![TOHO TTM-000W Series Operation Manual Download Page 33](http://html1.mh-extra.com/html/toho/ttm-000w-series/ttm-000w-series_operation-manual_1124805033.webp)
- 33 -
Iden-
tifier
Relative
Address
Absolute
Address
Charac-
ter
Name
R/W
Description
CNT
002Ah 40043
Setting of Control Type
R/W
R/W of the Setting of Control Type
DIR
002Ch 40045
Switching of Direct
R/W
R/W of the Switching of Direct Ac-
M(1
002Eh 40047
Manipulated (ariable of
R/W
R/W of the Manipulated (ariable of
TUN
0030h 40049
Setting of Tuning Type
R/W
R/W of the Setting of Tuning Type
ATG
0032h 40051
9. AT Coefficient
R/W
R/W of AT Coefficient
ATC
0034h 40053
AT Sensitivity
R/W
R/W of AT Sensitivity
□P1
0036h 40055
Setting of the Propor-
R/W
R/W of the Setting of the Proportional
□I1
0038h 40057
Setting of Reset Time
R/W
R/W of the Setting of Reset Time
□D1
003Ah 40059
Setting of Derivative
R/W
R/W of the Setting of Derivative Time
□T1
003Ch 40061
Setting of the Propor-
R/W
R/W of the Setting of the Proportional
ARW
003Eh 40063
Anti-Reset Windup
R/W
R/W of Anti-Reset Windup
MH1
0040h 40065
Maximum Limit of M(
Limiter
R/W
R/W of the Maximum Limit of M( Limiter
ML1
0042h 40067
Minimum Limit of M(
Limiter
R/W
R/W of the Minimum Limit of M( Limiter
□C1
0044h 40069
Setting of the Control
R/W
R/W of the Setting of the Control
CP1
0046h 40071
Setting of the OFF Point
of Output 1
R/W
R/W of the Setting of the OFF Point of
Output 1
M(2
0048h 40073
Manipulated (ariable of
R/W
R/W of the Manipulated (ariable of
□P2
004Ah 40075
Setting of the Propor-
R/W
R/W of the Setting of the Proportional
□T2
004Ch 40077
Setting of the Propor-
R/W
R/W of the Setting of the Proportional
MH2
004Eh 40079
Maximum Limit of M(
Limiter
R/W
R/W of the Maximum Limit of M( Limiter
ML2
0050h 40081
Minimum Limit of M(
Limiter
R/W
R/W of the Minimum Limit of M( Limiter
□C2
0052h 40083
Setting of the Control
R/W
R/W of the Setting of the Control
CP2
0054h 40085
OFF Point of Output 2
Settings
R/W
R/W of the OFF Point of Output 2
PBB
0056h 40087
Manual Reset
R/W
R/W of the Manual Reset
□DB
0058h 40089
Setting of Dead Band
R/W
R/W of the Setting of Dead Band
RP1
005Ah 40091
Setting of S( Ramp Time
R/W
R/W of the Setting of S( Ramp Time
RP2
005Ch 40093
Setting of S(2 Ramp Time
R/W
R/W of the Setting of S(2 Ramp Time
EIF
005Eh 40095
P( Event Output 1
Function
R/W
R/W of the P( Event Output 1 Function
E1H
0060h 40097
Maximum Limit of Event
Output 1
R/W
R/W of the Maximum Limit of Event Output
1
E1L
0062h 40099
Minimum Limit of Event
Output 1
R/W
R/W of the Minimum Limit of Event Output
1
E1C
0064h 40101
Event Output 1 Sensi-
tivity
R/W
R/W of the Setting of Event Output 1
Sensitivity
E1T
0066h 40103
Event Output 1 Delay
Timer Setting
R/W
R/W of the Setting of Event Output 1
Delay Timer
E1B
0068h 40105
Special Event Output 1
Function
R/W
R/W of the Setting of Special Event
Output 1 Function
E1P
006Ah 40107
Event Output 1 Polarity
Settings
R/W
R/W of the Setting of Event Output 1
Polarity
CM1
006Ch 40109
CT Input Monitor
R
R of CT Input Monitor
CT1
006Eh 40111
Event Output 1 Current
Abnormality
R/W
R/W of the Setting of Event Output 1
Current Abnormality