The rear box shall be mounted on the wall using four no.8 wood
screws.

If conduit is to be used then please follow the instructions below:

The drain feature must be drilled out using a 5mm drill if top 
or side entry conduit is used. Opening this drain hole will 
reduce the IP rating of the product.

If bottom entry conduit is used, there must be adequate 
drainage from the lowest point of the conduit.

With relevant cable entry cover removed. A waterproof cable 
or conduit entry must then be fitted in its place, and sealed 
using the washer supplied.

If two cable entry positions are used with metal conduit, 
then earth continuity between the conduits must be 
maintained.

If a product is installed with a built in isolating switch, then the
live and neutral supply must be connected to the relevant
terminal on the isolating switch. The protective conductor must
be connected to the earth terminal on the product. There are
spare terminals in the rear box for connecting earth loops.

All WPL switch products are provided with a neon locator for
locating the product in the dark (This is the only intended use for
this neon). To enable the neon to remain lit irrespective of switch
state the neon must be wired to a permanent L and N feed.

Ensure that the gasket is correctly fitted, and tighten the four
screws to fix the front cover in place. Do not overtighten. Use of
an electric screw driver is not recommended.

Operating instructions

For products with built in isolator:

To open the box lid, wipe off excess water from top surface, turn the
isolator switch to the off position (O position) and then open lid.

The box is opened by depressing the tab on the front (see figure 2).

Once the box lid is open, the isolating lever should not be turned
back to the on position.

Plugs may then be inserted into the sockets, and the socket
switches turned on.