Toshiba 1600EP Series Product Specifications Download Page 2

                                                                                                      

Toshiba International Corporation 

                                                                            Uninterruptible Power Systems

 

 

                                                                                                                           UE3G2L036C61T 

 

Max Peak Current 

45A 

 

Overload Capacity 

125% for 30 secs, 150% for 10 secs 

 

Crest Factor 

3.0 at full load 

 

Frequency 

50/60 Hz Auto Sensing 

 

Frequency Regulation 

±  0.5Hz/±  1.0Hz/±  1.5Hz (authorized service center selectable only) 

 

Wave Form 

Sine wave, Zero Transfer Time 

 Load 

Power 

Factor 

0.85 

 

Efficiency AC to AC 

 Greater than 83% 

 

Common Mode Noise 

Less than 0.5 Vrms 

BATTERY DC 

Voltage 

216V 

 

Backup Time 

10 min (full load) 30 min (half load)  

 

Battery type 

Enersys NPX-35 Flame Retardant Lead Acid 9Ah/12V Part #: 51896 

 

Number of batteries Pack 

3 (Six batteries in each pack) 

 

Recharge time 

<12 hours to 90% 

 

Interface 

RS-232, Dry Contact Connectivity, External Battery Connectivity  

 Input 

Hardwire 

Input 

 Output 

Hardwire 

Output 

 Dimensions 

WxDxH 

(mm) 

838x254x711 

BATTERY Ship 

Dimensions 

WxDxH (mm) 

965x432x940 

 

Dimensions W x D x H (inch) 

33x10x28 

 

Ship Dimensions WxDxH (inch) 

38x17x37 

 

Weight kg (lb) 

120.2 (265) 

 

Ship Weight kg (lb) 

127 (280) 

 

External Matching Battery Cabinet 

Single - 70 Mins, Double - 140 Mins.  Max Two Cabinets. Part #: UE3-BC-0650 

 

Line Cord Options 

3.6kVA L6-30 Plug with 8" Line Cord (3 wire) Part #: UE31-6LC-30A 

 

Receptacles Options 

Four L6-30R, Two 5-15R (Duplex) Part #: UE3-RP-B3  

 

 

Five 5-20R (Duplex) Part #: UE3-RP-B5  

 

 

Two L6-30R, Four 5-15R (Duplex) Part #: UE3-RP-B7  

 Network 

Interface 

Card 

RemotEye II - Part #: RMTI-INT-R25 

 

Environmental Monitoring Device 

Part #: RMTI-EMD-HT 

ENVIRONMENT 

Operating Ambient Temperature 

0 ~ 40

o

C (32 ~ 104

o

F) 

 Recommended 

Temperature 

+15

o

C ~ 25

o

 Storage 

Temperature 

-20

o

C ~ 40

o

 Humidity 

30-90%, 

Non-Condensing 

 

Audible Noise 

50dB (A) maximum @ 1 meter from Front Panel 