172-65318MA-04 (GP10/GT10/GP14/GT14 PowerTrap) 23 Nov 2018
8
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg (44 lb) or more). Failure to do so may result in back strain or other
injury if the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Do not use excessive force when connecting threaded pipes to the
product. Over-tightening may cause breakage leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Use only under conditions in which no water hammer will occur. The
impact of water hammer may damage the product, leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Open System Piping (Steam System Example)
Ci
Vo
Condensate
Recovery Line
Primary
Pressure
for Motive
Medium
Motive
Medium
Supply
Pressure
Pm
Pump
Exhaust
Km
Co
Condensate
Receiver
Dh
Vm
Ve
Vi
Back
Pressure
Pb
F
las
h
S
team
Temperature
Controller
Vent Pipe
Other Steam-using
Equipment
M
a
x
. H
ei
ght
:
3 m
(
10 f
t)
Sm
Se
Si
So
Sr
Equipment
Pressure
Steam for
Heating
Condensate
Amount
Q
Ki
Rm
St
Sv
TLV
Power
Trap
Steam Trap
B
ac
k
fl
ow
W
a
ter
H
a
m
m
er
P
rev
ent
ion C
hec
k
V
al
v
e
Vb
Backflow
Water Hammer
Prevention
Check Valve
Sf
O
v
er
fl
ow
C
onde
ns
at
e
If water hammer due to steam backflow in the condensate
recovery line is expected, installation of a check valve vertically
and as close as possible to the recovery line is recommended
When the rise in piping is 30 m (100 ft) or farther from the
PowerTrap
, installation of a check valve is recommended for
the prevention of return water hammer
F
ill
ing
H
ead
A
Steam Trap
Steam
Trap
Steam-using
Equipment
Pipe the discharge to a safe area such as a pit
NOTE: This sketch is for explanation purposes only and is not intended as an installation design.
Necessity of installing a condensate receiver
It is necessary for storing condensate during pumping.
Condensate cannot enter the PowerTrap while condensate is being pumped.
Q
Condensate Amount
Se Exhaust Pipe
Rm Motive Medium Pressure
A
Filling Head
Sv Vent Pipe
Reducing Valve
Pm Motive Medium Supply Pressure
Sf
Overflow Pipe
St
Steam Trap on Drip leg
Pb Back Pressure
Dh Condensate Receiver
Vi
Valve on Condensate Inlet Pipe
Si
Condensate Inlet Pipe
Ci
Condensate Inlet Check Valve
Vo
Valve on Condensate Outlet Pipe
So Condensate Outlet Pipe
Co Condensate Outlet Check Valve
Vm Valve on Motive Medium Supply Pipe
Sr
Condensate Recovery Line
Ki
Condensate Inlet Strainer
Ve
Valve on Exhaust Pipe
Sm Motive Medium Supply Pipe
Km Motive Medium Strainer
Vb
Blowdown Valve