TLC TAC-07CHSA/XA31 Service Manual Download Page 12

 Air Conditioner Service Manual

 

 

1

 

 

 
 
 

4)  Under emergency operation, the function of compressor’s time-delay protection, Anti-frosting 
protection in cooling mode,  Overheating protection in heating mode, sensor fault  protection and  
defrost operate are effective. 
5)  Under emergency operation, once effective signal from remote controller received, the A/C 
exits form of emergency mode without delay, and operates according to the setting value from remote 
controller immediately. 

9. Auto -restart function

 

1)  The PCB retains the setting parameters in case of power off. When the power supply is resumed, 
the machine, which has been started up the power-off memory function, is able to restore into the 
original running state automatically. 
To press the emergency button and power on the unit, and hold on for10 seconds, The buzzer 
2) will 

ring 

three times

, after this operation, the auto restart function activated. 

3)  To close auto restart function while it is activated, repeat process as above 2), the buzzer will ring 
four times.  

10.  Protection / Failure code

 

10.1 Protection 

1) Compre ssor’s protection: 

a. The PCB which with Auto-restart function, once it is activated, the compressor goes along 3min 
delay protection when power on, otherwise the compressor without this protection even when the PCB 
is power-on.   
b . The compressor’s 3 min interval protection: the compressor can’t start-up until it stops 3 min later. 
(

except for the defrosting process

). 

c. 

After the compressor started, it’s operation state remains the same within 3 min even when ST, RT 

variation. 

2) Anti-fro sting protection of indoor evaporator (Cooling mode): 

If IPT

0°C detected in consecutive 3 min, compressor and outdoor fan motor to be stopped operation, 

indoor fan motor runs at high-speed forcibly; if IPT

5°C detected 3min later, then outdoor fan motor 

and compressor will start up, and indoor fan motor restores to it’s original state. 

3)  Overheating protection (Heating mode): 

If IPT

55°C, the outdoor fan motor: OFF. 

If IPT

65°C, the compressor: OFF, and indoor fan motor runs at  high-speed forcibly.  

When IPT

48°C, the outdoor fan motor and the compressor start up, indoor fan motor restores to it’s 

original state. 

4)  Cold air prevention (Heating mode): 

This function is intend to prevent cold air from being discharged when the heating operation starts or 
when defrosting. 
a.  When running into the heating mode, once the compressor fails to comply with the start-up 
conditions, the fan speed is regulated according to the coil temperature within 2 min, 2 min later the 
indoor fan motor stops. If the compressor starts up within 2 min,  then operating according to Figure 5. 
Under heating process, while the compressor stop (including stopping for protection), the fan motor’s 
operation (including stopping the indoor fan motor) is regulated according to the coil temperature 
within 1min,  1min later  the fan will be stopped forcibly. 
 

Summary of Contents for TAC-07CHSA/XA31

Page 1: ...9CHSA XA31 TAC 12CHSA XA31 TAC 18CHSA XA31 TAC 24CHSA XA31 CONTENTS 1 IMPORTANT NOTICE 2 TECHNICAL SPECIFICATION 3 PRODUCT DIMENSIONS 4 REFRIGERATION CYCLE DIAGRAM 5 OPERATION DETAILS 6 WIRING DIAGRAM...

Page 2: ...for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameters are subject to change due to technical modification...

Page 3: ...gerant Charge Gram R410A 430g R410A 510g R410A 640g R410A 930g R410A 1300g Compressor Model ASN89V11UDZ1 ASN89V11UDZ1 PA140G1C 4DZ1 50A403VL 51KG ASH232MV C7EU1 MFG GMCC GMCC GMCC RECHI HIGHLY Type Ro...

Page 4: ...D E F G H I J K TAC 07CHSA XA31 698 255 190 600 500 232 357 276 256 52 55 TAC 09CHSA XA31 698 255 190 600 500 232 357 276 256 52 55 TAC 12CHSA XA31 777 250 205 700 550 256 439 2 302 277 8 48 55 TAC 1...

Page 5: ...Compressor Accumulator Heat exchange condenser Heat exchange Evaporator 2 way valve Liquid side 3 way valve Gas side Cooling Heating Gas side 3 way valve Liquid side 2 way valve Heat exchange Evapora...

Page 6: ...seconds the remote controller is preset as Heat Pump automatically LOCK UNLOCK Note If the air conditioner you purchased is a Cooling Only one but you preset the remote controller as Heat Pump it doe...

Page 7: ...le to retain and restore the original mode when being turned on or the power supply is resumed if the auto restart function activated power off after power on while if the auto restart function isn t...

Page 8: ...T CRT 1 C the compressor is running b When ST CRT 1 C the compressor stops c When 1 C ST CRT 1 C the compressor keeps its original state 2 Outdoor fan motor and the compressor run simultaneously excep...

Page 9: ...Off Tim be in accord ing during d ing optiona m run into de 3 d c all require ax IPT 0min the co tion 1 the fir me should b is more than erature is le e set is 8 mi or is operatin on wind tem mpresso...

Page 10: ...machine runs into defrosting and last for 8 min if the accumulative totally less than 30min but accord with one of the condition option 1 3 then the machine runs into defrosting at the option 1 3 and...

Page 11: ...n no changed anymore 3 The machine will automatically shut up after running 10 hours under sleep mode When Timer ON and Sleep mode are implemented at the same time the Sleep mode can not be functioned...

Page 12: ...tion the compressor can t start up until it stops 3 min later except for the defrosting process c After the compressor started it s operation state remains the same within 3 min even when ST RT variat...

Page 13: ...are several failure codes reported at the same time then failure codes appears by turns every eight seconds correspondingly 6a Sensor s failure protection when the sensor tested temperature out of the...

Page 14: ...Air Conditioner Service Manual 1 6 WIRING DIAGRAM MODEL TAC 07CHSA XA31 TAC 09CHSA XA31 TAC 12CHSA XA31 INDOOR UNIT OUTDOOR UNIT TAC 18CHSA XA31 TAC 24CHSA XA31...

Page 15: ...rd 1 16 210738393 Electrical Box Cover 1 17 210736832 Cable Clamp 1 18 210900376 Terminal 1 19 210901224 Transformer 1 20 210901617DQ Main PCB 1 21 210736831 Electrical Box 1 22 210900333 Indoor Senso...

Page 16: ...1 1120110016 4 way Valve 1 12 211244085 4 way Valve Assembly 1 13 210826872 Base 1 14 1081990012 Right Plate 1 15 211236491 Two way Valve 1 16 1081990013 Valve Supporter 1 17 1120130039 Three way Valv...

Page 17: ...8393 Electrical Box Cover 1 17 210736832 Cable Clamp 1 18 210900376 Terminal 1 19 210901224 Transformer 1 20 210901617DQ Main PCB 1 21 210736831 Electrical Box 1 22 210900333 Indoor Sensor Assembly 1...

Page 18: ...1 1120110016 4 way Valve 1 12 211244085 4 way Valve Assembly 1 13 210826872 Base 1 14 1081990012 Right Plate 1 15 211236491 Two way Valve 1 16 1081990013 Valve Supporter 1 17 1120130039 Three way Valv...

Page 19: ...15 210900478A Terminal 1 16 210736832 Cable Clamp 1 17 210901224 Transformer 1 18 210901617DY Main PCB 1 19 210736831 Electrical Box 1 20 210900333 Indoor Sensor Assembly 1 21 1170030067G Indoor Moto...

Page 20: ...1120110016 4 way Valve 1 12 211243953 4 way Valve Assembly 1 13 210838068 Base 1 14 210838045 Right Plate 1 15 211242714A Two way Valve 1 16 210836832 Valve Supporter 1 17 211242715A Three way Valve...

Page 21: ...Supply Cord 1 16 210738393 Electrical Box Cover 1 17 210736832 Cable Clamp 1 18 210900376 Terminal 1 19 210901224 Transformer 1 20 210901617T Main PCB 1 21 210900333 Indoor Sensor Assembly 1 22 210736...

Page 22: ...226 4 way Valve 1 12 211238305 4 way Valve Assembly 1 13 210800487 Base 1 14 1080050002 Right Plate 1 15 1120120021 Two way Valve 1 16 1080050003 Valve Supporter 1 17 1120130085 Three way Valve 1 18 1...

Page 23: ...Supply Cord 1 16 210738393 Electrical Box Cover 1 17 210736832 Cable Clamp 1 18 210900376 Terminal 1 19 210901224 Transformer 1 20 210901617AJ Main PCB 1 21 210900333 Indoor Sensor Assembly 1 22 2107...

Page 24: ...017 4 way Valve 1 12 211238193 4 way Valve Assembly 1 13 210800568 Base 1 14 1081990054 Right Plate 1 15 1120120021 Two way Valve 1 16 1081990055 Valve Supporter 1 17 1120130037 Three way Valve 1 18 1...

Page 25: ...ordance with the wiring rules z The air conditioner must be installed by professional or qualified persons Do not install the appliance at a distance of less than 50 cm from inflammable substances alc...

Page 26: ...res z The user is responsible for having the appliance installed by a qualified technician who must check that it is earthed in accordance with current legislation and insert a thermomagnetic circuit...

Page 27: ...Air filter 3 Special filter option 4 Display PCB 5 Vertical vane 6 Horizontal vane 7 Remote controller 9 Names of parts Outdoor unit No Name 8 Air outlet grille 9 Electronic box cover 10 2 way valve...

Page 28: ...g m A 5m TAC 07CHSA XA31 3 0 15 20g m TAC 09CHSA XA31 3 0 15 20g m TAC 12CHSA XA31 3 5 15 30g m TAC 18CHSA XA31 5 0 15 30g m TAC 24CHSA XA31 5 0 15 30g m Connecting cables The power cord should be sel...

Page 29: ...OOR UNIT Do not install the outdoor unit near sources of heat steam or flammable gas Do not install the unit in too windy or dusty places Do not install the unit where people often pass Select a place...

Page 30: ...the hole in the wall for the piping if necessary according to the position of the mounting plate 2 Install a flexible flange through the hole in the wall to keep the latter intact and clean The hole...

Page 31: ...pipe is bent or pulled too often it will become stiff Do not bend the pipe more than three times at one point z When extending the rolled pipe straighten the pipe by unwinding it gently as shown in th...

Page 32: ...htening procedures described for the indoor unit Note If the tightening torque is not sufficient there will probably be some leakage With excessive tightening torque there will also be some leakage as...

Page 33: ...t does not operate at all Power supply voltage check Connector contact check Power trans output voltage PCB assembly check Power receptable voltage Product input voltage PCB assembly Power input volta...

Page 34: ...l check Operation mode check PCB ass y check Check Motor driving circuit Relay output Check Motor output connector Motor capacitor Check Motor bearing inserted state Fan Blower fixed state Fan Blower...

Page 35: ...eon short of system and display E4 11 5 System protection E5 High low pressure protection model Start unit Check the pressure of system Check the resistance of pipe sensor Check the main PCB Check lea...

Page 36: ...rature sensor open short check Thermistor and evaporator surface contact check Clearance is needed 5mm Connector check Contact power Connector check Contact power Disconnection short circuit check of...

Page 37: ...short circuit mal connection Vane motor check PCB assembly check vane motor driving circuit Replace the vane motor Replace the PCB Heating operation ON by remote controller Connector check If the 4 wa...

Page 38: ...2 Room temperature sensor IRT and Indoor pipe coil temperature sensor IPT damage short or broken Solution check the resistance of the sensor R 25 5 k if short or broken please replace it 3 The PCB fai...

Page 39: ...Air Conditioner Service Manual 2 The indoor motor damage Solution Check and replace the motor 3 The indoor main PCB damage Solution Replace the indoor main PCB...

Page 40: ...3 981 2 192 76 0 895 0 746 13 26 239 4 186 32 3 836 2 146 77 0 869 0 728 12 24 984 4 152 33 3 697 2 101 78 0 843 0 710 11 23 795 4 117 34 3 563 2 057 79 0 819 0 692 10 22 671 4 082 35 3 435 2 012 80 0...

Page 41: ...sistance at 25 5 k TH1 indoor room temperature sensor and outside air temperature sensor TH2 indoor exchange temperature sensor and outside exchange temperature sensor Before measuring resistance disc...

Reviews: