ROOM CONTROL UNIT
20 Inputs 24 Outputs
INSTALLATION MANUAL
This device is used to control ON/OFF for lights
and other devices, electrical locks, 3
rd
-party curtain
motors, shutters, floor heaters, and it includes 20
Digital Inputs (dry inputs).
Automation Made Easy
Model: RCU-24R20Z
6
58921
79822
5
BARCODE (UPC-A)
PRODUCT INFORMATION
PRODUCT SPECIFICATIONS
Output switching voltage
Number of channels
24
Nominal voltage
0 – 230 V AC 50/60 Hz
Max. switching Voltage
440VAC / 125VDC
Output switching current
Nominal current per channel
Ch 1-12: 10A
Ch 13-24: 5A
Maximum total channels load
180 A / 230
Max switching current
CH 1-12: 16A
Ch 13-24: 6A
Max Continues current
Ch 1-12: 10A
Ch 13-24: 5A
Input
Number of channels
20
Input Type
Digital input. Open / Close
Length of connected wire
< 350 meter
TIS Bus
Number of devices on 1 line
Max. 64
Bus voltage
12-32 V DC
Current consumption (Normal)
<30 mA / 24 V DC
Current consumption (Peak)
<40 mA / 24 V DC
Protection
Reverse Polarity Protection
Operating and display
elements
Programming button/LED (PRG)
For assignment of the physical address
2 buttons
Manually ON/OFF and Programming
Functions
Lighting control ON/OFF Dimming
24 channels controlled separately
Curtain control
Can set 12 group of curtains (open/close) option
Fan speed control
Can set 8 group of Fan (low, med, high) option
Scenes
12 different scenarios
24 Digital inputs
Programmable inputs to connect to normal wall
switches and sensors
Dimensions
Width × Length × Height
215mm × 75mm × 91mm
Housing
Materials
ABS fire proof
Casing color
Black Gray
Button color
Silver
IP rating
IP 20