7
load and control terminal block points. Be sure to consult the appropriate field connection diagram included with
the manual. Make all field connections to the remote alarm functions and any other optional features.
AC POWER WIRING
Connect the AC power. Check to see that all connections are both correctly wired and tight (see torque label).
MOTOR WIRING
Connect the motor cable. Check to see that all connections are both correctly wired and tight (see torque label).
STEP 3 : FULL LOAD AMPERAGE (FLA)
Verify the FLA on the motor nameplate and rectify the overload relay settings if needed.
STEP 4 : CLOSE THE DOOR AND POWER ON
The disconnect switch handle must be in OFF position to close the door properly.
Put the disconnect switch in ON position. The controller is automatically in manual mode when powered for the
first time to avoid any motor start
STEP 5 : MOTOR ROTATION
Press START, check the motor rotation for 1 second, and Press STOP.
WRONG MOTOR ROTATION
In case of wrong rotation; put the disconnect switch in OFF position, open the door and swap two wires on motor
feeder only. Go back to STEP 5 and check the motor rotation again.
GOOD MOTOR ROTATION
When you have a good motor rotation, put the disconnect switch in OFF position.
STEP 6 : WATER CONNECTION
The controller must be connected to the pipe system according to NFPA20. The water connection is on the
bottom of the controller.
DANGER
HAZARDOUS VOLTAGE IS PRESENT IN THE ENCLOSURE WHICH WILL CAUSE
SEVERE PERSONAL INJURY OR DEATH. MAINTENANCE OR START UP SHOULD BE
PERFORMED ONLY BY EXPERIENCED LICENSED ELECTRICIANS.
ONLY QUALIFIED PERSONNEL SHOULD WORK ON OR AROUND THIS EQUIPMENT.
STEP 7 : POWER ON AND SET IPD+ BOARD
The front door mounted IPD+ membrane is described here from top to bottom, and from left to right.
• The upper right green LED is activated when the IPD is powered.
• The digital screen shows the pressure value, the Non-Auto mode, as well as all the parameters. A small Red dot
will appear on the lower right part of the screen when a timer is counting.
• The 3 vertical LED just right of the screen represent the pressure status. The upper Led is ON when the
pressure is above the cut-out, the middle LED is ON when the pressure is between the cut-out and the cut-in, and
the bottom LED is ON when the pressure is below the cut-in.
• The 2 motor images show the motor run cause, whether it is HAND or AUTO.
• The Green button creates a HAND run cause. It is always ready to start the pump.
• The Red button stops the engine and has a latency of 2 seconds, to prevent jogging the pump.
• The UP/+ button is use to increase a parameter value. It is also a shortcut to show the cut-out value when in
NORMAL mode.
• The DOWN/- button is use to decrease a parameter value. It is also a shortcut to show the cut-in value when in
NORMAL mode.
• The LEFT button is use to navigate between the parameters.