TJERNLUND PRODUCTS, INC.

1601 Ninth Street  White Bear Lake, MN 55110-6794     
Phone: 651.426.2993    800.255.4208    Fax: 651.426.9547
Visit our web site: www.tjernlund.com  

Copyright © 2003 Tjernlund Products, Inc.          P/N 8500590 Rev B 4/03

1. Inputs shown are
believed to be maximum
capacities for inducers
when mounted on pipe
sizes shown for ordinary
jobs where a moderate
amount of mechanical
induced draft is required.

2. Consideration is given 
to typically higher static
pressure requirements for
larger installations, for the
type of fuel burned and
for the type of draft 
control installed.

3. Some ratings may only
be valid for extremely
short vent lengths due to
excessive pressure loss; i.e.
the Model IL gas firing
with draft hood in 10"
pipe at 2,080,000 BTU/hr.

4. Where pressure require-
ments are unknown or
believed to be unusually
severe, ask for complete
performance curves or 
consult factory.

5. Draft Inducers should 
be installed in single wall
vent pipe in order to assure
proper performance.

Model Selection Table and Electrical Data

Model

DJ-3

D-3

I

IL

XL

HD

Pipe

Size

In.

3

4

5

6

5

6

7

8

8

9

10

12

9

10

12

14

16

18

16

18

20

24

20

24

69,000

105,000

111,000

100,000

270,000

356,000

360,000

320,000

900,000

1,110,000

1,250,000

1,030,000

1,460,000

2,080,000

1,920,000

1,840,000

900,000

650,000

4,000,000

3,900,000

2,800,000

1,500,000

5,300,000

3,500,000

Gas Firing

with Draft

Hood

270

0

F

Flue Gas

S.P.

.034

.042

.043

.041

.063

.073

.075

.068

.125

.135

.140

.128

.145

.170

.160

.159

.120

.099

.250

.240

.195

.150

.290

.220

CFM

48

72

72

68

190

246

259

217

590

765

850

710

1010

1370

1325

1270

620

450

2760

2650

1935

1035

3690

2415

72,000

109,000

104,000

34,000

330,000

377,000

330,000

222,000

1,200,000

1,330,000

1,260,000

710,000

1,970,000

2,460,000

2,230,000

1,470,000

650,000

440,000

4,000,000

3,250,000

2,100,000

1,100,000

5,200,000

3,750,000

Gas Firing

with Barometric

Draft Control

390

0

F

Flue Gas

S.P.

.047

.053

.052

.042

.085

.090

.085

.075

.143

.150

.145

.115

.175

.185

.182

.158

.113

.095

.260

.240

.175

.125

.270

.220

CFM

36

55

52

17

166

190

166

110

603

653

615

357

989

1240

1120

740

340

220

2010

1660

1079

527

2440

1660

58,000

92,000

74,000

25,000

295,000

300,000

230,000

123,000

1,100,000

1,100,000

840,000

400,000

1,700,000

1,900,000

1,500,000

825,000

350,000

200,000

3,300,000

2,100,000

1,200,000

503,000

3,600,000

2,900,000

Oil Firing

with Barometric

Draft Control

530

0

F

Flue Gas

S.P.

.048

.057

.052

.035

.092

.093

.080

.065

.147

.148

.136

.100

.180

.180

.170

.135

.095

.075

.230

.190

.150

.110

.240

.218

CFM

33

48

39

13

163

169

118

65

566

566

440

211

900

1010

789

453

184

106

1763

1103

626

266

1870

1550

Therm

Volts   HZ   RPM   Watts   Amps   Prot.

115      60   1550      35        .43       Imp.

Prot.

115      60   1550      74        .96        Yes

115      60   1725   1/4 HP     5.4        Yes

115      60   1725   1/4 HP     5.4     Yes

115      60   1725   1/3 HP     6.0      Yes

115                                   12.6
208     60   1725   1 HP        6.2       Yes
230                                    6.3

208                                     6.3
230     60   1725   2 HP        6.4        No
460                                     3.2

Heater

BTU

Input

Heater

BTU

Input

Heater

BTU

Input

Electrical Specifications

IMPORTANT: Vents/Chimneys utilizing In-Line Draft Inducers must be vertically terminated above the roof line.
Do not use for side wall venting. Consult factory for proper side wall vent system options.

Tjernlund Products also offers:

Auto-Draft variable & fixed speed Inducers for roof top or side wall
venting.  Reduce vent diameters by up to 50% and overcome convolut-
ed vent layouts. Fan speed is automatically regulated based on a user
set manifold/vent pressure, resulting in perfect draft and true energy
savings. Virtually unlimited capacities.

Combustion Air In-Forcers provide dedicated combustion air for safer,
more efficient equipment operation. Eliminates burner control lockouts
& oil odors associated with backdrafting. Ideal for "confined space" and
electric to oil or gas conversions. Residential and commercial fixed &
variable speed capacities up to 6000 CFM available. 

Auto-Draft

®

Inducer

Combustion Air 
In-Forcer

Note: Tjernlund
Products Inc. reserves
the right to make
changes to specifica-
tions without notice.