Introduction

The PDFM1500.1 utilises passive infrared technology to

detect heat radiation of moving human bodies.Upon

detection, the 

 lighting load will illuminate for

a user-determined time period. An integral daylight

sensor ensures all day or night-only operation.
Important Information: Light Pollution and

Considerate Lighting

Please be aware of the annoyance over-lighting an area

can cause to your immediate neighbours. Light

pollution caused by incorrectly installing a unit or

over-lighting an area can be limited by carefully

considering the location and position of your unit

before installation. The light spread on all halogen

floodlights can be reduced by angling the floodlight

downwards on the mounting bracket. This will also

concentrate the light on your property and limit the

potential inconvenience of the light shining into your

neighbours windows etc.

Please see Selecting a Location for information on

choosing the optimum location for any security light

controlled by this unit.

A

Parts included

• PIR  Sensor unit.

• Instruction manual. Please keep safe for future 

reference.

• Accessory Pack. Includes cable clamp wiring cover
   and 2 x screws.

Tools and parts needed

• 3 core flexible cable.

• Electric/hand-held drill & bits.

• 65mm or 2.5 inch diameter hole 

r.

• Terminal or Electricians screwdriver.

• Small philips screwdriver.

• Wire 

 

• Suitable mains interconnect cable.

This product is suitable for indoor use only. Connected

load must not exceed maximum 2300W halogen

or 400W fluorescent/low energy lighting.

Do not 

 to install if you are su

ff

ering from

nausea or dizzy spells or on medication with similar

side e

ff

ects. If in any doubt, consult a qualified

electrician.

Not suitable for use with discharge lighting.

Selecting a location

The motion detector has a number of detection zones,

at various vertical and horizontal angles as shown (see

diagram A).
A moving human body needs to cross/enter one of

these zones to activate the sensor. The best all-round

coverage is achieved with the unit mounted at the
optimum height of 3m. 

 up

Walk Test Procedure

TIME - Fully anti-clockwise (Test Mode)

DUSK - Fully clockwise

The unit will now operate during daytime as well as at

night, illuminating the lamp for approx. 5 seconds each

time. This allows testing to be carried out to establish

whether the sensor is covering the required area.

The lamp will immediately illuminate as the unit goes

through its "warm-up" period. A

 approximately 1 

minute the lamp will extinguish. Try to remain outside

the detection area during the warm-up period.

Walk around the sensor to establish the detection area.

The sensor will detect within an approximately 9 metre

diameter circle from the centre of the sensor location with a

3m ceiling.

As you cross a detection "zone" the lamp will illuminate.

Now stand still until the lamp extinguishes (this should

take approx. 5 seconds).

Start moving 

 As you cross each

 "zone" the lamp will illuminate.

Repeat the above, walking at various distances and

angles to the unit. This will help you to confirm the

detection 

.

B

Side View

Top View

Time On 

Lux 

Dusk/Dawn 

Careful positioning of the sensor will be required to

ensure optimum performance. See diagram A detailing

detection range and direction.
The sensor is more sensitive to movement ACROSS  its

field of vision than to movement directly TOWARDS

(see diagram B). Therefore position the unit so that the

sensor looks ACROSS  the likely approach path.
Avoid positioning the sensor where there are any

sources of heat in the detection area (extractor fans,

tumble dryer exhausts etc.) including opposite any

other light sources such as other security lights.
Reflective surfaces (ie pools of water or white-painted

walls) and overhanging branches may cause false

activation under extreme conditions.
During extreme weather conditions the motion sensor

may exhibit unusual behaviour. This does not indicate

a fault with the sensor. Once normal weather conditions

return, the sensor will resume normal operation.

Connection

Connect the mains supply cable Live core (brown) to L
and Neutral core(Blue) to N terminal.  
Connect the lighting cable Neutral core (blue) to N 
and Lighting Live core (brown) to the L1 terminal 
on the unit as follows (see diagram D):-

NEUTRA L (Blue) 

N

NEUTRA L (Blue) 

N

LIVE  (Brown) 

L1

LIVE  (Brown) 

L

Set the two adjustment controls on the side of the 
unit (diagram C) to the following positions:

When wiring is complete, fit the cable clamp

 wiring

cover to the sensor unit with the 2 screws provided.
(diagram E) 

 TIME  -Fully anti-clockwise (Test mode).
DUS K - Fully  clockwise.
Push back the locating springs (diagram D) and feed

the unit into the ceiling void via the 65mm hole. The

locating springs will now fold back and hold the

PDFM1500.1 in place.

Installation

IMPO RTANT

Switch o

ff

 the electricity at the fuse box by removing the

relevant fuse or switching o

ff

the circuit breaker before proceeding with the installation.

All  

 should be installed by competent person in

accordance with IEE  Wiring Regulations (BS7671)

 choosing a suitable location (see previous section)

install the unit as follows:
The unit is suitable for connection to a 230 V ac 50Hz

electricity supply. It is suggested that 3-core round

flexible cable of 1.5 sq. mm gauge is used. An isolating

switch should be installed to switch the power to the unit

ON & OFF. This allows the sensor to be easily switched 
o

ff

 when not required or for maintenance purposes.

Mark the position of the 65mm diameter locating hole

centre taking care to avoid ceiling joists and other

obstructions within the 65mm diameter. Drill a pilot

hole to take the centre 

 of the hole 

r. Use the

hole 

 to cut the required hole.

 

 

Levering area

C

D

Sensor

E

Cable clamp

Wiring cover

L1

N

Switched

Load

OUT

Mains 

Supply 

IN

L

N

L

ocating

springs

pulled

back

Min 12mm
Max 20mm

3m

3m

Presence detection

Motion detection

9m

360

More

sensitive

Less

sensitive

5

2

3

4

6

Introduction

The PDFM1500.1 utilises passive infrared technology to

detect heat radiation of moving human bodies.Upon

detection, the 

 lighting load will illuminate for

a user-determined time period. An integral daylight

sensor ensures all day or night-only operation.
Important Information: Light Pollution and

Considerate Lighting

Please be aware of the annoyance over-lighting an area

can cause to your immediate neighbours. Light

pollution caused by incorrectly installing a unit or

over-lighting an area can be limited by carefully

considering the location and position of your unit

before installation. The light spread on all halogen

floodlights can be reduced by angling the floodlight

downwards on the mounting bracket. This will also

concentrate the light on your property and limit the

potential inconvenience of the light shining into your

neighbours windows etc.

Please see Selecting a Location for information on

choosing the optimum location for any security light

controlled by this unit.

A

Parts included

• PIR  Sensor unit.

• Instruction manual. Please keep safe for future 

reference.

• Accessory Pack. Includes cable clamp wiring cover
   and 2 x screws.

Tools and parts needed

• 3 core flexible cable.

• Electric/hand-held drill & bits.

• 65mm or 2.5 inch diameter hole 

r.

• Terminal or Electricians screwdriver.

• Small philips screwdriver.

• Wire 

 

• Suitable mains interconnect cable.

This product is suitable for indoor use only. Connected

load must not exceed maximum 2300W halogen

or 400W fluorescent/low energy lighting.

Do not 

 to install if you are su

ff

ering from

nausea or dizzy spells or on medication with similar

side e

ff

ects. If in any doubt, consult a qualified

electrician.

Not suitable for use with discharge lighting.

Selecting a location

The motion detector has a number of detection zones,

at various vertical and horizontal angles as shown (see

diagram A).
A moving human body needs to cross/enter one of

these zones to activate the sensor. The best all-round

coverage is achieved with the unit mounted at the
optimum height of 3m. 

 up

Walk Test Procedure

TIME - Fully anti-clockwise (Test Mode)

DUSK - Fully clockwise

The unit will now operate during daytime as well as at

night, illuminating the lamp for approx. 5 seconds each

time. This allows testing to be carried out to establish

whether the sensor is covering the required area.

The lamp will immediately illuminate as the unit goes

through its "warm-up" period. A

 approximately 1 

minute the lamp will extinguish. Try to remain outside

the detection area during the warm-up period.

Walk around the sensor to establish the detection area.

The sensor will detect within an approximately 9 metre

diameter circle from the centre of the sensor location with a

3m ceiling.

As you cross a detection "zone" the lamp will illuminate.

Now stand still until the lamp extinguishes (this should

take approx. 5 seconds).

Start moving 

 As you cross each

 "zone" the lamp will illuminate.

Repeat the above, walking at various distances and

angles to the unit. This will help you to confirm the

detection 

.

B

Side View

Top View

Time On 

Lux 

Dusk/Dawn 

Careful positioning of the sensor will be required to

ensure optimum performance. See diagram A detailing

detection range and direction.
The sensor is more sensitive to movement ACROSS  its

field of vision than to movement directly TOWARDS

(see diagram B). Therefore position the unit so that the

sensor looks ACROSS  the likely approach path.
Avoid positioning the sensor where there are any

sources of heat in the detection area (extractor fans,

tumble dryer exhausts etc.) including opposite any

other light sources such as other security lights.
Reflective surfaces (ie pools of water or white-painted

walls) and overhanging branches may cause false

activation under extreme conditions.
During extreme weather conditions the motion sensor

may exhibit unusual behaviour. This does not indicate

a fault with the sensor. Once normal weather conditions

return, the sensor will resume normal operation.

Connection

Connect the mains supply cable Live core (brown) to L
and Neutral core(Blue) to N terminal.  
Connect the lighting cable Neutral core (blue) to N 
and Lighting Live core (brown) to the L1 terminal 
on the unit as follows (see diagram D):-

NEUTRA L (Blue) 

N

NEUTRA L (Blue) 

N

LIVE  (Brown) 

L1

LIVE  (Brown) 

L

Set the two adjustment controls on the side of the 
unit (diagram C) to the following positions:

When wiring is complete, fit the cable clamp

 wiring

cover to the sensor unit with the 2 screws provided.
(diagram E) 

 TIME  -Fully anti-clockwise (Test mode).
DUS K - Fully  clockwise.
Push back the locating springs (diagram D) and feed

the unit into the ceiling void via the 65mm hole. The

locating springs will now fold back and hold the

PDFM1500.1 in place.

Installation

IMPO RTANT

Switch o

ff

 the electricity at the fuse box by removing the

relevant fuse or switching o

ff

the circuit breaker before proceeding with the installation.

All  

 should be installed by competent person in

accordance with IEE  Wiring Regulations (BS7671)

 choosing a suitable location (see previous section)

install the unit as follows:
The unit is suitable for connection to a 230 V ac 50Hz

electricity supply. It is suggested that 3-core round

flexible cable of 1.5 sq. mm gauge is used. An isolating

switch should be installed to switch the power to the unit

ON & OFF. This allows the sensor to be easily switched 
o

ff

 when not required or for maintenance purposes.

Mark the position of the 65mm diameter locating hole

centre taking care to avoid ceiling joists and other

obstructions within the 65mm diameter. Drill a pilot

hole to take the centre 

 of the hole 

r. Use the

hole 

 to cut the required hole.

 

 

Levering area

C

D

Sensor

E

Cable clamp

Wiring cover

L1

N

Switched

Load

OUT

Mains 

Supply 

IN

L

N

L

ocating

springs

pulled

back

Min 12mm
Max 20mm

3m

3m

Presence detection

Motion detection

9m

360

More

sensitive

Less

sensitive

5

2

3

4

6

Introduction

The PDFM1500.1 utilises passive infrared technology to

detect heat radiation of moving human bodies.Upon

detection, the 

 lighting load will illuminate for

a user-determined time period. An integral daylight

sensor ensures all day or night-only operation.
Important Information: Light Pollution and

Considerate Lighting

Please be aware of the annoyance over-lighting an area

can cause to your immediate neighbours. Light

pollution caused by incorrectly installing a unit or

over-lighting an area can be limited by carefully

considering the location and position of your unit

before installation. The light spread on all halogen

floodlights can be reduced by angling the floodlight

downwards on the mounting bracket. This will also

concentrate the light on your property and limit the

potential inconvenience of the light shining into your

neighbours windows etc.

Please see Selecting a Location for information on

choosing the optimum location for any security light

controlled by this unit.

A

Parts included

• PIR  Sensor unit.

• Instruction manual. Please keep safe for future 

reference.

• Accessory Pack. Includes cable clamp wiring cover
   and 2 x screws.

Tools and parts needed

• 3 core flexible cable.

• Electric/hand-held drill & bits.

• 65mm or 2.5 inch diameter hole 

r.

• Terminal or Electricians screwdriver.

• Small philips screwdriver.

• Wire 

 

• Suitable mains interconnect cable.

This product is suitable for indoor use only. Connected

load must not exceed maximum 2300W halogen

or 400W fluorescent/low energy lighting.

Do not 

 to install if you are su

ff

ering from

nausea or dizzy spells or on medication with similar

side e

ff

ects. If in any doubt, consult a qualified

electrician.

Not suitable for use with discharge lighting.

Selecting a location

The motion detector has a number of detection zones,

at various vertical and horizontal angles as shown (see

diagram A).
A moving human body needs to cross/enter one of

these zones to activate the sensor. The best all-round

coverage is achieved with the unit mounted at the
optimum height of 3m. 

 up

Walk Test Procedure

TIME - Fully anti-clockwise (Test Mode)

DUSK - Fully clockwise

The unit will now operate during daytime as well as at

night, illuminating the lamp for approx. 5 seconds each

time. This allows testing to be carried out to establish

whether the sensor is covering the required area.

The lamp will immediately illuminate as the unit goes

through its "warm-up" period. A

 approximately 1 

minute the lamp will extinguish. Try to remain outside

the detection area during the warm-up period.

Walk around the sensor to establish the detection area.

The sensor will detect within an approximately 9 metre

diameter circle from the centre of the sensor location with a

3m ceiling.

As you cross a detection "zone" the lamp will illuminate.

Now stand still until the lamp extinguishes (this should

take approx. 5 seconds).

Start moving 

 As you cross each

 "zone" the lamp will illuminate.

Repeat the above, walking at various distances and

angles to the unit. This will help you to confirm the

detection 

.

B

Side View

Top View

Time On 

Lux 

Dusk/Dawn 

Careful positioning of the sensor will be required to

ensure optimum performance. See diagram A detailing

detection range and direction.
The sensor is more sensitive to movement ACROSS  its

field of vision than to movement directly TOWARDS

(see diagram B). Therefore position the unit so that the

sensor looks ACROSS  the likely approach path.
Avoid positioning the sensor where there are any

sources of heat in the detection area (extractor fans,

tumble dryer exhausts etc.) including opposite any

other light sources such as other security lights.
Reflective surfaces (ie pools of water or white-painted

walls) and overhanging branches may cause false

activation under extreme conditions.
During extreme weather conditions the motion sensor

may exhibit unusual behaviour. This does not indicate

a fault with the sensor. Once normal weather conditions

return, the sensor will resume normal operation.

Connection

Connect the mains supply cable Live core (brown) to L
and Neutral core(Blue) to N terminal.  
Connect the lighting cable Neutral core (blue) to N 
and Lighting Live core (brown) to the L1 terminal 
on the unit as follows (see diagram D):-

NEUTRA L (Blue) 

N

NEUTRA L (Blue) 

N

LIVE  (Brown) 

L1

LIVE  (Brown) 

L

Set the two adjustment controls on the side of the 
unit (diagram C) to the following positions:

When wiring is complete, fit the cable clamp

 wiring

cover to the sensor unit with the 2 screws provided.
(diagram E) 

 TIME  -Fully anti-clockwise (Test mode).
DUS K - Fully  clockwise.
Push back the locating springs (diagram D) and feed

the unit into the ceiling void via the 65mm hole. The

locating springs will now fold back and hold the

PDFM1500.1 in place.

Installation

IMPO RTANT

Switch o

ff

 the electricity at the fuse box by removing the

relevant fuse or switching o

ff

the circuit breaker before proceeding with the installation.

All  

 should be installed by competent person in

accordance with IEE  Wiring Regulations (BS7671)

 choosing a suitable location (see previous section)

install the unit as follows:
The unit is suitable for connection to a 230 V ac 50Hz

electricity supply. It is suggested that 3-core round

flexible cable of 1.5 sq. mm gauge is used. An isolating

switch should be installed to switch the power to the unit

ON & OFF. This allows the sensor to be easily switched 
o

ff

 when not required or for maintenance purposes.

Mark the position of the 65mm diameter locating hole

centre taking care to avoid ceiling joists and other

obstructions within the 65mm diameter. Drill a pilot

hole to take the centre 

 of the hole 

r. Use the

hole 

 to cut the required hole.

 

 

Levering area

C

D

Sensor

E

Cable clamp

Wiring cover

L1

N

Switched

Load

OUT

Mains 

Supply 

IN

L

N

L

ocating

springs

pulled

back

Min 12mm
Max 20mm

3m

3m

Presence detection

Motion detection

9m

360

More

sensitive

Less

sensitive

5

2

3

4

6

Locating springs fitted position

Min 12mm
Max 20mm

Time On 

setting

Lux

Dusk/Dawn

setting

Summary of Contents for PDFM1500

Page 1: ...360 Flush Mount Ceiling PIR Light Controller Model PDFM1500 I n s t a l l a t i o n O p e r a t i n g I n s t r u c t i o n s...

Page 2: ...nceof thelight shining intoyour neighbourswindows etc Please see Selectinga Locationfor informationon choosingtheoptimumlocationfor any security light controlled by this unit A B Side View Top View 3m...

Page 3: ...aylight night onlyoperation ight Pollution and noyanceover lightingan area iateneighbours Light rrectly installinga unit or belimited by carefully and positionof your unit ght spreadon all halogen dby...

Page 4: ...es as shown see diagram A A moving human body needs to cross enter one of these zones to activate the sensor The best all round coverage is achieved with the unit mounted at the optimum height of 3m C...

Page 5: ...uitable for connection to a 230 V ac 50Hz electricity supply It is suggested that 3 core round flexible cable of 1 5 sq mm gauge is used An isolating switch should be installed to switch the power to...

Page 6: ...NEUTRAL Blue N LIVE Brown L1 Load When wiring is complete fit the cable clamp wiring cover to the sensor unit with the 2 screws provided diagram E Set the two adjustment controls on the side of the un...

Page 7: ...uminate Now stand still until the lamp extinguishes this should take approx 5 seconds Start moving again after 2 seconds As you cross each zone the lamp will illuminate Repeat the above walking at var...

Page 8: ...n a clockwise direction until a point is reached where the lamp illuminates in response to a hand moving below the unit Leave the control set at this point At this position the unit should become oper...

Page 9: ...r false activation from heat wind or reflective source Check that the power is switched ON at the power supply or isolation switch Turn OFF the power to the unit and check the wiring connections Check...

Page 10: ...t Dusk Level Adjustment Environmental Protection Up to 10 metres diameter 4 5m Radius at mounting height of 3m Up to 3 metres diameter 1 5m Radius at mounting height of 3m 360 230 V AC 50Hz 1500W Halo...

Page 11: ...re within 3 years of the date of purchase please return it to your supplier in the first year with proof of purchase and it will be replaced free of charge For years 2 and 3 or any difficulty in the f...

Page 12: ...imeguard Limited Victory Park 400 Edgware Road London NW2 6ND Sales Office 020 8452 1112 or email csc timeguard com For a product brochure please contact Zerofour September 2011 or email helpline time...

Reviews: