background image

<SET1 : 

Input setting mode

SET1

 

INP

1. 

Setting item selection screen

2. 

Input type setting

Select input type

  0

0

 INP

3. 

PV compensation gain setting

0.50

2.00

 PVG

 1

00

4. 

PV compensation zero setting

-199

999

-199.9

999.9

 PVS‘

   

0

5. PV 

Filter setting

0.0

99.9

 PDF

  0

0

6. 

Decimal point setting

   0:

Not required

0.1

Required

(Except R/S/B Thermocouple)

  DP

   

0

7. 

Temperature unit setting

℃:

Celsius

℉:

Fahrenheit

 C/F

  

*C

SET2 : 

Key function setting mode

SET2

 

KEY

1. 

Setting item selection screen

Setting related to 

<SET3 : 

Control setting mode

SET3

 

CNT

1.

Setting item selection screen

<SET4 : EV1

 setting mode

SET4

 

AL1

Setting related to control

Setting related to input

key functions

<SET5 : EV2

 setting mode

SET5

 

AL2

<SET6 : 

Timer setting mode

SET6

TIME

<SET7 : LCD

 setting mode

SET7

 LCD

<SET0 : 

Priority screen setting mode

>

SET0

 PR1

Setting for priority screen
(Refer to Ex.1.)

M key

2. 

Priority screen 1 setting

PRI1

 OFF

Select 1st screen on

Run mode B

Select 2nd screen on

Select 3rd screen on

Select 4th screen on

Select 5th screen on

3. 

Priority screen 2 setting

PRI2

 OFF

4. 

Priority screen 3 setting

PRI3

 OFF

5. 

Priority screen 4 setting

PRI4

 OFF

6. 

Priority screen 5 setting

PRI5

 OFF

7. 

Priority screen 6 setting

PRI6

 OFF

8. 

Priority screen 7 setting

PRI7

 OFF

9. 

Priority screen 8 setting

PRI8

 OFF

10. 

Priority screen 9 setting

PRI9

 OFF

When select PID control

When select ON/OFF control

  Thermocouple





  

00

  

01

  

02

  

03

  

04

  

05


Pt

100

JPt

100

  

06

  

10

  

11

●Setting mode

●POWER ON

RUN mode 

A

Primary screen

Measured value

Set the temperature
required

Set value

(Press for 4 seconds)

▲KEY

▼KEY

▲KEY

▼KEY

Protect setting mode

Setting screen

Mode to set the protection level

“Input type setting screen” appears for 4seconds,

 

then it will oriceed to “Run mode” .

PTLV

   0

Non-Protect

  

 0

  

 1

  

 2

  

 3

parameters except for the following:

Setting Change not possible.

PV compasation zero setting
Alarm reset
AT start/reset
Proportional band setting for OUT1/OUT2
Integral time setting
Deviative time setting
Control sensitivity setting for OUT1/OUT2
Upper limit setting for EV1/EV2
Lower limit setting for EV1/EV2

The Setting Mode Parameter blinds 

Setting change for SV/Priority Screen is Possible

B

Priority screens (1

9)

 

Priority displays by setting 

and shows max.9 screens by setting.

EX1

Priority screens & its setting

This function enables the selection of the most necessary screen indication

from all the screen indication found in the setting mode,and assign it to

eg

Basic screen

  

OUT1 manipulated value   →  Setting high limit for EV1

*

Screen is shifted when pressing M key each time.

the RUN mode on priority basis.

Please select priority screen indication through the priority screen setting mode.

EX2

  

Function

 key works

This function is to enable F key to use as a specific key,for the following actions

selected in F key setting belonging to setting mode.

1. Digit shift

Setting digit shift is enabled when setting value is changed.

2. RUN/READY

Control stop(READY)  and control performance(RUN) are

alternately switched by F key.

3. AT Start / Reset

AT(Auto -Tuning) starts instantly after pressing F key.

Start and Reset are alternately switched by F key.

4. Timer Start / Reset

Press once for function.

Press once for function.

5. Alarm Reset

6. Enter

Function

Effective

in all modes

Effective only

in Operating mode

EX3

  To select PID

Features of type A,B,FUZZY

TypeA

If control is unstable under self-tuning,

please change to type A ,B or FUZZY and also ON/OFF control.

TypeB
FUZZY

the RUN mode on priority basis.

Basic PID
Over shoot protection PID
Effectively control the over shoot in the beginning of PID control. 

●EX4.   ARW (Anti-Reset-Windup)

ARW take effect for overshooting by over-integral of PID action.

ARW controls integral action (PV accords with SV).

If integral value goes down,it takes effects.
If integral value is set “0” ,it stops integral action.

Table1. To select input sensors and setting range.     unit : 

Symbol

K Thermocouple

Low limit

~ 

High limit

-200 ~ 1372

0.0 Setting

-200 ~  850

0 ~ 1700

-200 ~  400

-200 ~ 1300

   0 ~ 1700

0 ~ 1800

Pt100

-200 ~  500

JPt100

-200 ~  500

OPERATION FLOW AND SETTING MENU

*12*13

(Press for 2 seconds)

Setting change is possible with SV only.

The priority screen is with indication/

All setting mode parameters will be blinded.

SV is with indication / setting change not possible.

not possible.

 

Priority Screen is with indication / setting change

 

All setting mode parameters will be blinded.

Press for 

2 seconds

Effective 

in all modes

"
"
"
"
"
"

Select 6th screen on

Select 7th screen on

Select 8th display on

Select 9th screen on

M key

M key

M key

M key

M key

M key

M key

M key

M key , return to 1 

M key , return to 1 

M key

M key

M key

M key

M key

"
"
"
"
"
"

M key

M key

M key

M key

M key

seconds

times

-199.9 ~  999.9
-199.9 ~  850.0

-199.9 ~  400.0
-199.9 ~  999.9


-199.9 ~  500.0
-199.9 ~  500.0

*1

No indication when the type of control OUT1 is ON/OFF Control.

*2

No indication when the type of control OUT1 is PID Control.

*3

No indication when the OUT1 loop error determination time is “0” .

*4

 No indication when the type of control OUT2 is either “None” or “EV2” .

*5

No indication when the type of control OUT2 is ON/OFF Control.

*6

No indication when the type of control OUT2 is PID Control.

*7

No indication when the OUT2 loop error determination time is “0” .

*8

No indication when the EV1 Function is set at “No Function” .

*9

No indication when the EV1 Function is not used in the Upper Limit Alarm.

*10

No indication when the EV1 Function is not used in the Lower Limit Alarm.

*11

No indication when the EV1 & 2 Functions to “No Function” .

*14

No indication when EV2 Function is set at “No Function” .

*15

No indication when the EV2 Function is not used in the Upper Limit Alarm.

*16

No indication when the EV2 Function is not used in the Lower Limit Alarm.

*17

No indication when the EV 1 & 2 Functions to “No Function” .

*12

No indication when Option-B is not specified.

*13

No indication when the type of Control OUT2 is set to anything other than “EV2” .

*18

No indication when the Timer Output is set to “Timer Not Used” .

*19

No indication when the Timer Function is set to other than “SV Start” .

2. 

Function key function setting

  FU

  

00++

① 

Function setting

0

 

:

 

None

1

 

:

 

Digit shift

2

 

:

 

RUN/READY

3

 

:

 

AT start/stop

4

 

:

 

Timer start/stop

5

 

:

 

Alarm reset

6

 

:

 E

NTER

② 

Pressing time setting

0

 

:

 

None

1

 

:

 

Pressing time 1 second

2

 

:

 

Pressing time 2 seconds

3

 

:

 

Pressing time 3 seconds

4

 

:

 

Pressing time 4 seconds

5

 

:

 

Pressing time 5 seconds

3. 

Key-lock setting

   

0

 LOC

Lock OFF
Lock all
Lock run mode
Lock except run mode

Protect Level Setting is not subjected to 

Key-Lock Setting.

   

0

   ‘

1

   ‘

2

   ‘

3

4. 

Alarm reset

 0 

0

ALRS

No alarm occurrence
Only EV1 is occurring
Only EV2 is occurring

 0 

0

 0 

1

 1 

0

 1 

1

Both EV1/EV2 are occurring

Screen for Alarm reset of EV1/EV2

Press F key for 1 second to reset the alarm.

 

(The indication momentarily disappears as 

 

the Alarm reset is executed). 

2. 

SV limiter upper limit

 SLH‘

1200

3. 

SV limiter lower limit

 SLL‘

   0

4. 

Control mode setting

 

RUM

  MD

Control start
Control stop 
Manual

 

RUN

 

RDY

 

MAN

Setting for control mode

5. 

Control type setting

 CNT

020++

Function

0

 

:

 

TypeA

1

 

:

 

TypeB

2

 

:

 

Fuzzy

Control type of OUT2

0

 

:

 

None

1

 

:

 

PID control

2

 

:

 

ON/OFF control

3

 

:

 

EV2 output

Coutrol type of OUT1

1

 

:

 

PID control

2

 

:

 

ON/OFF control




When Option B is not specified,Control type of 

OUT2 shall be fixed at “None” .

6. 

Forward/reverse operation setting

0

Reverse operation

 DIR‘

   

0

1

Forward operation

7. 

Operating amount for OUT1

 MV1‘

  0

0

M key

M key

8. 

Tuning type setting

   

1

 TUN

*1

Auto-tuning

Self -tuning

Auto-tuning

Self -tuning

Auto-tuning

  

 1

  

 2

  

 3

  

 4

  

 5

OUT

: OUT1

: OUT2

: OUT2

: OUT1/OUT2

9. 

AT coefficient setting

 ATG

  1

0

10. 

AT sensitivity setting

 ATC

   

2

11.

 AT start/stop

  AT

 

OFF

AT stop
AT start

※AT 

start and ATstop are alternately switched 

 

OFF

  

ON

12. 

Proportional band setting for OUT1

  P1

  3

0

13. 

Integral time setting

   I

   

0

14. 

Deviative time setting

   D

   

0

15. 

Proportional cycle setting for OUT1

  T1

  

20

16. 

ARW setting (see Ex.4)

 ARW

11

0

0

17. 

Operating amout limiter upper limit for OUT1

MLH1

10

0

0

18. 

Operating amout limiter lower limit for OUT1

MLL1

  

0

0

19. 

Sensitivity setting for OUT1

  C1

   1

21. 

Loop anormaly time setting for OUT1

LOP1

   0

seconds

22. 

Loop anormaly PV change threshold for OUT1

 PS1

   0

23. 

Loop anormaly PV threshold for OUT1

 TS1

   0

24. 

Protection OFF timer time setting for OUT1

FDT1

   

0

25. 

Protection ON timer time setting for OUT1

NDT1

   

0

26. 

Operating amount for OUT2

Displays operating amount for OUT2

and set the amount on manual control.

 MV2‘

  0

0

0.0

100.0(

)

MLL2

MLH2

(%)

27. 

Proportional band setting for OUT2

.

10~10

.

00

  P2

 1

00

28. 

Proportional cycle setting for OUT2

  T2

  

20

29. 

Operating amout limiter upper limit for OUT2

MLH2

10

0

0

MLL2

100.0

30. 

Operating amout limiter lower limit for OUT2

MLL2

  

0

0

0.0

MLH2

20. 

OFF point position setting for OUT1

 CP1

   0

*1

*2

*3

*3

*2

*2

*4

*4 *5

*4 *5

*4 *5

*4 *5

*1

*1

*1

*1

*1

*1

*1

*1

*1

*2

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

 key

Go to 21

31. 

Sensitivity setting for OUT2

  C2

   1

32. 

OFF point position setting for OUT2

 CP2

   0

*4 *6

*4 *6

33.

Loop anormaly time setting for OUT2

LOP2

   0

 ※

At “0” setting,there is no loop error determination.

34. 

Loop anormaly PV change threshold for OUT2

 PS2

   0

35. 

Loop anormaly PV threshold for OUT2

 TS2

   0

36. 

Protection OFF timer time setting for OUT2

FDT2

   

0

37. 

Protection ON timer time setting for OUT2

NDT2

   

0

*4 *7

*4

38. 

Balance less / Bump less

 BMP

 

  1

No Balance less / Bump less function
With Balance less / Bump less function

 

  0

  

 1

39. 

Manual reset setting

 PBB

  

0

0

0.0

100.0%

 

-100.0

100.0%

Heat / Cool

*1

40. 

Dead band setting

  DB

   0

-100

100

*4

41. 

Ramp time setting

 RMP

  

0

0

Ramp function OFF at  0.0

42. 

Control back up function setting

 PWZ

  

0

0

0.0

10.0

*4 *7

*6 *4

2. 

EV1 setting mode

EV1 alarm function 1 setting

A1F1

 

000++

Function

0

 

:

 

None

1

 

:

 

Deviation upper and lower limits

2

 

:

 

Deviation upper limit

3

 

:

 

Deviation lower limit

4

 

:

 

Deviation range

5

 

:

 

Absolute value upper and lower limits

6

 

:

 

Absolute value upper limit

7

 

:

 

Absolute value lower limit

8

 

:

 

Absolute value range



Control mode interlocking function 

Add-on function

0

 

:

 

None

1

 

:

 

Hold

2

 

:

 

Standby

3

 

:

 

Delay

4

 

:

 

Hold

Standby

5

 

:

 

Hold

Delay

6

 

:

 

Standby

delay

7

 

:  Hold

standby

delay

3. 

EV1 alarm upper limit setting

 

 A1H

   0

-1999

3276

 

or

 

-199.9

999.9

 ※

In case of thermocouple R/S/B : -1999

3276

4. 

EV1 alarm lower limit setting 

 A1L

   0

5. 

EV1 alarm sensitivity setting 

 A1C

   0

0

999 or 0.0

999.9

6. 

EV1 alarm delay timer setting 

 A1T

   0

0

9999

seconds

7. 

EV1 alarm function 2 setting 

EV1 alarm function 2 setting 

for PV error

A1F2

 

000++

Function

0

 

:

 

None

1

 

:

 

PV error



Add-on function

0

 

:

 

None

1

 

:

 

Hold

2

 

:

 

Delay

3

 

:

 

Hold

Delay

8. 

EV1 alarm function 3 setting 

EV1 alarm function 3 setting

A1F3

  

00++

Function

0

 

:

 

None

1

 

:

 

Loop error


Add-on function

0

 

:

 

None

1

 

:

 

Hold

for loop anormaly

9. 

EV1 alarm polarity setting 

 A1P

 

  0

Normal open
Normal close

 

  0

  

 1

*8 *9

*8 *10

*8

*11

*12*14
*15

*12*14

*12*14

*12*17

*12

*12

*12

*16

0

 

:

 

All modes

1

 

:

 

RUN/ MANUAL  mode only

2

 

:

 

RUN mode only

*12

M key

M key

M key

M key

M key

2.

 Timer output setting

   

0

 TMO

Non-use timer function
Control
EV1 output
EV2 output

“3” is not selectable when Option-B is not specified.

   

0

   ‘

1

   ‘

2

   ‘

3

3. 

Function setting

   

1

 TMF

Auto start

Manual start
EV1 start
Auto start
Manual start

  

 1

  

 2

  

 3

  

 4

  

 5

EV1 start
SV start
EV2 start

  

 6

  

 7

   

8

EV2 start

   

9

( ON   delay

 

)

( ON   delay

 

)

“8” and “9” are not selectable 

when Option-B is not specified.

4. 

Unit setting

 H/M

 

  1

Hour / Minute
Minute / second

 

  1

  

 2

5. 

Start SV permissible range setting

 TSV

   0

6. 

Time setting

 TIM

00

00

99

59

Hour/Minute

00

00

99

59

Minute/second)

7. 

Remaining time monitor

 TIA

00 00

Screen for remaining time monitor

2. 

Brightness setting

 LLV

 100

5

100

3. 

Dimming function setting

LRFT

   0

0

9999

seconds

 ※

No dimming function when set to “0” .

4. 

Dimming Brightness setting

LRLV

   5

0

100

00 00

*18

*18*19

*18

*18

*18

M key

M key

M key

M key

M key , return to 1

M key

M key

0.1

10.0

times

%  per  

SLL

SLH

 

seconds 

1

120

%

0.0

110.0

%

MLL1

100.0

%

0.0

MLH1

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

0.1

200.0

seconds 

0

3600

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

*6 *4

1. 

Setting item selection screen

Start and Reset are alternately switched by F key.

Digit under selection will blink.

M key , return to 1 

M key

M key

Setting range : 

 

Setting range : 

 

Setting unit  : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

by F key. 

 0

999 or 0.0

999.9

Setting range : 

 

Setting unit  : 

 

-199

999 or -199.9

999.9

Setting range : 

 

Setting unit  : 

 

0

9999

seconds

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

 ※

At “0” setting,there is no loop error 

PV change determination.

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

 ※

At “0” setting,there is no loop error determination.

Setting range: 

 

Setting unit  : 

 

seconds 

Display amount  : 

 

Setting amount   : 

 

Setting range : 

 

Setting unit  : 

 

Low to high limit

 ※

Keep the difference of more than 5 degrees(

℃ or ℉)

Setting range : 

 

Setting unit  : 

 

Low to high limit

between Low 

and high limit of the SV limiter.

 ※

At “0” setting,there is no loop error 

PV threshold determination.

 ※

At “0” setting,there is no loop error 

PV change determination.

 ※

At “0” setting,there is no loop error 

PV threshold determination.

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

0

99

Minuites

Setting range : 

 

Setting unit  : 

 

0

99

Minuites

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting range : 

 

-100.0

100.0

 or 

Setting unit  : 

 

/min.  or  

/min.

Setting range : 

 

Setting unit  : 

 

Control back up function OFF at 0.0

Setting range : 

 

Setting unit  : 

 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

 or 

1.

Setting item selection screen

Setting range: 

 

Setting unit  : 

 

 or 

-1999

3276

 

or

 

-199.9

999.9

 ※

In case of thermocouple R/S/B : -1999

3276

Setting range: 

 

Setting unit  : 

 

 or 

Setting range: 

 

Setting unit  : 

 

 or 

Setting range : 

 

Setting unit  : 

 

M key

M key

M key

Control mode interlocking function 

0

 

:

 

All modes

1

 

:

 

RUN/ MANUAL  mode only

2

 

:

 

RUN mode only

M key , return to 1 

M key , return to 1 

2. 

EV2 setting mode

EV2 alarm function 1 setting

A2F1

 

000++

Function

0

 

:

 

None

1

 

:

 

Deviation upper and lower limits

2

 

:

 

Deviation upper limit

3

 

:

 

Deviation lower limit

4

 

:

 

Deviation range

5

 

:

 

Absolute value upper and lower limits

6

 

:

 

Absolute value upper limit

7

 

:

 

Absolute value lower limit

8

 

:

 

Absolute value range



Control mode interlocking function 

Add-on function

0

 

:

 

None

1

 

:

 

Hold

2

 

:

 

Standby

3

 

:

 

Delay

4

 

:

 

Hold

Standby

5

 

:

 

Hold

Delay

6

 

:

 

Standby

delay

7

 

:  Hold

standby

delay

3. 

EV2 alarm upper limit setting

 

 A2H

   0

-1999

3276

 

or

 

-199.9

999.9

 ※

In case of thermocouple R/S/B : -1999

3276

4. 

EV2 alarm lower limit setting 

 A2L

   0

5. 

EV2 alarm sensitivity setting 

 A2C

   0

0

999 or 0.0

999.9

6. 

EV2 alarm delay timer setting 

 A2T

   0

0

9999

seconds

7. 

EV2 alarm function 2 setting 

EV2 alarm function 2 setting 

for PV error

A2F2

 

000++

Function

0

 

:

 

None

1

 

:

 

PV error



Add-on function

0

 

:

 

None

1

 

:

 

Hold

2

 

:

 

Delay

3

 

:

 

Hold

Delay

8. 

EV2 alarm function 3 setting 

EV2 alarm function 3 setting

A2F3

  

00++

Function

0

 

:

 

None

1

 

:

 

Loop error


Add-on function

0

 

:

 

None

1

 

:

 

Hold

for loop anormaly

9. 

EV2 alarm polarity setting 

 A2P

 

  0

Normal open
Normal close

 

  0

  

 1

0

 

:

 

All modes

1

 

:

 

RUN/ MANUAL  mode only

2

 

:

 

RUN mode onl

M key

M key

M key

M key

M key

Setting range: 

 

Setting unit  : 

 

 or 

-1999

3276

 

or

 

-199.9

999.9

 ※

In case of thermocouple R/S/B : -1999

3276

Setting range: 

 

Setting unit  : 

 

 or 

Setting range: 

 

Setting unit  : 

 

 or 

Setting range : 

 

Setting unit  : 

 

M key

M key

M key

Control mode interlocking function 

0

 

:

 

All modes

1

 

:

 

RUN/ MANUAL  mode only

2

 

:

 

RUN mode only

M key , return to 1 

1.

Setting item selection screen

EV2 output function setting

1.

Setting item selection screen

Setting concerned with
timer parameters 

EV1 output function setting

1. 

Setting item selection screen

Setting related to LCD

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

M key

M key

M key

M key , return to 1 

( ON   delay

 

)

( OFF delay

 

)

( OFF delay

 

)

( OFF delay

 

)

( OFF delay

 

)

( ON   delay

 

)

( OFF delay

 

)

0

999 or 0.0

999.9

Setting range: 

 

Setting unit  : 

 

 or 

Setting range: 

 

 0

999 or 0.0

999.9

 0

999 or 0.0

999.9

 0

999 or 0.0

999.9

 0

999 or 0.0

999.9

 0

999 or 0.0

999.9

-199

999 or -199.9

999.9

0

9999

 0.0

999.9

 0

999 or 0.0

999.9

Setting range: 

 

Setting unit  : 

 

0

3600

1

120

Setting range : 

 

Setting unit  : 

 

seconds 

Setting range : 

 

Setting unit  : 

 

Setting range : 

 

Setting unit  : 

 

M key (

Go to 33

M key

M key

M key

※Timer 

start  and stop are alternately 

switched by F key.

0

99

Minuites

0

99

Minuites

~~~~

Displays whenever input value exceeds the high limit of display range.

Also displays when the wire is snapped off thermocouple and that of R.T.D.

____

Displays whenever input value exceeds the low limit of display range.

ERR0cv

Displays at memory error.

ERR1cv

Displays at input circuit error.

ERR2cv

Displays when auto-tuning does not end after 3 hrs., 

or when error occurs during the auto-tuning.

Displays when the parameter change is attempted during key lock mode.

 LOC

Displays when the control mode change is attempted 

FUNC

during which function keys are allocated to RUN/READY.

Displays during auto-tuning.

  AT

Displays when the control mode change is attempted 

TIME

Other Display Indication

during which the timer is in use..

TOHO ELECTRONICS INC.

2-4-3 NISHIHASHIMOTO MIDORI-KU SAGAMIHARA KANAGAWA

252-0131 JAPAN

Phone: +81-50-3535-9960  Fax: +81-42-700-2118

[email protected]

http://www.toho-inc.com

Head office:

E-Mail:

URL:

▲KEY

▼KEY

▲KEY

▼KEY

▲KEY

▼KEY

▲KEY

▼KEY

▲KEY

▼KEY

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

M key

Run mode B

Run mode B

Run mode B

Run mode B

Run mode B

Run mode B

Run mode B

Run mode B

Magnification to 

MV1

 

Displays operating amount for OUT1

and set the amount on manual control.

0.0

100.0(

)

MLL1

MLH1

(%)

Display amount  : 

 

Setting amount   : 

 

 ※

Keep the difference of more than 5 degrees(

℃ or ℉)

between Low 

and high limit of the SV limiter.

M key

When select PID control

When select ON/OFF control

Blind setting mode

****

  

ON

Value is indicated.
No indication

 

 ON

 

OFF

**** :

Selected parameter is indicated.

M key (

Press for 10 seconds)

Indication disappears momentarily

SET0

  ON

SET1

  ON

SET2

  ON

SET3

  ON\

SET4

  ON

SET5

  ON

SET6

  ON

SET7

  ON

PRI1

  ON

 INP

  ON

  FU

  ON

 SLH

  ON\

A1F1

  ON

A2F1

  ON

 TMO

  ON

 LLV

  ON

M key

M key

M key

M key

M key

M key

M key

M key

 to 

SET0

M key (

Press for 2 seconds)

Reset the power for Blind setting mode OFF.

Shift to Blind setting mode

 ON/OFF is changed by F key.

●POWER ON

“Input type setting screen” appears for 4 seconds,

 

then it will procceed to “Run mode” .

●RUN mode

F

 key (

Press for once)

M

 key (

Press for once)

●RUN mode

Please select parameters to be blinded 

through the Blind setting mode. 

Reviews: