration element ove...

Page 25: ...y of trip information e 23 Error code 55 Add on option 1 error This error is displayed at the time the bottom side option has an error or only one option is installed and has an error e 24 Error code 56 Add on option 2 error This error is displayed at the time the two units are installed and the upper side option has an error 9 2 Disconnection error of network cable When network trouble occurred b...

Page 26: ...r the parameter in detail Command Setpoint Operation Panel EASY key f750 2 Local Remote key Logic input 48 SC LC Network cancel switch Network APOGEE FLN Network APOGEE FLN LDO point 68 1 LDO point 69 1 0 1 ON OFF 0 1 Operation Panel ON OFF Control Terminal VI Control Terminal RR Operation Panel Network APOGEE FLN fmod 1 2 4 7 Control Terminal Operation Panel Network APOGEE FLN cmod 0 1 4 Remote L...

Page 27: ...minal board fmod Frequency setting mode selection 1 2 RR S4 f112 Input terminal selection 2 R 48 Remote Local control Operation R CC terminal open VF PS1 is controlled as a slave device of The APOGEE FLN R CC terminal closed F CC terminal short to RUN F CC terminal open to STOP Output frequency is set up by the RR S4 signal input Note When the local HAND remote key f750 2 is chosen as EASY key sel...

Page 28: ...he inverter APG001Z network specification Item Specification Station type Remote device station Number of occupied stations 1 station occupied by 1 unit Maximum FLN device 32 FLN devices to each FLN port of the Field Cabinet Communication baud rate 4800 9600 19200 38400 57600 76800bps Bias resistor and termination Local bias resistors are mounted Termination resistor 120 ohm can be select by SW Te...

Reviews: