GENERAL INSTALLATION DATA

  

This equipment is designed and sold for commercial use only by personnel trained and experienced 

in its operation and is not sold for consumer use in and around the home nor for use directly by the 

general public in food service locations. For equipment to be used by the general public, please 

contact the factory.

This gas appliance  is equipped for the types of gas indicated on the nameplate mounted on the  front 

panel. It is shipped adjusted for use on natural gas.

The installation of the Appliance should conform to the NATIONAL FUEL GAS CODE "ANSI 

Z223.1 - LATEST EDITION" AND ALL LOCAL GAS COMPANY RULES AND REGULATIONS.

IN CANADA INSTALLATION SHALL BE IN ACCORDANCE WITH THE CURRENT 

CAN/CGA-B149.1 NATURAL GAS INSTALLATION CODE OR CAN/CGA-B149.2 

PROPANE INSTALLATION CODE AND LOCAL CODES WHERE APPLICABLE.

WARNING

: Improper installation, adjustment, alteration, service or maintenance 

can cause property damage, injury or death. Read the installation, operating and 

maintenance instructions thoroughly before installing or servicing the equipment.

FOR YOUR SAFETY 

DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN 

THE VICINITY OF THIS OR ANY OTHER APPLIANCE. KEEP THE APPLIANCE AREA CLEAR 

AND FREE FROM COMBUSTIBLES.

This appliance, its pressure regulator and its individual shutoff valve must be disconnected from the 

gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 

PSIG. This appliance and its pressure regulator must be isolated from the gas supply piping system by 

closing its individual manual shutoff valve during any pressure testing of the gas supply piping system 

at test pressures equal to or less than 1/2 PSIG. For your protection, we recommend a qualified 

installing agency install this appliance. They should be familiar with gas installations and your local 

gas requirements. In any case, your gas company should be called to approve the final installation. 

In addition, there should be posted, in a prominent location, detailed instructions to be followed in the 

event the operator smells gas. Obtain the instructions from the local gas supplier.

LEVELING UNIT

Units are shipped with feet detached.  To attach feet, remove the grates, lay unit on it's side and screw 

feet into sockets on bottom.  Level unit by adjusting the (4) feet which have an adjustment of 1-3/4" for 

accurate and perfect line-up with other Star-Max series units. 

DO NOT REMOVE FEET.

GAS PIPING

Gas piping shall be new, clean and of such size and so installed as to provide a supply of gas sufficient 

to meet the full gas input of the appliance. If the appliance is to be connected to existing piping, it 

shall be checked to determine if it has adequate capacity. Joint compound (pipe dope) shall be used 

sparingly and only on the male threads of the pipe joints. Such compounds shall be resistant to the 

action of L.P. gases. WARNING: Any loose dirt or metal particles which are allowed to enter the gas 

lines on the appliance will damage the automatic valve and affect its operation. When installing this 

appliance, all pipe and fittings must be free from all internal loose dirt.

CAUTION

CAUTION

Summary of Contents for TMHP2

Page 1: ...1 TMHP2 TMHP4 GAS HOT PLATES Models TMHP2 TMHP4 TMHP6 Installation and Operation Instructions 2M Z12969 Rev March 13 2013 is a registerd trademark of Toastmaster A Middleby Company All rights reserved ...

Page 2: ...2 ...

Page 3: ...pliance and its pressure regulator must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG For your protection we recommend a qualified installing agency install this appliance They should be familiar with gas installations and your local gas requir...

Page 4: ...d at the factory to prevent entry of dirt Do not remove this seal until the actual connection is made to the gas supply line CHECKING FOR GAS LEAKS Soap and water solution or other material acceptable for the purpose shall be used in locating gas leakage Matches candle flame or other sources of ignition shall not be used for this purpose AIR SUPPLY Provisions for adequate air supply must be furnis...

Page 5: ...rt unit from natural to propane gas follow these instructions 1 Set regulator outlet pressure to 10 water column A 1 8 pipe plug on the manifold can be removed for attaching a pressure gauge Remove the slotted cover from the pressure regulator and invert the plug Replace the cover on the regulator and plug on the manifold Regulator is now set at 10 W C 2 Remove natural gas orifices 46 for all mode...

Page 6: ...6 MODEL TMHP2 TMHP4 TMHP6 Gas Hotplates SK2431 REV 8 26 09 1 2 3 4 5 6 8 9 10 11 14 15 16 23 17 18 19 20 21 22 12 13 7 ...

Page 7: ...P6 5 I4 602013 1 PILOT TUBE ASSY SHORT TMHP2 2 TMHP4 3 TMHP6 6 2F Z0747 2 VENTURI SHORT CASTING TMHP2 4 TMHP4 6 TMHP6 7 2P 1453 1 PLUG PIPE 1 8NPT SQ HD ALL 8 2J 602012 1 MANIFOLD ASSEMBLY TMHP2 2J 604002 TMHP4 2J 606002 TMHP6 9 2J Z0792 1 REGULATOR TMHP2 10 I8 TC0010 1 BASIC ASSY HOTPLATE 12 TMHP2 I8 TC0012 BASIC ASSY HOTPLATE 24 TMHP4 I8 TC0014 BASIC ASSY HOTPLATE 36 TMHP6 11 2A Z0314 4 FOOT 4 I...

Page 8: ... TMHP4 TMHP6 Gas Hotplates Fig No Part No Qty Description Application 17 2V Y8832 2 VALVE MANUAL GAS TMHP2 4 TMHP4 6 TMHP6 18 2A Z0790 1 FITTING STRAIGHT TMHP2 2 TMHP4 3 TMHP6 19 2V 6671 2 VALVE LINCOLN BRASS 3817 TMHP2 4 TMHP4 6 TMHP6 20 2V Z0869 1 TUBE 3 8 DIA TMHP2 2 TMHP4 3 TMHP6 21 2A Y3961 1 ORIFICE FITTING TMHP2 2 TMHP4 3 TMHP6 22 2A Y3297 2 4 6 ORIFICE 46 NAT ALL 2A Z1455 2 4 6 ORIFICE 54 ...

Page 9: ......

Page 10: ......

Page 11: ...9 ...

Page 12: ... suivez les instructions ci dessous 1 Réglez la pression de sortie du régulateur à 254 mm de colonne d eau 10 pouces Un tuyau de 1 8 de pouce sur le conduit peut être retiré pour y connecter une jauge de pression Retirez le couvercle rainuré du régulateur de pression et insérez y la prise Replacez le couvercle sur le régulateur et branchez sur le conduit Le régulateur est maintenant réglé à 254 mm...

Page 13: ...ion pour vérifier la pression Il est possible d accéder au conduit de distribution en retirant le panneau frontal ROBINET D ARRÊT MANUEL Un robinet d arrêt manuel devrait être installé en amont de l unité à environ 183 cm 6 pieds de l appareil Ce robinet n est pas fourni CONNEXION DE LA CANALISATION D ALIMENTATION DE GAZ L entrée de gaz pour cet appareil est scellée à l usine pour éviter que des s...

Page 14: ...REIL OU DE TOUT AUTRE APPAREIL TENIR TOUT COMBUSTIBLE HORS DU VOISINAGE DE L APPAREIL Cet appareil le régulateur de pression et le robinet d arrêt individuel doivent être déconnectés du système d alimentation de gaz pendant les essais de pression du système lorsque les pressions d essai sont supérieures à 0 5 PSIG Cet appareil et le régulateur de pression doivent être coupés de l alimentation de g...

Page 15: ...ues dans ce manuel sont susceptibles de changer sans préavis Quoique Toastmaster exerce la bonne foi de fournir le renseignement correct Toastmaster n est pas responsable pour les erreurs ou les omissions dans le renseignement pourvu ou les conclusions tirées à la suite de l utilisation des spécifications En utilisant le renseignement pourvu l utilisateur assume tous les risques en relation avec t...

Page 16: ...TMHP4 PLAQUES CHAUFFANTES AU GAZ Modèles TMHP2 TMHP4 TMHP6 Instructions d installation et d opération 2M Z12969 Rev Oct 1 2009 est une marque de Registerd Toastmaster la Compagnie A Middleby Tous droits réservés ...

Reviews: