MODEL HS-3C WIRING WITH SINGLE APPLIANCE

The HS-3C Power Venter is equipped with 2 relays. One is used to activate the Power Venter while the other is used to isolate the
Fan Proving Switch from the load of the appliance. The relays and Fan Proving Switch are factory wired for easy installation. The
installer needs to complete 3 steps to wire the Power Venter as noted below:

1. Route the metal conduit from the electrical box to the Power Venter motor and connect the Black, White and Ground wires to the 

motor.

2. Connect the Red, Blue and Orange wires in the electrical box to the appliance.

3. Supply 115 VAC to the input wires in the electrical box.

NOTE:

The HS-3C as viewed from the opposite end of the shaft should rotate clockwise. 

O

LADDER DIAGRAM OF HS-3C

FACTORY WIRING OF HS-3C ELECTRICAL BOX

Summary of Contents for HS-3C CANADIAN 8504002 REV 2 0997

Page 1: ... THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE R...

Page 2: ...ction should occur SPECIFICATIONS CAPACITY The installer must verify that the Power Venter is sized properly using the capacity table to the right The installer may reduce the vent pipe diameter to the size shown in the selection table immediately after the draft hood draft diverter or barometric draft control The vent pipe length shown includes all equivalent vent pipe before and after the Power ...

Page 3: ...diverter or barometric draft control 5 The Power Venter shall not be installed where the flue gas temperature exceeds 285oC 550o F at the Power Venter inlet Flue gas temperature verification A Consult appliance manufacturer for flue gas temperature after dilution by the draft hood draft diverter or barometric draft control B Measure flue gas temperature at the Power Venter inlet after installation...

Page 4: ... A venting system shall not direct flue gases towards brickwork siding or other construction in such a manner that may cause damage from heat or condensate from the flue gases A vent system shall not direct flue gases so as to jeopardize people overheat combustible structures or enter buildings A venting system shall not terminate within 1 8 m 6ft of the following A window door or mechanical air s...

Page 5: ...appropri ate type of vent pipe to the inlet of the Power Venter The vent pipe chosen must be in compliance with local codes The Power Venter inlet and outlet are designed to accept single wall vent pipe If using vent pipe other than single wall the installer must supply adapters to connect to the Power Venter While it is recommended that the Power Venter be mounted at the point of termination it i...

Page 6: ...at is on the exterior of the housing DO NOT trim the sensing tube portion that will be mounted in the interior of the housing No attempts should be made to substitute the specified materials See Fan Proving Switch installation diagram WIRING All wiring from the Power Venter to the appliance must be in compliance with the local codes or in their absence The Canadian Electrical Code CSA Std C22 1 Al...

Page 7: ...he installer needs to complete 3 steps to wire the Power Venter as noted below 1 Route the metal conduit from the electrical box to the Power Venter motor and connect the Black White and Ground wires to the motor 2 Connect the Red Blue and Orange wires in the electrical box to the appliance 3 Supply 115 VAC to the input wires in the electrical box NOTE The HS 3C as viewed from the opposite end of ...

Page 8: ...HS 3C Power Venter is interlocked to 24V controlled appliances Variations of these diagrams are acceptable as long as the Fan Proving Switch isolation circuit is wired to disable the gas valve if a venting mal function should occur 7 HS 3C CONNECTED TO APPLIANCE WITH SPARK IGNITION HS 3C CONNECTED TO A BOILER ...

Page 9: ...ometric draft control and the appliance flue outlet 2 Make necessary draft adjustments with the barometric draft control appliance burner air intake and the damper located on the outlet of the Power Venter until the appliance manufacturer s recommended draft is present SAFETY INTERLOCK TEST 1 Adjust the appliance thermostat s or aquastat s to call for heat 2 Determine that the Power Venter operate...

Page 10: ...Housing WHAT IS NOT COVERED Product installed contrary to our installation instructions Product that has been altered neglected or misused Product that has been wired incorrectly Product that has been damaged by a malfunctioning or mistuned burner Any freight charges related to the return of the defective part Any labor charges related to evaluating and replacing the defective part REPLACEMENT PAR...

Reviews: