background image

5

System Troubleshooting (continued)

Sprinklers

Possible equipment failures with causes and corrective action are listed below.

PROBLEM

POSSIBLE CAUSE – CORRECTIVE ACTION

1.

Sprinkler won't rotate

(a) Stator too large for nozzle - Use proper nozzle.
(b) Debris wedged between stator and turbine - Remove obstruction.
(c) Drive assembly defective - Replace with new drive assembly.

2.

Head sticks up

(a) Dirt in riser assembly - Flush out. (See Flushing Procedure.)
(b) Damaged riser - Replace.

3.

Poor distribution pattern

(a) Nozzle plugged with debris - Clean or replace nozzle.
(b) Nozzle orifice/stream straightener damaged - Replace nozzle.
(c) Low operating pressure - Determine why system overloaded and correct.
(d) Head misaligned during installation (two-speed only) - Realign properly.

4.

Valve won't close

(a) Leak in control tubing - Isolate and repair.

(Hydraulic 69X-01-XX)

(b) Pilot valve leak in controller - Confirm by observing constant dripping

from discharge line of controller. Refer to Controller Service Manual.

(c) Foreign object keeping valve from seating - Remove, clean and check

valve for damage. Replace if necessary.

(d) Damaged piston seal or piston assembly - Replace valve assembly.
(e) Valve not properly communicated to tube in body - Reassemble if

necessary.

5.

Valve won't open

(a) Plugged controller discharge line or discharge port in pilot valve -

(Hydraulic 69X-01-XX)

Verify by checking for discharge at discharge line when station is
activated - If no discharge, refer to Controller Service Manual.

(b) Water supply to sprinkler closed off - Determine if closure is shut-off

valve or blockage and correct.

6.

Valve won't close

(a) Leak in pilot valve assembly - Replace pilot valve assembly.

(Electric 69X-06-XX)

(b) Plugged supply screen on piston - Clean or replace screen.
(c) Manual control selector on pilot valve assembly turned to "ON" position -

Turn to "AUTO" position.

7.

Valve won't open

(a) Control (field) wires severed - Isolate and repair.

(Electric 69X-06-XX)

(b) Defective solenoid - Replace solenoid.
(c) No power to controller - Establish controller power.
(d) No power from controller to solenoid - Check for blown fuse and replace.
(e) Manual control selector on pilot valve assembly turned to "OFF" position

- Turn to "AUTO" position.

(f) No supply from main valve and piston - Remove supply tube from supply

port. If no supply port, repair valve and piston assembly.

8.

Valve leaks

(a) Damaged or blocked valve seat - Remove blockage and, if necessary,

replace valve assembly.

(b) Damaged piston seal or piston assembly - Replace valve assembly.
(c) Low pressure on supply line on hydraulic NO sprinklers - Check for low

pressure reason and correct.

9.

Several valves on different

(a) Control tubing leak which lowers supply pressure to other stations -

stations fail to close

Turn controller from station to station until a station is reached where

(Hydraulic 69X-01-XX)

only valves on that station stay open. The leak would be in the tubing on
that station - Isolate and repair.

(b) Leak in supply line to controller - Verify by checking pressure in all

control lines.

(c) Leak in controller pilot valve - Verify by constant discharge on controller -

Refer to Controller Service Manual.

(d) Plugged supply line filter - Replace filter if more than 3 psi differential exists.

All manuals and user guides at all-guides.com

Summary of Contents for 69-01

Page 1: ...hydraulic normally open or 24 Volt electric systems Sprinkler Operating Mode Electric valve in head models have three modes of operation AUTO ON and OFF Mode is set using a selector tool inserted thr...

Page 2: ...e 1 Triple Swing Joints Base Nozzle Set Nozzle Set Nozzle Set Pressure 90 91 92 Size 3 8 in Size 7 16 in Size 1 2 in PSI Rad GPM Rad GPM Rad GPM 40 50 60 78 ft 45 1 87 ft 53 7 70 82 ft 48 6 91 ft 57 2...

Page 3: ...than 2 feet per second See Table 2 below 1 Use jockey pump only to fill system at velocity fill rate of less than 2 feet per second 2 Use quick coupler keys at all tees and greens with quick coupler v...

Page 4: ...thin the system and maintains a constant pressure for optimum sprinkler operation The 690 series pilot valve is factory set to regulate at 80 or 100 PSI depending on sprinkler model Sprinkler operatio...

Page 5: ...ine if closure is shut off valve or blockage and correct 6 Valve won t close a Leak in pilot valve assembly Replace pilot valve assembly Electric 69X 06 XX b Plugged supply screen on piston Clean or r...

Page 6: ...provided on edge of stator 10 Thoroughly clean and inspect all parts Replace parts as required Note If changing nozzle to a different size appropriate stator must also be installed to ensure proper r...

Page 7: ...tube and correctly seat the snap ring See Figure 6 NOTE It is possible to install the snap ring backwards upside down See inset in Figure 6 to insure that snap ring is installed in the correct manner...

Page 8: ...om sprinkler body and cut control tubing just below tube retainer Unless pilot valve has been previously removed control tubing length will be sufficient for re connection 4 Remove tube retainer and r...

Page 9: ...9973 Spring 100 lbs Blue 1 11 89 0029 Piston 1 12 89 0005 Diaphragm Assembly 1 SERVICE PARTS AND ASSEMBLIES 89 0009 Pilot Valve Assy 50 lbs Elec 89 0010 Pilot Valve Assy 65 lbs Elec 89 0011 Pilot Valv...

Page 10: ...100 PSI 4 Full Circle 06 NPT Electric Valve In Head 92 6 Full Circle 2 Speed 08 NPT NC Valve In Head 60 120 8 Full Circle 2 Speed Pressure Regulation available on 180 180 Electric NC VIH models only A...

Page 11: ...1 19 3 3355 Piston Assy Valve Drain 1 19 89 0937 Piston Assy Valve El Hyd NC 1 20 Body 690 See Service Items 1 21 9 6002 Adapter Tubing Threaded 1 4 1 22 89 8157 Cap Poly 1 4 1 23 900 40 Retainer Tube...

Page 12: ...2001 The Toro Company Irrigation Division An ISO 9001 Certified Facility Form No 366 0041 Rev B All manuals and user guides at all guides com...

Reviews: