Toa DA-250F CU Operating Instructions Manual Download Page 4

4

When Installing the Unit

• Do not expose the unit to rain or an environment

where it may be splashed by water or other liquids,
as doing so may result in fire or electric shock. 

• Use the unit only with the voltage specified on the

unit. Using a voltage higher than that which is
specified may result in fire or electric shock.

• Do not cut, kink, otherwise damage nor modify the

power supply cord. In addition, avoid using the
power cord in close proximity to heaters, and never
place heavy objects -- including the unit itself -- on
the power cord, as doing so may result in fire or
electric shock. 

• Be sure to replace the unit's terminal cover after

connection completion. Because the voltage of up
to 140 V is applied to the high impedance speaker
terminals, never touch these terminals to avoid
electric shock.

• External wiring connected to the terminals marked

with 

requires installation by an instructed person.

• The apparatus shall be connected to a mains

socket outlet with a protective earthing connection.

When the Unit is in Use 

• Should the following irregularity be found during

use, immediately switch off the power, disconnect
the power supply plug from the AC outlet and
contact your nearest TOA dealer. Make no further
attempt to operate the unit in this condition as this
may cause fire or electric shock. 

· If you detect smoke or a strange smell coming

from the unit.

· If water or any metallic object gets into the unit 
· If the unit falls, or the unit case breaks 
· If the power supply cord is damaged (exposure of

the core, disconnection, etc.)

· If it is malfunctioning (no tone sounds.)

• To prevent a fire or electric shock, never open nor

remove the unit case as there are high voltage
components inside the unit. Refer all servicing such
as modification inside the unit to qualified service
personnel.

• Do not place cups, bowls, or other containers of

liquid or metallic objects on top of the unit. If they
accidentally spill into the unit, this may cause a fire
or electric shock. 

• Do not insert nor drop metallic objects or

flammable materials in the ventilation slots of the
unit's cover, as this may result in fire or electric
shock. 

• Do not touch a plug during thunder and lightning,

as this may result in electric shock. 

When Installing the Unit

• Never plug in nor remove the power supply plug

with wet hands, as doing so may cause electric
shock.

• When unplugging the power supply cord, be sure

to grasp the power supply plug; never pull on the
cord itself. Operating the unit with a damaged
power supply cord may cause a fire or electric

2. SAFETY PRECAUTIONS

• Before installation or use, be sure to carefully read all the instructions in this section for correct and safe

operation.

• Be sure to follow all the precautionary instructions in this section, which contain important warnings and/or

cautions regarding safety.

• After reading, keep this manual handy for future reference.

Safety Symbol and Message Conventions 

Safety symbols and messages described below are used in this manual to prevent bodily injury and property
damage which could result from mishandling. Before operating your product, read this manual first and
understand the safety symbols and messages so you are thoroughly aware of the potential safety hazards. 

WARNING

Indicates a potentially hazardous situation which, if mishandled, could
result in death or serious personal injury.

Indicates a potentially hazardous situation which, if mishandled, could
result in moderate or minor personal injury, and/or property damage.

WARNING

CAUTION

CAUTION

Summary of Contents for DA-250F CU

Page 1: ...WER AMPLIFIERS DA 250F CU DA 250FH CU Thank you for purchasing TOA s Multichannel Power Amplifier Please carefully follow the instructions in this manual to ensure long trouble free use of your equipm...

Page 2: ...ont 8 Rear 9 8 CONNECTIONS 8 1 Procedure 10 8 2 Button Settings and Speaker Connections 10 9 REMOVABLE TERMINAL PLUG CONNECTION 12 10 INPUT SENSITIVITY AND HIGH PASS FILTER ON OFF SETTINGS 13 11 PROTE...

Page 3: ...torms or when unused for long periods of time Refer all servicing to qualified service personnel Servicing is required when the apparatus has been damaged in any way such as power supply cord or plug...

Page 4: ...as there are high voltage components inside the unit Refer all servicing such as modification inside the unit to qualified service personnel Do not place cups bowls or other containers of liquid or me...

Page 5: ...AC outlet use the AC outlet with current capacity allowable to the unit When the Unit is in Use Make sure that all volume controls are set to minimum position before power is switched on Loud noise p...

Page 6: ...ase Input output status LED indicators for each channel Built in protection circuitry disconnects the output when a short circuit overload or unusual temperature rise occurs 1U size 44 5 mm reference...

Page 7: ...Perforated Panel larger than 1U in size 1 at the top and the bottom of the rack and 2 above and below every 5 units Perforated panel Power amplifiers DA 250F 250FH Power amplifiers DA 250F 250FH Robu...

Page 8: ...and 4 In this event the CH 4 volume control cannot be used 4 Ventilation panel Air Vent A filter is located inside the ventilation panel To clean the filter remove the ventilation panel See p 15 Clea...

Page 9: ...wiring See p 10 The unit s input mode changes as follows depending on the BRIDGE ON OFF button setting 4 channel input mode Set both BRIDGE 1 and 2 buttons to OFF 3 channel input mode Set either BRID...

Page 10: ...terminal cover in place BRIDGE 1 ON OFF button BRIDGE 2 ON OFF button CH 1 mode ON OFF button CH4 CH3 CH2 CH1 Speaker output terminals Button BRIDGE 1 BRIDGE 2 CH 1 mode OFF OFF OFF Setting 4 8 4 8 4...

Page 11: ...Setting CH3 CH4 3 inputs 3 outputs 2 CH3 CH4 CH1 CH3 CH4 CH1 CH2 Speaker output terminals 8 16 4 8 4 8 39 2 19 6 19 6 DA 250F DA 250FH BRIDGE 1 Button BRIDGE 1 BRIDGE 2 CH 1 mode ON OFF OFF Setting C...

Page 12: ...old Earth Bit shape 3 mm 9 REMOVABLE TERMINAL PLUG CONNECTION Cautions Be sure to use shielded cables for audio signal lines Avoid soldering cable conductor as contact resistance may increase when the...

Page 13: ...socket position to 4 dB or 10 dB for the Input sensitivity and to ON or OFF for the High pass filter DA 250FH only as illustrated below DA 250F 250FH Viewed from top with the top cover detached Front...

Page 14: ...mperature over 110 C Load disconnected Protection indicator lights Temperature rise inside the unit over 80 C Built in amplifier unit that caused the failure halted Four indicators of the correspondin...

Page 15: ...move the ventilation panel as shown in the figure Step 3 Detach the filter inside the ventilation panel Step 4 Clear the filter of dust Step 5 Replace the filter and ventilation panel Detach the panel...

Page 16: ...E 1 OUTPUT Current Limitter Short Detector Protection Circuit OUTPUT 2 relay CH 1 to all switch Current Limitter Short Detector Protection Circuit OUTPUT 3 relay CH 3 OUTPUT CH 4 OUTPUT 4 dB 10 dB CH...

Page 17: ...10 dB CH 2 volume control ON OFF BRIDGE 1 ON OFF switch BRIDGE 1 OUTPUT Current Limitter Short Detector Protection Circuit OUTPUT 2 relay CH 1 to all switch Current Limitter Short Detector Protection...

Page 18: ...18 15 DIMENSIONAL DIAGRAM Unit mm 482 465 400 374 20 31 8 44...

Page 19: ...0 3 20 Hz 20 kHz 0 3 100 Hz 20 kHz HPF ON 0 3 20 Hz 20 kHz HPF OFF 4 dB 1 23 V 10 dB 0 24 V selectable with the inner jumper 10 k electronically balanced 100 dB Input CH 1 4 Removable terminal block O...

Page 20: ...Printed in Japan 133 22 027 00...

Reviews: