Step 5: 
Set the warning period for 1 or 5 minutes using
switch # 4. See table for desired timing.

Step 6 (optional):
If it is desirable to have the auxiliary load on
momentarily only (4 seconds i.e. for bell or other
warning signal) place the 

special switch down in

the momentary position (see below).

Step 7: 
Remote ON/OFF momentary push buttons can be
connected at the remote input terminal between C
& ON to activate extended time, and C & OFF to
disable extended time.

MAIN SWITCH 
CONFIGURATION

SPECIAL SWITCH FOR 
AUXILIARY LOAD ONLY 

UP (Main) Position:
ON for same 1 or 5 minute 
period as set by main  switch 
#4 (see above).

DOWN (Momentary) Position:
Auxiliary load is on for 4 seconds only,
but main load is on for the warning period set
by main switch #4 (see above)

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

TIME

SET

1

2

3

*

*

*

*

*

*

*

ON

4

1/2 HR

1 HR

1-1/2 HR

2 HR

6 HR

9 HR

12 HR

TEST

OFF

OFF

OFF

OFF

ON

ON

ON

ON

*Switch 4 (ON) –   5 Minute Warning Period

*Switch 4 (OFF) – 1 Minute Warning Period

ON

SW1

OFF

1

2

3

4

MAIN

MOM

C5

C4

TORK

®

MLI-142(B)

1 GROVE STREET, MT. VERNON, NY 10550  TEL: 914-664-3542

FAX: 914-664-5052

WIRING DIAGRAMS

Important Note:
When the Lighting Delay Switch is first activated –

A. If a time switch is connected and is set to ON,

the main load will remain ON.

B. If no time switch is used or if one is connected

but is set to OFF, the main load will turn ON for
10 minutes. At the end of the 10 minute period,
the warning circuit turns on for 4 seconds, 1
minute, or 5 minutes. The main load will remain
ON for the 1 or 5 minute warning period. If an
extension of time is required for the main load,
press the remote ON button momentarily, the
warning circuit will turn off, and the main load
will remain on for an additional 1/2 - 12 hour
extension of time.

OFF

ON

NO

C

NC

REMOTE
INPUT

TIME SWITCH

INPUT

AUX. OUTPUT

TERMINALS  

MAIN LOAD OUTPUT

TERMINALS  

INPUT POWER

MOMENTARY
PUSH-BUTTON SWITCH

AUX 

LOAD

LOAD

H

N

N

120

208
240 

277

VAC

NC NC 

NO NO 

C

C

H

N

H

N

H

N

TORK TIME SWITCH

OUTPUT TERMINALS

C   ON OFF

DO NOT APPLY

VOLTAGE 

CAUTION: Turn power off at main circuit prior
to installation or when servicing this unit.