background image

2. To facilitate installation and reduce vibration we have included 2 mounting 

brackets, 2 rubber isolaters and 2 rubber grommets. One of the brackets 
may be used temporarily as a third hand while positioning it for permanent
installation.

3. When installing the Power Venter for horizontal mount, install one of the 

brackets to the electrical box using the nut/screw provided. Install the 
other  to the damper rod as shown to the right. When installing the Power 
Venter for vertical mount, only one bracket is needed.  This bracket 
should be mounted to the motor as shown to the right.  Temporarily 
support the Power Venter using wire or a ladder and assemble the mount-
ing brackets,(See Diagram F).

4. Install plumbers strap from the Power Venter to the floor joist,(See 

Diagram F).

5. Install 4 inch vent pipe from the Power Venter inlet to the appliance flue 

outlet avoiding elbows when possible.

ELECTRICAL WIRING

INSTALLATION RESTRICTIONS

1.The installer must ensure that all electrical connections between the appliance and Power Venter are tight and that all wires are 

positioned and secured so they cannot come in contact with high temperature locations.  Use adequate conduit supports where 
necessary.

2. The installer must ensure that the internal appliance transformer is rated no lower than 40VA..
3. The installer must ensure that the heat anticipator in the comfort thermostat is adjusted according to the thermostat manufacturers 

recommendation.

4.  All wiring From the Power Venter to the appliance must be appropriate Class 1 wiring as follows:  installed in rigid metal conduit, 

intermediate metal conduit, rigid non-metallic conduit, electrical metallic tubing Type MI, Type MC Cable, or otherwise be suitably 
protected from physical damage.

5. The Fan Proving Switch is not suitable for loads which exceed the limitations below.  The electrical  contact ratings for the Fan 

Proving Switch are as follows:

3 AMPS (full load) at 120VAC; 28VA Pilot Duty (1.16 Amps) at 24VAC; 125VA Pilot Duty at 120VAC

6.  All 24V wiring must be at least 18 AWG.  All 115V wiring must be at least 14 AWG.
7.  All wiring must be in compliance with local codes or in their absence, with the latest Edition of the National Electric  Code (NFPA #70).
8.  Disconnect 115V power before attempting to wire the Power Venter to the appliance.  Power may be disconnected by means of 

the appliance circuit breaker/fuse.

GPAK-J/GPAK-1 SEQUENCE OF OPERATION WIRED TO GAS VALVE:

As the thermostat/aquastat senses a need for heat, the internal switch of the thermostat /aquastat will close.  The switch closure com-
pletes the 24V electrical circuit to the internal controls of the appliance.  Before the 24V signal reaches the appliance gas valve, it is
interrupted by the Power Venter Relay and Fan Proving Switch.  When the Power Venter Relay coil receives the 24V signal, the con-
tact side closes completing the 115V circuit to the Power Venter motor.  The air movement generated by the Power Venter closes the
Fan Proving Switch and completes the circuit to the appliance gas valve.  The appliance gas valve will only receive power when the
appliance thermostat/aquastat is calling for heat and the Power Venter is operating.

GPAK-JT/GPAK-1T SEQUENCE OF OPERATION WIRED TO GAS VALVE:

As the thermostat/aquastat senses a need for heat, the internal switch of the thermostat/aquastat will close.  The Switch closure com-
pletes the 24V electrical circuit to the internal controls of the appliance.  Before the 24V signal reaches the appliance gas valve, it is
interrupted by the Power Venter Relay/Timer and Fan Proving Switch.  When the Power Venter Relay/Timer receives the 24V signal,
the contact side closes completing the 115V circuit to the Power Venter motor.  The air movement generated by the Power Venter
closes the Fan Proving Switch and completes the circuit to the appliance gas valve.  The appliance gas valve will only receive power
when the appliance thermostat/aquastat is calling for heat and the Power Venter is operating.  When the appliance thermostat/aquas-
tat is satisfied, 24V will be discontinued to the Relay/Timer and the Power Venter will continue to operate for a non-adjustable post
purge period of approximately 45 seconds.

NOTES: 

While it is impossible to include every possible wiring scenario, the following diagrams represent the most common.  If wiring the
GPAK to an appliance not equipped with the controls shown on the following diagrams, determine which terminals of the gas valve
are considered “HOT” and “COMMON” and follow the steps on the bottom of page 8 for GPAK-J/GPAK-1 or page 9 for 
GPAK-JT/GPAK-1T.

When wiring Power Venter to the gas valve wire all thermostats, zones, circulators and limits as would normally be done if venting into
a chimney.

NAT

If you are unable to wire the GPAK as outlined in these instructions, call our Customer Service department toll free at 1-800-255-4208
for fast assistance.

7

DIAGRAM F

Summary of Contents for 1

Page 1: ... SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION OR PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE REFERENCE MODELS DESCRIPTION GPAK J FOR GAS APPLIANCES WITH A BTU HR INPUT OF 120 000 OR LESS GPAK JT FOR GAS APPLIANCES WITH A BTU HR INPUT OF 120 000 OR LESS WHICH REQUIR...

Page 2: ... seconds after the appliance burner shuts off The GPAK J and GPAK 1 are equipped with a 24 115V Relay without the post purge feature GPAK SIZING Verify that the GPAK you are about to install is properly sized for the appliance 1 If installing the GPAK J or GPAK JT confirm that the BTU HR input of the appliance is 120 000 or less If installing the GPAK 1 or GPAK 1T confirm that the BTU HR input of ...

Page 3: ...arometric draft control Do not install the Power Venter on an appliance with an automatic valve having a manual opener unless the manual opener has been rendered inoperative or the automatic valve has been replaced with a valve not equipped with a manual opener Failure to install maintain and or operate the Power Venter in accordance with manufacturer s instructions may result in conditions which ...

Page 4: ... load controlled through the Fan Proving Switch must not exceed the electrical ratings marked on the Fan Prover INSTALLER NOTES 1 The installer must read and follow these instructions carefully to assure proper installation and operation of the GPAK 2 The installer must fill in the required information on the nameplate located on the Power Venter electrical box cover 3 The installer must affix the...

Page 5: ...ks openings or excessive corrosion Check both the limit control and fan control for proper operation 6 Applicable only to boilers Inspect for evidence of water or combustion product leaks Determine that the water pumps are in operating condition Test low water cutoffs automatic feed controls pressure and temperature limit controls and relief valves in accordance with the manufacturer s recommendat...

Page 6: ... the National Fuel Gas Code NFPA 54 All portions of the vent system under positive pressure during operation on the outlet side of Power Venter shall be designed and installed so as to prevent leakage of flue or vent gases into the building All appliances must enter the vent system on the inlet side of the Power Venter Provision shall be made to interlock the appliance s to prevent the flow of gas...

Page 7: ...Series Venting System may only be used with furnaces capable of being chimney vented It is not suitable for use on high efficiency condensing models POWER VENTER MOUNTING 1 Slide the outlet of the Power Venter over the inlet of the Vent Hood and connect them together using the provided screws See Diagram D If you are unable to make a direct connection to the Vent Hood vent pipe may be installed be...

Page 8: ...ce circuit breaker fuse GPAK J GPAK 1 SEQUENCE OF OPERATION WIRED TO GAS VALVE As the thermostat aquastat senses a need for heat the internal switch of the thermostat aquastat will close The switch closure com pletes the 24V electrical circuit to the internal controls of the appliance Before the 24V signal reaches the appliance gas valve it is interrupted by the Power Venter Relay and Fan Proving ...

Page 9: ...8 ...

Page 10: ...9 ...

Page 11: ...istance When the fan proving switch closes the furnace com bustion relay is energized Normal combustion sequence for the furnace begins Induced draft furnace blower starts its proving switch makes energizing ignition control and or gas valve DO NOT OPERATE THE FURNACE WITHOUT THE FAN PROVING SWITCH WIRED INTO THE 24V FURNACE CIRCUIT NOTE When Power Venter is interlocked with thermostat wire all zo...

Page 12: ...11 WIRING GPAK JT GPAK 1T WITH THERMOSTAT ...

Page 13: ...com bustion air opening s into the appliance room as outlined NFPA 54 NFPA 211 Tjernlund s IN FORCERTM engineered combustion air intakes provide a convenient interlocked way to supply combustion air to the utility room When installing a GPAK it is not necessary to supply any more combustion air than normally required when conventional venting SAFETY INTERLOCK COMBUSTION AIR TEST The Power Venter F...

Page 14: ...ports are located on the top of the motor Magnetek motors do not need to be oiled 2 The homeowner must semiannually inspect the Vent Hood and vent pipe for blockage corrosion and leaks 3 A vent system inspection must be performed annually by a qualified service agency The inspection should include the operation circuit check safety interlock test combustion air test and a visual inspection of the ...

Page 15: ... thermostat to call for heat Check for 24V across terminals 4 and 5 of the Relay Timer GPAK JT 1T or the coil of Ice Cube Relay with the BLUE and ORANGE leads attached GPAK J 1 SYMPTOM 2 POWER VENTER RUNS CONTINUOUSLY ERRATICALLY No Solution Replace Relay Timer GPAK JT 1T Part 950 0014 non adjustable or Part 950 1067 adjustable Relay Timer or for GPAK J 1 Ice Cube Relay Part 950 1040 Solution Cont...

Page 16: ...sary to prove the unit has been in service for under one year All receipts should include the date code of the Power Venter to ensure that the defective component corresponds with the complete unit This will help preclude possible credit refusal 15 SYMPTOM 3 POWER VENTER RUNS BUT APPLIANCE DOESN T No Bad Tube Wheel Dirty Contact Tjernlund Products for replace ment tube Clean Power Venter Wheel Sup...

Page 17: ...Any labor charges related to evaluating and replacing the defective part PERFORMANCE CURVES 16 TJERNLUND LIMITED ONE YEAR WARRANTY Tjernlund Products Inc warrants to the original purchaser of this product that the product will be free from defects due to faulty material or workmanship for a period of 1 year from the date of original purchase or delivery to the original purchaser whichever is earli...

Page 18: ...17 GPAK 1 GPAK 1T ...

Page 19: ... clearances are met before attempting to cut opening through exterior wall 4 Attach the template to the building exterior aligning the pilot holes on the template with the pilot holes drilled in step 2 5 Using a reciprocating saw cut an opening through the building siding wall board etc following the appropriate lines of the template 6 Slide the Vent Hood through the opening and fasten to exterior...

Reviews: