16. HOW TO USE THE CONTROL/MONITOR TERMINALS

The Control/Monitor terminals on the rear panel permit power ON/OFF control of the individual channels and
monitoring for the power ON/OFF status and protection status on each channel, and fan operation status.
Prepare the control panel and status monitor display panel separately referring to the descriptions below.

Note

All terminals are electrically isolated from the unit body with the photocouplers.

16.1. Control Terminal (Input)

While the unit's power switch is turned ON, each individual channel's power can be turned ON and OFF from
the distant location using this terminal. The power indicator extinguishes only when the all channels' powers
are turned off, but otherwise remains lit.
Using the power supply, which you need to prepare separately, perform the control by applying DC voltage to
the control terminal.
This terminal is a photocoupler input, and requires max. 8 mA per control. Note the power capacity of the
power supply.

Control voltages are as follows.

16.2. Monitor Terminal (Output)

Indicators on the externally-connected device (status monitor display panel) or relays can be turned on and off
in response to the power ON/OFF status, protection status, and fan operation status from the distant location
using this terminal. 
This monitor terminal is a photocoupler open-collector output terminal. Note that it is rated at withstand
voltages of 30 V DC and control current of 12 mA or less when ON.
At the time of circuit design, consider the control current assuming that 1 V appears at the monitor terminal
when ON.

[Example of a circuit]

Control voltage (Vin)

Power ON/OFF status on each channel

0 – 3 V DC

ON

9 – 14 V DC

OFF

Control voltage (Vin)      R1 resistance value (rated power)

14 V to under 20 V DC

1 k

Ω

(0.1 W or more)

20 V to under 30 V DC

3.3 k

Ω

(0.25 W or more)

30 V to under 50 V DC

5.6 k

Ω

(0.5 W or more)

When controlling the control terminal with a power supply of 14 V DC or more, connect the specified
resistance referring to the table below.

Note:

The use of the resistance other than those specified may cause unit failure.

Note

Be sure to connect a diode across the relay in the direction
as shown above when connecting to the external relay.

Terminal pin No.

Pin 1 or 4

Vin

Pin 7

External DC power

(Max. 14 V DC)

Terminal pin No.

Pin 1 or 4

Pin 7

Vin

R1

External DC power

(Max. 50 V DC)

Terminal pin No.

When an LED is used

Pin 2, 3, 5, 6, or 8

Pin 7

Control current: 

12 mA or less

Control current: 

12 mA or less

External DC power

(Max. 30 V DC)

External DC power

(Max. 30 V DC)

Terminal pin No.

When a relay is used

Pin 2, 3, 5, 6, or 8

Pin 7

16

Summary of Contents for DA-500F-HL CU

Page 1: ...Switch Settings and Speaker Connections 10 9 REMOVABLE TERMINAL PLUG CONNECTION 12 10 INPUT SENSITIVITY SETTING 13 11 PROTECTION OPERATION LIST 13 12 TAMPER PROOF CAP ATTACHMENT 14 13 CLEANING THE FIL...

Page 2: ...torms or when unused for long periods of time Refer all servicing to qualified service personnel Servicing is required when the apparatus has been damaged in any way such as power supply cord or plug...

Page 3: ...se a fire or electric shock Do not insert nor drop metallic objects or flammable materials in the ventilation slots of the unit s cover as this may result in fire or electric shock Do not touch a plug...

Page 4: ...erwise may cause a fire or electric shock 3 GENERAL DESCRIPTION TOA s DA 550F Multichannel Power Amplifier features high power handling of 550 W x 4 channels 4 output or 350 W x 4 channels 8 output an...

Page 5: ...the unit s power then wipe with a dry cloth When the unit gets very dirty use a cloth damped in a neutral cleanser Never use benzene thinner alcohol or chemically treated cleaning cloth because such v...

Page 6: ...s about 20 dB Output indicator OUTPUT Lights yellow when an output level exceeds about 1 W at an 8 load DA 550F or 9 8 load DA 500F HL Peak indicator PEAK Lights red when an output signal clips distor...

Page 7: ...ng XLR type connector Removable terminal block 3 pins H Hot C Cold E Earth XLR type male connector XLR 3 31 equivalent Pin 1 Earth Pin 2 Hot Pin 3 Cold If a straight plug hits the rack s rear cover or...

Page 8: ...rminal is not for protective ground 13 HPF ON OFF switch DA 500F HL only Input signals to CH1 CH4 can be filtered through the High pass filters having 6 dB attenuation at a cut off frequency of 50 Hz...

Page 9: ...e unit s terminal cover after connection completion Because high voltage is generated at the speaker output terminals never touch these terminals to avoid electric shock DA 500F HL only WARNING Input...

Page 10: ...ts 2 outputs DA 550F 16 19 6 16 19 6 DA 500F HL CH4 CH3 CH2 CH1 Speaker output terminals Switch BRIDGE 1 BRIDGE 2 CH 1 mode OFF OFF ON Setting 4 8 4 8 4 8 4 8 CH1 CH1 CH2 CH3 CH4 1 input 4 outputs DA...

Page 11: ...ting 8 4 8 4 8 CH3 CH4 CH1 CH3 CH4 CH1 CH2 BRIDGE 1 3 inputs 3 outputs 2 DA 550F 16 19 6 4 9 8 4 9 8 DA 500F HL CH3 CH4 Speaker output terminals Switch BRIDGE 1 BRIDGE 2 CH 1 mode ON OFF ON Setting 8...

Page 12: ...Terminal screw Slotted screwdriver Shielded cable Removable terminal plug Hot Cold Earth 1 1 2 Bit shape 3 mm 0 12 9 REMOVABLE TERMINAL PLUG CONNECTION Cautions Be sure to use shielded cables for audi...

Page 13: ...ts Contact the TOA dealer where the unit was purchased 10 INPUT SENSITIVITY SETTING The input sensitivity for each channel can be set to either 4 dB factory preset or 10 dB These servicing instruction...

Page 14: ...anel Detach the panel by pressing on the right side Filter Ventilation Panel Ventilation Panel 2 3 14 DIMENSIONAL DIAGRAM 465 18 31 442 17 4 76 2 3 88 4 3 48 482 18 98 371 14 61 22 5 0 89 404 2 15 91...

Page 15: ...H 3 INPUT E H C CH 4 INPUT E 15 2 DA 500F HL H C CH 1 INPUT E H C E H C CH 3 INPUT E H C CH 4 INPUT E CH 2 INPUT HPF 50 Hz CH 1 HPF ON OFF switch CH 2 HPF ON OFF switch CH 3 HPF ON OFF switch CH 4 HPF...

Page 16: ...us protection status and fan operation status from the distant location using this terminal This monitor terminal is a photocoupler open collector output terminal Note that it is rated at withstand vo...

Page 17: ...dicator front panel Light off Light on Protection status output OFF ON Terminal Pin No Pin name Unit operation status HI LEVEL LO LEVEL CH1 2 CH1 power ON OFF control input CH1 power OFF CH1 power ON...

Page 18: ...or LAN CAT5 UTP RJ45 pin No To Control Monitor terminal 1 2 5 6 3 4 7 8 RJ45 pin No Cable color Cable color for T568B for T568A Orange white Green white Orange Green Green white Orange white Blue Blue...

Page 19: ...trol input Power ON OFF status of the individual channels Photocoupler input drive voltage 9 V DC Min 14 V Max 12 V Typ Monitor output Power ON OFF status of the individual channels Protection status...

Page 20: ...voltage output and heat sink temperature rise over 100 C 100 dB A weighted 70 dB A weighted Control input Power ON OFF status of the individual channels Photocoupler input drive voltage 9 V DC Min 14...

Reviews: