Technical Data
Technical Data
Details
Input
Voltage range (Un)
100
–
400 V (L-L) main voltage (nominal)
Measuring range
1
–
520 V TRMS L-L 50/60 Hz or
1 - 520 V TRMS L-
L 16⅔ Hz
Configurable measuring range
0 - 500 V L-L / 0 - 300 V L-N
Frequency
50/60 Hz (
10…40….70…120 Hz
)
16
⅔
Hz (
10…15….18…120 Hz
)
Overload voltage
1.5 x Un
–
continuously, 2 x Un
–
10 s
Consumption
U x 1 mA / phase
Current (In)
1
–
5 A
Measuring range
5 mA
–
10 A TRMS
Configurable measuring range
0
–
10 A
Overload current
2 x In continuously, 10 x In 15 s, 40 x In 1 s
Consumption
<0.05 VA / phase
Auxiliary power supply
24
–
230 VDC / 90
–
230 V AC ±10 %
Burden
max 7.1 W / 15 VA
Output
Analog outputs
4 or 2
Programmable range
±20mA, ±5 mA, ±10V (settings within the range)*
Resolution
16 bits
External resistance load
Current output: max 750
Ω (15
V)
Voltage output: min 750
Ω
Response time
<100 msec
Digital Outputs
2 (Energy pulse output)
Communication
Modbus RS485 (RTU)
General Data
Accuracy
0.2 (Ref. temp. 23 °C)
Galvanic isolation
Supply, in- and output are galvanically isolated
Connection terminals / Torque
Input and Auxiliary power supply: 6 mm
2
/ 0.8 Nm
Output: 2.5 mm
2
/ 0.5 Nm
Humidity
95 % non-condensing
USB
USB Micro-B, port for configuration
Temperature
-
10…+55 °C (operation)
-
40…+70 °C (storage)
Temperature coefficient < 0.1 % / 10 °C
Test voltage
4 kV AC /1 min
Inputs
overvoltage cat. III
Pollution degree
2
Dimension (W x H x D)
70 x 132 x 101 mm
Weight
330 gr
Protection
IP40 (housing), IP20 (terminals)
Standards
SS-EN 60688 Transducers
SS-EN 61010-1 Safety
EN 61000-6-2 / -6-4 / -6-5
*
Depending on the version