TOSHIBA
MODEL NUMBER UC3G2L080C6
CAPACITY 8 kVA (5.6 kW) (*)
Input
Input voltage Single phase, 208/240 Vac, +10% to -30% *
Input frequency 45 to 65 Hz
Input capacity 8.0 kVA
Input power factor Approximate unity (0.98 to 1.0 lagging)
Input harmonic distortion Less than 5% (typ)
Battery
Battery rated voltage 252 Vdc
Battery backup time when fully charged
9 mins. at full load (**)
with 0.7 power factor and 77° F (25° C)
32 mins. at half load (**)
Recharge time Maximum 24 hrs to 100%, 90% in 10 hrs (***)
Type of batteries Sealed lead-acid, maintenance free
Output
Output voltage Single-phase, 240/208/120 volts
Output voltage regulation ±3%, steady state (during normal or battery-backup operation)
Output frequency 50/60 Hz ±0.1% in free-running mode (line sync range ±1.0%)
Output voltage waveform Computer-grade sine wave; less than 3.0% total harmonic distortion
with linear load
Rated load power factor 0.7 lagging
Voltage transient characteristic ±8% under 100% load step change
Rated output current (rms) 33.3A
Maximum peak output current (peak) 100.0A
Inverter overload capacity 125% for 1 minutes; 150% for 30 seconds
Bypass overload capacity 125% for 10 minutes; 1000% for 1 cycle
Crest factor 3.0
Environment
Operating temperature 32 to 104° F (0 to 40° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude Less than 3000 ft (1000 m) above sea level (****)
External dimensions
9.9W x 28.0H x 35.2D in
(250W x 700H x 890D mm)
Weight 447 lb (203.2 kg)
Acoustical noise 50 dB (A) max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) Greater than 85%
Heat generation 1000W (3444 Btu/hr)
Switches
Bypass switch Manual bypass provided
Bypass transfer switch Static switch standard (transfer time: less than 4 mS)
Automatic retransfer switch Provided (this function can be disabled)
Interface
IBM AS/400
TM
compatible signals Signals: (1) UPS on (2) UPS battery low (3) UPS bypass active
(normally open contacts) (4) utility failure
RS232C ASCII interface Provided
Options
Novell
TM
local area network Contact Toshiba for details on these options
SNMP Network Adapter
(*) Input/output figures rated for 240 volts. Output capacity will be reduced when input voltage is below 204 volts.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
Novell
TM
is a registered trademark of Novell Inc.; IBM AS/400
TM
is a registered trademark of International Business Machines, Inc.