172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
42
3.7 Parameter Setting Mode [F]
3.7.1 Parameter group No. 00: Setting (
SV
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Pn00
Parameter group No. 00
This is the first parameter symbol of
Parameter group No. 00.
24
1. SV
Input 1_Set value (SV)
★
Input 1_Setting limiter low to Input 1_
Setting limiter high
[Varies with the setting of the Decimal
point position.]
0
25
2. SV
Input 2_Set value (SV)
1)
★
Input 2_Setting limiter low to Input 2_
Setting limiter high
[Varies with the setting of the Decimal
point position.]
0
26
dSV
Set value (SV) of
differential temperature
input
2)
★
-(Input 1_Input span) to +(Input 1_Input
span)
[Varies with the setting of the Decimal
point position.]
0
★
Data included in Memory area
1)
Displayed when "2-loop control/Differential temperature control" or "Cascade control" is selected in "Select function for Input 2."
2)
Displayed when "2-loop control/Differential temperature control" is selected in "Select function for Input 2" AND "Differential
temperature control" is selected in "two-loop control/Differential temperature control."
3.7.2 Parameter group No. 40: Event (
EV
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Pn40
Parameter group No. 40
1)
This is the first parameter symbol of
Parameter group No. 40.
27
EV1
Event 1 set value (EV1)
2)
Event 1 set value (EV1)
[high]
2) 3)
★
Deviation:
When assigned to Input_1 or
Differential temperature input
(Input 1_Input span) to
(Input 1_
Input span)
When assigned to Input 2
(Input 2_Input span) to
(Input 2_
Input span)
When Control with PV select is
selected at Select function for input 2.
-(PV select input span) to +(PV select
input span)
[Varies with the setting of the Decimal
point position.]
Input value or Set value:
When assigned to Input 1
Input 1_Input range low to Input 1_
Input range high
When assigned to Input 2
Input 2_Input range low to Input 2_
Input range high
When assigned to Differential
temperature input
(Input 1_Input span) to
(Input 1_
Input span)
When Control with PV select is
selected at Select function for input 2.
PV select input range low to PV select
input range high
[Varies with the setting of the Decimal
point position.]
Manipulated output value:
-5.0 to +105.0%
High
action,
high/low
action:
max.
Low action,
process
action: min.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...