Introduction

Description

The   

THRC

  is  a  portable,  self-contained  high  efficiency  particulate  air  (HEPA)  filtration  system  with  an  optional 

ultraviolet lamp that helps to disinfect the filter face. The 

THRC

 is designed to easily and economically create a negative 

pressure isolation room that will meet OSHA and CDC TB guidelines. The 

THRC

  can be used as a positive pressure clean 

air recirculating system in clinics, waiting rooms, hospital emergency rooms and other confined areas or as a partial or 

complete exhausting system to create a negative pressure isolation room for possible use with patients known or 

suspected of having TB, SARS, COVID-19, or other infectious diseases. The 

THRC

  is available in two different sizes: the 

THRC

 

Low Flow (LF)

 and the 

THRC

 

High Flow (HF)

.  As a recirculating unit, the 

THRC

’s powerful motor/blower can deliver 

up to 370 CFM (628 m

3

/hr) for the 

THRC

 

LF

 and up to 800 CFM (1360 m

3

/hr) for the 

THRC

 

HF

  to provide a large number 

of room air changes per hour to minimize the spread of airborne diseases to patients and health care workers. As a 

negative pressure unit, the air passing through the HEPA filter is filtered of 99.99% of particles at 0.3 micron and may be 

exhausted directly to the exterior through a window, or through a wall, simply by connecting flexible ducting to the 6 in. (152 

mm) collar 

located on the top of the 

THRC

.

Features

Low Cost Isolation Room

The 

THRC

 is an easy and economical solution for creating a negative pressure isolation room. Simply roll the

THRC

 into a standard room, connect flexible ducting to the 6 in. (152 mm) collar on the top of the unit for partial

exhaust or to the optional 8 in. (204 mm) flanged collar for total exhaust, and vent the purified air to the exterior through

a window or wall.

Flexible Applications

The versatile 

THRC

 can be used as a clean air recirculating unit, a negative pressure unit, or as a split system

 

to

create  both  negative  pressure  and  clean  air  recirculation  by  simultaneously  exhausting  some  of  the  air  out  while

recirculating the remainder back into the room.

Small and Portable

The 

THRC

 can be rolled from one room to another and easily fits into areas with limited floor space.

Simple Maintenance

Both HEPA filter and prefilter are easily accessible for replacement by authorized personnel.

Adjustable Airflow

The 

THRC

 provides effective air filtration for a wide variety of room sizes.  The 

THRC

 LF

 utilizes a solid state

 

speed

control with airflows ranging from 70 to 370 CFM (118 to 628 m

3

/hr).  The 

THRC

 HF

 utilizes a three position

 

switch with

airflows ranging from 560 to 800 CFM (951 to 1360 m3/hr).

Low-High Clean Air Circulation Pattern

Room air, along with airborne contaminants, is drawn into the intake grill at the bottom while the purified air is discharged

at  a  high  velocity  from  the  exhaust  grill  located  at  the  top  of  the 

THRC

  to  generate  a  sweeping,  low-to-high  air

circulation pattern with adequate “reach” to optimize the clean breathing zone for patient and staff.

Quiet Operation

Applications

Hospital

Negative Pressure Rooms

Emergency Rooms

Waiting Rooms

Sputum Induction

Aerosol Pentamidine Treatment

Intensive Care Units

Bronchoscopy Rooms

Renal Dialysis Rooms

Summary of Contents for THRC High Flow

Page 1: ...Redefine your comfort zone www titus hvac com INSTALLATION OPERATION MANUAL Titus HEPA Room Cleaner High Flow Low Flow Configurations...

Page 2: ...rt zone www titus hvac com IOM THRC HF LF Table of Contents Introduction 3 Installation 4 Operation 5 Maintenance Service 7 Troubleshooting 10 Wiring Diagram 11 Specifications 13 Replacement Parts 14...

Page 3: ...e pressure isolation room Simply roll the THRC into a standard room connect flexible ducting to the 6 in 152 mm collar on the top of the unit for partial exhaust or to the optional 8 in 204 mm flanged...

Page 4: ...unit in its final operating position 3 Lock the wheel locks on the casters to keep the unit from accidental repositioning Initial Start Up NOTE THECDCREQUIRESTHATQUANTITATIVELEAKAGEANDFILTERPERFORMAN...

Page 5: ...he airflow indicator should not be used as the only guide for when a filter change is necessary The unit should be checked at each use to ensure recommended room air changes per hour are being met 2 T...

Page 6: ...aust Collar with Flange is available to convert the THRC unit to the 100 exhaust mode 1 Remove the front exhaust grille by pulling down and lifting out 2 Place the optional 8 inch 203mm exhaust collar...

Page 7: ...leaks Maintenance Service CAUTION PROPER PROTECTIVE EQUIPMENT AND MEASURES MUST BE USED AT ALL TIMES DURING UNIT CLEANING AND MAINTENANCE CHECK WITH YOUR SAFETY OFFICE TO ASSURE THE CLEANING SOLUTIONS...

Page 8: ...cess panel The rear panel may now be lifted off Primary Filter Replacement The CDC recommends that in any application HEPA filters should be maintained meticulously and should be carefully installed b...

Page 9: ...f the unit 4 Remove the old cord and replace with the new one by following the steps above in reverse order On Off Switch 1 With the back panel removed unplug the white connector on the switch and squ...

Page 10: ...r can now be disposed of as general waste Phenolic Decontamination ln facilities where the above decontamination procedures are prohibited or not feasible the unit can be disinfected by the following...

Page 11: ...amperage and distribution frequency 5 Check for down stream obstructions or erratic isolation room ventilation balance 6 Replace HEPA filter if the air velocity remains low after checking all other ca...

Page 12: ...12 IOM THRC Redefine your comfort zone www titus hvac com IOM THRC HF LF Wiring Diagrams Cont THRC Low Flow Wiring Diagram...

Page 13: ...r MERV8 multi pleat anti microbial pleated prefilter with frame Motor 1 3 HP 0 25 kW direct drive three speed continuous duty Exhaust Port 6 inch 152 4mm Duct Collar THRC Low Flow Dimensions 38 25 H x...

Page 14: ...RC 1 11055 8 inch A C Collar with Flange for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 THRC High Flow UV Part No Description Quantity S62954 WIRED Motor 1 3 HP 3 Speed 115V 1 S63...

Page 15: ...Plate for THRC 1 11055 8 inch A C Collar with Flange for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 THRC Low Flow UV Part No Description Quantity S267793 001 Motor 1 4 HP 3 Speed...

Page 16: ...16 IOM THRC Redefine your comfort zone www titus hvac com IOM THRC HF LF Airflow Measurement Testing...

Page 17: ...605 Shiloh Rd Plano TX 75074 ofc 972 212 4800 fax 972 212 4884 Redefine your comfort zone www titus hvac com...

Reviews: