43
■
Protection OFF timer time setting for OUT1/Protection ON timer time setting for OUT1
Character
Name
Description
Initial Value
1
SET3
CNT
Setting Mode Selection
Screen
Control Parameter Mode
Settings about Control
24
FDT1
Protection OFF timer
time setting for OUT1
Setting Range: 0–99
Setting Unit: Minute
0
25
NDT1
Protection ON timer time
setting for OUT1
Setting Range: 0–99
Setting Unit: Minute
0
Sets the shortest retaining time of ON or OFF during ON/OFF control.
The time that was set after the switching of output retains the state of the output.
Example: Action of which Output 1 Protection OFF Timer (Fdt1) was set
■
Setting of the Loop Abnormality PV Threshold of Output 1
Character
Name
Description
Initial Value
1
SET3
CNT
Setting Mode Selection
Screen
Control Parameter Mode
Settings about Control
26
MV2
Manipulated Variable of
Output 1
Display Range: 0.0%–100.0%
Setting Range:
MLL2
-
MLH2
0
0
It shall be used to monitor the manipulated variable of Output 2 and to set the manipulated variable during manual control.
The screen displays the manipulated variable of Output 2.
Setting of manipulated variable is not allowed at normal control.
Setting of manipulated variable is allowed only when the control mode is set to manual control.