TROUBLESHOOTING
PRG Button Blinks Red Color
Rapidly
Reason:
The Module address conflicts with other
device in TIS network, you need to press and hold the
PRG button for 6 seconds so the module can get new
address
Device PRG LED is not Blinking;
Device not Powered
Reason:
Device is not powered on; no TIS-BUS 24V
supply connected to the device.
Device E1, E2 Button LED ON
but lights not ON
Reason 1:
Lights’ neutral wire not connected
Reason 2:
E1.E2 default setup in software has
changed
Wall Panels can’t Control the
Device Channels
Reason 1:
TIS-BUS connection has a problem; check
the wires and make sure there’s not a short in the
connection.
Reason 2:
Programming address is wrong.
Dry input is not turning the RCU
lights ON/OFF
Reason:
Either the default setting in software or the
RCU address has changed.
Channel is turning off by itself
after few seconds
Reason:
It is programmed as shutter / curtain
combination, and running time is enabled in the
software.