9. SPECIFICATIONS
Standards
Certified to the European Standard EN 54-24:2008
Loudspeaker for voice alarm systems
for fire detection and fire alarm systems
Certification No. 0359-CPD-0109
Certified to the International Standard ISO 7240-24: 2010 Sound-system
loudspeakers for fire detection and fire alarm systems
In Compliance with the British Standard BS 5839-8: 2008 14.8
Environment Type
Type B (Outdoor applications)
Rated Noise Power
15 W (100 V line and 70 V line)
Rated Impedance
100 V line: 670
Ω
(15 W), 1 k
Ω
(10 W), 2 k
Ω
(5 W), 3.3 k
Ω
(3 W)
70 V line: 330
Ω
(15 W), 670
Ω
(7.5 W), 1 k
Ω
(5 W), 2 k
Ω
(2.5 W), 3.3 k
Ω
(1.5 W)
Sensitivity
109 dB (1 W, 1 m at 500 Hz to 2.5 kHz peak level)
100 dB (1 W, 1 m at 100 Hz to 10 kHz pink noise)
88 dB (1 W, 4 m at 100 Hz to 10 kHz pink noise)
Max.SPL
110 dB (15 W, 1 m at 100 Hz to 10 kHz pink noise)
98 dB (15 W, 4 m at 100 Hz to 10 kHz pink noise)
Frequency Response
315 Hz – 12.5 kHz
Coverage Angle (–6 dB) Horizontal: 360° (500 Hz), 160° (1 kHz), 85° (2 kHz), 45° (4 kHz)
Vertical:
360° (500 Hz), 200° (1 kHz), 115° (2 kHz), 60° (4 kHz)
Operating Temperature –20 ºC to +55 ºC (–4 ºF to +131 ºF)
Dust/Water Protection
IP65
Cable Gland
Size: PG 13.5
One cable gland is factory-installed.
For bridge connection, one cable gland can be added.*
Cable Connection
Screw terminal (Steatite)
Applicable Cable Size
Outer diameter:
ø8.0 – ø12.5 mm
Conductor:
Solid wire or 7-core wire
No bridge connection: 0.8 – 10 mm
2
(AWG18 – 7) for solid wire,
0.8 – 8 mm
2
(AWG18 – 8) for 7-core wire
Bridge connection:
0.8 – 2.5 mm
2
(AWG18 – 13) for solid wire,
0.8 – 1.5 mm
2
(AWG18 – 15) for 7-core wire
Finish
Horn flare:
Aluminum, off-white, powder coating
Reflector horn, Trans case, and Terminal cover:
ABS resin, off-white
Bracket, screws and bolts:
Stainless steel
Dimensions
172 (w) x 200 (h) x 229 (d) mm (6.77" x 7.87" x 9.02")
Weight
1.5 kg (3.31 lb)
Accessory
Terminal cover ..... 1
Option
Swivel bracket: YS-151S (Can be used instead of the supplied bracket.)
Notes
• The design and specifications are subject to change without notice for improvement.
• The specifications data was measured in an anechoic chamber, according to EN 54-24.
• Reference axis: Axis is on the center of horn-mouth and perpendicular to the horn-mouth.
• Reference plane: Plane is on the horn-mouth and perpendicular to the reference axis.
• Horizontal plane: Plane is containing the reference axis and perpendicular to the reference plane.
* Suppliable cable gland's part code and name: 525-52-011-70 Cable gland AVC PGB13.5-12 (GRY)
EN 54-24: 2008