4400 Series UPS Seismic Kit Installation Instructions – 94016-002

FIgUrE 2.3: 50KVA SEISMIC  

ANCHOrAgE - FLOOr PATTErN

28.06 in. (713 mm)

11.5 in. (292 mm)

11.5 in. (292 mm)

4.59 in  (112 mm)

2.03 in 

(51 mm)

37.2 in. (944 mm)

32.1 in. (816 mm)

5/8 in. Bolt Anchor (6)

FIgUrE 2.6: BOTTOM SEISMIC BrACKET INSTALLATION 

(FLOOr  AND ANCHOrS NOT SHOWN)

11

11

11

11

11

11

11

11

Bottom 

Bracket

P/N 67193

6

6

FIgUrE 2.4: 50KVA SEISMIC  

ANCHOrAgE - WALL PATTErN

5/16 in. Bolt  

Anchor (4)

7.0 in 

(178 mm)

75.01 in. (1905 mm)

7.0 in 

(178 mm)

10.0 in 

(254 mm)

5.0 in 

(127 mm)

14.03 in 

(356 mm)

Seismic 

Mounting 

Channel

32.1 in. (816 mm)

4.06 in 

(103 mm)

FIgUrE 2.5: TOP SEISMIC BrACKET INSTALLATION

11

11

11

5

Top Bracket

P/N 66437

Summary of Contents for 4400 15-30kVA Seismic

Page 1: ...VA Seismic Installation Table 1 lists the contents of the 4400 15 30kVA Seismic Kit Figure 1 1 shows the order of assembly for the bolt lockwasher washer fastener group TABLE 1 15 30KVA SEISMIC CONTENTS 440300SEISMICKIT Contents No P N Description Quan 1 93437 TOP SEISMIC BRACKET 30kVA 1 3 67813 BASE MOUNTING BRACKET 1 4 a Hex Bolt 1 4 20 1 1 2 1 4 b Flat Washer 1 4 1 4 c E Ring F 0 25 Shaft 1 11 ...

Page 2: ...o the floor anchors installed in Step 1 7 Roll the 15 30 kVA UPS cabinet between the two vertical sides of the Base Mounting Bracket 4 Figure 1 6 8 Line up the UPS so the bolt holes on the Bottom Seismic Brack ets line up with the holes on the Seismic Base Plate vertical sides 9 Secure the UPS to the Seismic Base Plate using the remaining eight 8 fastener group 11 Insert the bolts through the Seis...

Page 3: ...PS Seismic Kit Installation Instructions 94016 002 15 30 kVA Seismic Adapter Kit Cont 11 11 11 11 11 11 Slide UPS into Base Plate Figure 1 6 INSTALLING ON SEISMIC BASE PLATE Figure 1 7 SEISMIC DOOR ANCHOR 15 30 KVA 4 ...

Page 4: ...4 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 1 8 SEISMIC 15 30 KVA DIMENSAIONAL DRAWING ...

Page 5: ... placement in Step 1 Figure 2 4 3 Table 2 lists the components of the 50kVA Seismic Kit Figure 2 2 shows the Seismic anchorage components in the Seismic Kit for the 50kVA cabinets 4 Assemble the fastener groups in Table 2 7a 7c 10a 10c and 11a 11c as shown in Figure 2 1 5 Secure the Top Seismic Bracket 5 to the top rear of the UPS using three 3 fastener group 11 Figure 2 5 6 Position the UPS over ...

Page 6: ...olt Anchor 6 Figure 2 6 BOTTOMSEISMICBRACKETINSTALLATION FLOOR AND ANCHORS NOT SHOWN 11 11 11 11 11 11 11 11 Bottom Bracket P N 67193 6 6 Figure 2 4 50KVA SEISMIC ANCHORAGE WALL PATTERN 5 16 in Bolt Anchor 4 7 0 in 178 mm 75 01 in 1905 mm 7 0 in 178 mm 10 0 in 254 mm 5 0 in 127 mm 14 03 in 356 mm Seismic Mounting Channel 32 1 in 816 mm 4 06 in 103 mm Figure 2 5 TOP SEISMIC BRACKET INSTALLATION 11 ...

Page 7: ...it Installation Instructions 94016 002 7 7 Anchor Bolt 5 16 in x 18 Press Nut 5 16 in x 18 Bolt 5 16 in Lock Washer 5 16 Washer 11 Fastener Group Figure 2 7 50 KVA SEISMIC FLOOR ANCHOR DETAIL Figure 2 8 SEISMIC DOOR ANCHOR 50KVA ...

Page 8: ...8 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 2 9 SEISMIC 50 KVA DIMENSAIONAL DRAWING ...

Page 9: ...cement for ancillary battery and or Auxiliary cabinets Figure 3 3 2 Prepare the wall anchorages Key measurements off the an chorage placement in Step 1 Figure 3 4 3 Table 3 lists the components of the 80kVA Seismic Kit Figure 3 2 show the Seismic anchorage component in the Seismic Kit for the 80kVA cabinets 4 Assemble the fastener groups in Table 3 7a 7c and 11a 11c as shown in Figure 3 1 5 Secure...

Page 10: ...7 1 in 689 mm 2 5 in 64 mm 2 5 in 64 mm 37 2 in 944 mm 32 1 in 816 mm 5 8 in Bolt Anchor 4 Figure 3 4 80KVA SEISMIC ANCHORAGE WALL PATTERN 5 16 in Bolt Anchor 4 7 0 in 178 mm 74 98 in 1904 mm 7 0 in 178 mm 10 0 in 254 mm 5 0 in 127 mm 13 55 in 344 mm Base C Channel 32 1 in 816 mm 11 11 11 Figure 3 5 TOP SEISMIC BRACKET INSTALLATION 5 ...

Page 11: ...11 4400 Series UPS Seismic Kit Installation Instructions 94016 002 Figure 3 6 SEISMIC 80 KVA DIMENSAIONAL DRAWING ...

Page 12: ...This Page Left Intentionally Blank ...

Page 13: ......

Page 14: ...EMS GROUP POWER ELECTRONICS DIVISION 13131 West Little York Road Houston Texas 77041 9990 Tel 855 803 7087 Fax 713 896 5212 US 800 231 1412 Canada 800 872 2192 Mexico 01 800 527 1204 https www toshibaups com Printed in the U S A ...

Reviews: