DIMENSIONS
DESCRIPTION
The
Model 2522
continuously monitors 3-phase power
lines for abnormal conditions. When properly adjusted, the
Model 2522 will detect phase loss on a loaded motor even
when regenerated voltage is present.
This unit consists of a solid-state voltage and phase-angle
sensing circuit, driving an electromechanical relay with
DPDT contacts. When correct voltage and phase rotation
are applied, the internal relay will energize. A fault
condition will de-energize the relay. When the fault is
corrected the Model 2522 will reset.
Both automatic and manual reset versions are available.
The Model 2522 does not require a neutral connection, and
can be used with Wye or Delta systems. Adjustment
ranges are sufficiently wide to allow for proper adjustment
to existing conditions. A failure indicator is provided to aid
in adjustment and system troubleshooting.
TYPICAL APPLICATION
MODEL 2522
3-Phase Monitor
Detects Phase Loss, Low Voltage,
Phase Reversal
Automatic or Manual Reset
DPDT Relay Output
TIME MARK is a division of
Telephone: Main - (918) 438-1220
Sales - (800) 862-2875
Fax:
(918) 437-7584
E-mail:
Internet:
http://www.time-mark.com
11/2011
© 2011
TIME MARK CORPORATION
11440 Eas t Pine Stree t
Tuls a, Ok lahom a 74116
Shows No Power Applied
2.88”
2.44”
1.75”
3.52”
SPECIFICATIONS
AUTO Reset
MANUAL Reset
B2522B
B2522BM
2522B
2522BM
Nominal Voltage
120VAC
208/240VAC
Max Input Voltage
132VAC
262VAC
Adjustment Range
85-120VAC
160-240VAC
Frequency
60Hz
60Hz
Power Consumption
.
75W
1
.
5W
Transient Protection
2500 VRMS for 10ms
Repeat Accuracy
±0
.
1% of set-point (fixed conditions)
Response Time
0
.
05 seconds
Reset Time
0
.
05 seconds
Reset Type
Automatic or Manual
Dead Band
2%
Contact Rating
DPDT 5 amps , 115VAC resistive
Max. Contact Rating
870 VA, 30VDC, 300VAC
Expected Relay Life
Mech:
10 million operations
Elec:
100,000 operations at rated load
Operating Temp
- 20º to +131º F
Humidity Tolerance
97% w/o condensation
Enclosure Material
ABS plastic
Mounting
*11-pin socket (order separately)
Weight
5 oz.
*Order socket number 51X016