19
6.4 Composition of an RTU response message (transmitted from this product
to a high-level computer)
For the codes from a) to h), see "6.5 Description of RTU codes."
6.4.1 Response message for a read request message
a) Slave address
01H
b) Function code
03H
d) Number of byte items
04H
Number of registers
×
2
g)
Data for the first register
(a low-level word)
High level
0AH
③
Data composition is
①
,
②
,
③
,
and
④
H. (
①
represents 1
byte.)
Low level
A1H
④
Data for the first register
(a high-level word)
High level
00H
①
Low level
00H
②
e) CRC-16
Low level
09H
High level
A8H
6.4.2 Response message for a write/store request message
a) Slave address
01H
b) Function code
10H
c) Register address
High level
01H
First register address
Low level
00H
d) Number of registers
High level
00H
Fixed at 2
Low level
02H
e) CRC-16
Low level
34H
High level
40H
6.4.3 Response message in the case of an error
a) Slave address
01H
b) Function code
83H
←
In the case of an error, the function
for the request m 80H is
entered.
h) Error code
03H
e) CRC-16
Low level
31H
High level
01H