TIME MARK B2522B Installation Instructions Download Page 1

DIMENSIONS 

DESCRIPTION

 

 

The 

Model  2522

  continuously  monitors  3-phase  power 

lines for abnormal conditions.  When properly adjusted, the 
Model 2522 will detect phase loss on a loaded motor even 
when regenerated voltage is present.

 

 

This unit consists of a solid-state voltage and phase-angle 
sensing  circuit,  driving  an  electromechanical  relay  with 
DPDT  contacts.  When  correct  voltage  and  phase  rotation 
are  applied,  the  internal  relay  will  energize.    A  fault 
condition  will  de-energize  the  relay.    When  the  fault  is 
corrected the Model 2522 will reset.

 

 

Both  automatic  and  manual  reset  versions  are  available. 
The Model 2522 does not require a neutral connection, and 
can  be  used  with  Wye  or  Delta  systems.  Adjustment 
ranges are sufficiently wide to allow for proper adjustment 
to existing conditions.  A failure indicator is provided to aid 
in adjustment and system troubleshooting. 

TYPICAL APPLICATION 

MODEL 2522 

3-Phase Monitor 

 

Detects Phase Loss, Low Voltage,  

     Phase Reversal

  

  Automatic or Manual Reset

   

  DPDT Relay Output

   

TIME MARK is a division of

Telephone:  Main -  (918) 438-1220 
 

 

 

Sales -  (800) 862-2875

 

Fax:  

 

 

 

(918) 437-7584 

 
E-mail:   

[email protected] 

Internet:  

http://www.time-mark.com 

11/2011 

© 2011   

TIME MARK CORPORATION

 

11440  Eas t Pine Stree t  

Tuls a,  Ok lahom a  74116  

Shows No Power Applied 

2.88”

2.44”

1.75”

3.52”

SPECIFICATIONS

 

 

AUTO Reset 
MANUAL Reset 

B2522B 

B2522BM 

2522B 

2522BM 

Nominal Voltage 

120VAC 

208/240VAC 

Max Input Voltage 

132VAC 

262VAC 

Adjustment Range 

85-120VAC 

160-240VAC 

Frequency 

60Hz 

60Hz 

Power Consumption 

.

75W 

1

.

5W 

Transient Protection 

2500 VRMS for 10ms  

Repeat Accuracy 

±0

.

1% of set-point  (fixed conditions)  

Response Time 

0

.

05 seconds  

Reset Time 

0

.

05 seconds  

Reset Type 

Automatic or Manual  

Dead Band 

2%  

Contact Rating 

DPDT     5 amps , 115VAC   resistive 

Max. Contact Rating 

870 VA, 30VDC, 300VAC  

Expected Relay Life   

Mech: 

 

10 million operations 

 

Elec:  

 

100,000 operations at rated load  

Operating Temp 

- 20º to +131º F  

Humidity Tolerance 

97% w/o condensation  

Enclosure Material 

ABS plastic  

Mounting 

*11-pin socket (order separately)  

Weight 

5 oz.  

*Order socket number  51X016 

 

Reviews: