(950-8302) CRAWL SPACE VENTILATOR T-STAT REPLACEMENT KIT
Disconnect power or unplug 115 VAC power cord before
servicing the Crawl Space Ventilator.
1. Remove Crawl Space Ventilator from wall.
IMPORTANT:
Note set-
ting of dehumidistat (if equipped) so it can be reset when finished.
Remove BLACK T-stat leads.
2. Use caution and drill out (2) T-stat rivets from exterior mounting
plate with a 5/32” drill bit, (See Diagram A).
3. Insert (2) 6-32 x 1/4” studs through mounting plate and T-stat and
tighten keps nuts. Replace BLACK T-stat leads.
4. Reinstall Crawl Space Ventilator in opening.
5. Reestablish 115 VAC power and cycle Crawl Space Ventilator “on” to verify proper operation. Reset dehumidistat (if equipped).
NOTE:
If outside temperature is below 50
o
F, T-stat may not allow Ventilator to turn on.
Rev. 10/06
Copyright © 2006, Tjernlund Products, Inc. All rights reserved.
P/N 8504132
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
EXTERIOR VIEW
Model V1 Shown
Drill out (2) T-stat
rivets on exterior
mounting plate with
5/32” drill bit.
DIAGRAM A