172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
153
6.3 Using Retransmission Output
Retransmission output can be provided from OUT1 to 3. To use the Retransmission
output, the output type must be current.
Description of function
To use the Retransmission output, select Retransmission output at OUT1 to 3
function selection. If Retransmission output is selected at the OUT1 function selection,
the output is provided as Retransmission output 1. If Retransmission output is selected at
the OUT2 function selection, the output is provided as Retransmission output 2. If
Retransmission output is selected at the OUT3 function selection, the output is provided
as Retransmission output 3.
Refer to 6.1 Changing Output Assignment [Control Output, Retransmission
Output, Logic Calculation (Event) Output, Instrument Status Output] for OUT1
to 3 function selection..
Details of Retransmission output type
Setting
Assigned functions
0
No retransmission output
1
Input 1_Measured value (PV)
Input 1_Measured value (PV) is output.
2
Input 1_Local SV
Input 1_Set value (SV) is output. The local SV is the SV set. If the set value is changed,
irrespective of the Soft start/Setting change rate limiter whether or not it is set, the new set
value will be used as soon as the value is changed.
3
Input 1_SV monitor value
Input 1_Set value (SV) is output. The SV monitor value is the monitored value of the set
value (SV). If a Soft start/Setting change rate limiter is set, the set value starts changing
according to the setting when the setting is changed.
4
Input 1_Deviation
[Input 1_Measured value (PV)
Input 1_Set value (SV)] is output.
5
Input 1_Manipulated output value [heat-side]
Input 1_Manipulated output value [heat-side] is output.
6
Input 1_Manipulated output value [cool-side]
Input 1_Manipulated output value [cool-side] is output.
7
Input 2_Measured value (PV)
Input 2_Measured value (PV) is output.
8
Input 2_Local SV
Input 2_Set value (SV) is output. The local SV is the SV set. If the set value is changed,
irrespective of the Soft start/Setting change rate limiter whether or not it is set, the new set
value will be used as soon as the value is changed.
9
Input 2_SV monitor value
Input 2_Set value (SV) is output. The SV monitor value is the monitored value of the set
value (SV). If a Soft start/Setting change rate limiter is set, the set value starts changing
according to the setting when the setting is changed.
10
Input 2_Deviation
[Input 2_Measured value (PV)
Input 2_Set value (SV)] is output.
11
Input 2_Manipulated output value
Input 2_Manipulated output value is output.
12
Remote setting input value
1)
Remote setting input value is output.
13
Measured value (PV) of differential temperature input
Measured value (PV) of Differential temperature input [Input 1_Measured value (PV) -
Input 2_Measured value (PV)] is output.
1)
Available
when “Remote setting input” is selected in Select function for Input 2.
The output will be 0% when the Retransmission output type not provided on the
instrument is set.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...